Load, Battery and External DC Input Connections

All DC connections should be wired according to Figure 3 on page 11.

A block diagram of the basic internal wiring of the Genius-II can be found in 
Figure 4 on page 14.

Wire Size

DC cables must be sized to carry the maximum full load current and to not exceed 
the system volt drop requirements. The following cable sizes are recommended.

When running wires, if they pass through panels or wall, ensure the wires are 
protected form damage by sharp edges. One option is to use cable glands.

Current

Minimum Wire Size

0 – 10 A

1.0 mm² or 18 AWG

10 – 20 A

3.0 mm² or 14 AWG

20 – 30 A

5.5 mm² or 10 AWG

Table 1: Wire Size Recommendations

8

Figure 1: Mounting holes

F

ou

5m

m

 m

ou

nt

in

h

ol

es

328 mm

316 mm

1

38

 m

m

18

0

 m

m

Содержание GENIUS-II

Страница 1: ...GENIUS II POWER SUPPLY Owner s Manual Please read the Installation section of this manual before installing the product...

Страница 2: ...racy or suitability of the information contained in this manual Diverse Power Systems accepts no liability for any loss or damage which may occur as a result of improper or unsafe use of its products...

Страница 3: ...Connection 9 Solar Panel Connection 9 Remote Load isolator Switch Connection 10 Battery Connection Disconnection Procedure 12 Battery Connection Procedure 12 Battery Disconnection Procedure 12 Batter...

Страница 4: ...not cause short circuits Remove any personal metal adornment such as a chain watch or ring which could cause short circuits and personal injury CAUTION Failure to observe these instructions properly m...

Страница 5: ...tput at 35 A for powering the load and charging the caravan battery All the necessary protection and operating features for the load and battery are provided An optional DC input is also provided to e...

Страница 6: ...tive connection Used for connecting the negative wire of the 12 V loads Indicator Multi colour Status indicator Battery Fuse Fuse for caravan battery connection Battery Negative Terminal Connection po...

Страница 7: ...e air temperature can easily exceed 50 C if adequate ventilation is not provided The unit has over temperature protection meaning it will shut down if its internal temperature rises above a safe level...

Страница 8: ...ull load current and to not exceed the system volt drop requirements The following cable sizes are recommended When running wires if they pass through panels or wall ensure the wires are protected for...

Страница 9: ...batteries when mains voltages are not present This input is to be powered from a suitable 12 V system e g your Car The voltage of this external DC power source should not exceed 14 8 volts This input...

Страница 10: ...o use a voltage regulator may result in power supply damage Remote Load isolator Switch Connection The Genius II allows for remote control of the load connections A pair of contacts are provided for c...

Страница 11: ...ravan Battery Solar Regulator Load 10 Fuse 1 Fuse 2 Fuse 3 Fuse 4 Fuse 5 Fuse 6 Fuse 7 Fuse 8 Fuse 9 Fuse 10 Fuses for Loads 12V Solar Regulator Car Battery or other DC source 12V 10A 10A 10A 10A 10A...

Страница 12: ...us II Battery Disconnection Procedure The caravan battery should be disconnected as per the following steps 1 Disconnect all loads Turn off all 12 volt equipment connected to the Genius II or disconne...

Страница 13: ...o the Genius II should never become deeply discharged so recharging it should never be a problem If a battery has become deeply discharged and the Genius II will not charge it remove the battery see B...

Страница 14: ...own It will then automatically attempt to restart every 5 seconds until such case that the fault is removed Fusing Each load circuit and the caravan battery connection have been fused to provide fault...

Страница 15: ...ng current will be reduced accordingly Note that for the Genius II to operate in the manner described above all loads must be connected to its load terminals not directly to the caravan battery Low Vo...

Страница 16: ...harging Store Mode During float charging typically at 13 65 V there is continuous charging current into the battery sufficient in a long term charging situation to cause corrosion on the battery posit...

Страница 17: ...ery voltage above disconnect voltage The battery is powering the loads Red Solid Mains present AND battery connected AND power supply in over temperature shutdown mode Red Flash Mains present AND Batt...

Страница 18: ...Output Ripple Voltage 150 mV Over Voltage Protection 17 V Over Current Protection 35 A to 38 A load battery current Battery Current Limit 15 A 1 A Battery Connect 11 5 0 2 V Disconnect 10 0 0 2 V Bat...

Страница 19: ...to claim under this warranty you must a Ensure the product is installed by a suitably qualified person and is installed in accordance with this Owner s Manual and any applicable Australian Standard b...

Страница 20: ...DESIGNED AND MANUFACTURED IN AUSTRALIA 023484 Rev A...

Отзывы: