background image

dIXEL

 

Installing and Operating Instructions 

1598029050

 

 

1598029050 XW40L NFR GB r1.0 11.07.2008.doc 

XW40L 

3/3 

12.

 

HOW TO USE THE HOT KEY  

12.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message 

appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key if you 

want to restart the upload again or remove the “

Hot key

” to abort the operation. 

12.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the Controller ON. 

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller memory, 

the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then 

on if you want to restart the download again or remove the “

Hot key

” to abort the operation. 

13.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and “COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

13.1

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P2”,

  start some seconds after the fault in the related probe; they automatically 

stop some seconds after the probe restarts normal operation. Check connections before replacing 
the probe. Temperature alarms “

HA

”, “

LA

” automatically stop as soon as the temperature returns to 

normal values. 

13.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

14.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

facia 38x185 mm; depth 76mm 

Mounting :

 panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

 

Distance between the holes 165mm 

Protection: 

IP20; 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston 

Power supply: 

230Vac or. 110Vac or 24Vac 

±

 10% 

 

Power absorption: 

5VA max.

 

Display

: 3 digits, 14,2 mm high; 

Inputs

: 2 NTC probes.

 

Relay outputs: 

Total current on loads MAX. 20A

 

compressor:

 relay SPST 16(3)A, 250Vac  

light: 

relay SPST 8 or 16(3) A, 250Vac  

 defrost:

 relay SPST 16(3) A, 250Vac  

Other output :

 buzzer (optional) 

Serial output :

 TTL standard; 

Communication protocol:

 Modbus - RTU

 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Over voltage Category

: II

 

Operating temperature: 

0÷60 °C; 

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F);  

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 

15.

 

CONNECTIONS 

 

Supply: 120Vac or 24Vac: 

connect to terminals 7-8

 

16.

 

DEFAULT SETTING VALUES 

Label 

Name Range 

Value Level

Set 

Set point 

LS÷US 

0 --- 

Hy 

Differential 

0,1

÷

25.5°C/ 1

÷

 255°F 

4 Pr1 

LS 

Minimum set point 

-50°C

÷

SET/-58°F

÷

SET 

-2 Pr2 

US 

Maximum set point 

SET

÷

110°C/ SET 

÷

 230°F 

16 Pr2 

Ot 

Thermostat probe calibration 

-12

÷

12°C /-120

÷

120°F 

0 Pr2 

P2P 

Evaporator probe presence 

n=not present; Y=pres. 

Y Pr2 

OE 

Evaporator probe calibration 

-12

÷

12°C /-120

÷

120°F 

0 Pr2 

OdS 

Outputs delay at start up 

0÷255 min 

1 Pr2 

AC 

Anti-short cycle delay 

÷

 50 min 

1 Pr2 

CCt 

Continuous cycle duration 0.0÷24.0h 

0.0 Pr2 

CCS 

Set point for continuous cycle 

 (-55.0÷150,0°C) (-67÷302°F) 

0 Pr2 

COn 

Compressor ON time with faulty probe 

÷

 255 min 

15 Pr2 

COF 

Compressor OFF time with faulty probe  0 

÷

 255 min 

20 Pr2 

CF 

Temperature measurement unit 

°C 

÷

 °F 

°C Pr1 

rES 

Resolution 

in=integer; dE= dec.point 

in Pr2 

tdF 

Defrost type 

EL=el. heater;  in= hot gas 

EL Pr2 

dtE 

Defrost termination temperature 

-50 

÷

 50 °C 

8.0 Pr1 

IdF 

Interval between defrost cycles 

÷

 120 ore 

4 Pr1 

MdF 

(Maximum) length for defrost 

÷

 255 min 

60 Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it Pr2 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 Pr2 

Fdt 

Draining time 

0÷120 min 

0 Pr2 

dPo 

First defrost after start-up 

n=after IdF; y=immed. 

n Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 Pr2 

ALc 

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

rE Pr2 

ALU 

MAXIMUM temperature alarm 

Set

÷

110.0°C; Set÷230°F 

10 Pr2 

ALL 

Minimum temperature alarm 

-50.0°C

÷

Set/ -58°F

÷

Set 

10 Pr2 

ALd 

Temperature alarm delay 

÷

 255 min 

10 Pr2 

dAO 

Delay of temperature alarm at start up 

÷

 23h e 50’ 

2.0 Pr2 

Adr 

Serial address 

1÷247 

1 Pr2 

rEL 

Software release 

-- 

1.8 Pr2 

Ptb 

Map code 

-- 

  

Pr2 

 

Dixell S.p.A.  Z.I. Via dell’Industria, 27 
32010 Pieve d’Alpago (BL) ITALY 
tel. +39 - 0437 - 98 33  -  fax +39 - 0437 - 98 93 13 

E-mail: [email protected] - http://www.dixell.com

 