SUPPLY (Vs) = (10 to 30) V dc
MAX LOAD
KΩ = [(Vs – 10)/20]
OUTPUT
2 Wire (4 to 20) mA
INPUT CONNECTION
RTD wire must be equal length and type .
To maintain CE compliance cable length must be less than 30
metres.
OUTPUT CONNECTION
Use twisted pair or screened cables for cable lengths greater
than 30 metres. Max cable length 1000 metres. Ensure loop is
grounded at one point.
Vs
Loop
Load
+
-
9
7
8
2
1
INPUT
RTD
Ø 3mm
Screw Driver
Screened Cable
Twisted Pair Cable
TURN OFF SUPPLY BEFORE WORKING ON ANY ELECTRICAL CONNECTION
SEM1605P Enclosure
Style
DIN 43880 (1 module width)
Material
Polyamide 6.6 self extinguishing
Terminals
Screw terminal
Cable
2.5 mm Max
Colour
Grey
Ø 3 mm
90 mm
MOUNTING
Screw driver
EN50022 DIN RAIL
56.4 mm
17.5 mm
1
2
11 12
10
9
8
7
4
5
6
1
2
3
To fit or release module
Insert screw driver into
slot and lever latch
away from body
1
2
+ 70 °C Max
- 30 °C Min
1
2
ADJUST
STATE
ADJUST
STATE
+
_
MECHANICAL INSTALLATION
ELECTRICAL INSTALLATION
USB
1605 P
MT-KOS1605
P
_EN_
20190606
User Guide
307277
2
3