1592009211 XW10L-V GB r1.0 30.05.2011 

                           XW10L – XW10V 

3/4 

6.7

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “I2P” parameters. 
 CL : the digital input is activated by closing the contact. 

 OP : the digital input is activated by opening the contact 

 

7.

 

INSTALLATION AND MOUNTING 

Instruments  XW10L  shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two 
screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). 

Instruments XW10V shall be mounted on vertical panel, in a 72x56 mm hole, and fixed using screws 

 

3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RGW-V).  
To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). The temperature 
range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations, corrosive 
gases, excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate by 
the cooling holes. 

 

7.1

 

XW10V: CUT OUT   

 

56

72

40

83

,5

 

7.2

 

XW10L: CUT OUT 

 

165

150

31

+0.5

-0

+0

.5

-0

+1

-1

Ø3 x2

 

 

7.3

 

XW10L: MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD 

 

CLICK!

1

2

2

3

3

1

1

 

7.4

 

XW10L: MOUNTING WITH KEYBOARD COVER OPENING UPWARD 

 

CLICK!

1

2

2

2

3

3

1

1

 

8.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 
mm

for the digital and analogue inputs. Relays and power supply have a Faston connection (6,3mm). 

Heat-resistant cables have to be used. Before connecting cables make sure the power supply complies 
with the instrument’s requirements. Separate the probe cables from the power supply cables, from the 
outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case 
of heavier loads use a suitable external relay. 
N.B. Maximum current allowed for all the loads is 20A. 

8.1

 

PROBE CONNECTIONS 

The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. 
It is recommended to place the thermostat probe away from air streams to correctly measure the 
average room temperature.. 

9.

 

USE OF THE PROGRAMMING “HOT KEY “ 

The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the 
“Hot Key” and vice-versa. 

9.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1.

 

Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, 
insert the “Hot Key” and then turn the Wing ON. 

2.

 

Automatically the parameter list of the “Hot Key” is downloaded into the Wing memory, the 
DoL” message is blinking. After 10 seconds the instrument will restart working with the new 
parameters. 

3.

 

Turn OFF the instrument remove the “Hot Key”, plug in  the TTL serial cable, then turn it ON 
again. 

At the end of the data transfer phase the instrument displays the following messages: 
end “ for right programming. The instrument starts regularly with the new programming. 
err” for failed programming. In this case turn the unit off and then on if you want to restart the 
download again or remove the “Hot key” to abort the operation. 

 

9.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1.

 

Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if 
present; then turn it ON again. 

2.

 

When the Wing unit  is ON, insert the “Hot key” and push 

o

 

key; the  "uPL"  message 

appears. 

3.

 

Push “SET” key to start the UPLOAD; the “uPL” message is blinking. 

4.

 

Turn OFF the instrument remove the “Hot Key”, plug in  the TTL serial cable, then turn it ON 
again. 

At the end of the data transfer phase the instrument displays the following messages: 
end “ for right programming. 
err” for failed programming. In this case push “SET” key if you want to restart the programming again 
or remove the not programmed “Hot key”. 

10.

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“P1” 

Thermostat probe failure 

Alarm output ON; Compressor output according to 
parameters “COn” and “COF” 

“HA” 

Maximum temperature alarm 

Alarm output ON; Other outputs unchanged 

“LA” 

Minimum temperature alarm 

Alarm output ON; Other outputs unchanged 

“EE”   Data or memory failure 

Alarm output ON; Other outputs unchanged 

“dA” 

Door switch alarm 

Alarm output ON; Other outputs unchanged 

“EAL”  External alarm 

Alarm output ON; Other outputs unchanged 

“BAL”  Serious external alarm 

Alarm output ON; Other outputs OFF 

“PAL”  Pressure switch alarm 

Alarm output ON; Other outputs OFF 

 
The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is 
flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is 
displayed for about 3s. 

10.1

 

SILENCING BUZZER 

Once the alarm signal is detected the buzzer can be silenced by pressing any key.  

10.2

 

 “EE” ALARM 

The 

dIXEL

 instruments are provided with an internal check for the data integrity. Alarm “EE” flashes 

when a failure in the memory data occurs. In such cases the alarm output is enabled. 

Содержание Wing Series

Страница 1: ...fferential the compressor is started and then turned off when the temperature reaches the set point value again In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters COn and COF 3 3 CH HT HEATING APPLICATION The Hy value is automatically set under the Set Point If the temperature decreases and reaches set point minus differential the regulation ...

Страница 2: ...C Ab ALL 110 C or 230 F when this temperature is reached and after the ALd delay time the HA alarm is enabled ALL Low temperature alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled AFH Temperature alarm differential 0 1 25 5 C 1 45 F Intervention differential for temperature alarm set point always positi...

Страница 3: ...ove the TTL serial cable if present insert the Hot Key and then turn the Wing ON 2 Automatically the parameter list of the Hot Key is downloaded into the Wing memory the DoL message is blinking After 10 seconds the instrument will restart working with the new parameters 3 Turn OFF the instrument remove the Hot Key plug in the TTL serial cable then turn it ON again At the end of the data transfer p...

Страница 4: ...1 digit 12 CONNECTIONS Room Probe XW10V Comp Line Neutral Light 19 12 5 6 7 8 9 10 11 2 3 4 17 18 20 21 Digital Input 20A 250Vac MAX 20A 16A 250Vac Digital inp Room Probe XW10L 20A 250Vac MAX 20A Comp Line Neutral 8A 250Vac 13 1415 16 12 5 6 7 8 9 10 11 1 2 3 4 17 Luce 13 DEFAULT SETTING VALUES Label Name Range Default Level REGULATION C F Set Set point LS US 5 41 Pr1 Hy Differential 0 1 25 5 C 1 ...

Отзывы: