background image

DRP16 - 

User Guide 

 

1. 

Replaceable Battery

  

The DRP16 Series is equipped with a replaceable battery. 
Replacement of the battery should be done with the unit in an off 
position and unplugged from the wall outlet to ensure no AC 
voltage exists. The battery has a limited lifespan. Battery 
duration will decrease with repeated usage and age. If battery 
duration becomes extremely short, it may be time to replace the 
battery. The battery must be replaced with a sealed lead acid 
battery rated to 12V 5.5AH. Contact your authorized DITEK 
dealer. 

(See battery warnings on page 7 of this manual) 

2. 

Internal Warning Audible Alarm

  

When the DRP16 is switched on, the audible alarm will sound 
once for safety diagnosis. After 5 seconds, the DRP16 will check 
the strength of the battery. If the battery is weak, the audible 
alarm will sound continuously for 30 seconds. Alarm will sound at 
any time for battery failure. Contact your authorized DITEK 
dealer. 

3. 

Battery Test Switch

 

 

 

 

 

Press this button to test the status of battery. The battery 
indicator LED will light up if the voltage of the battery is greater 
than 11.5V. 

4. 

Battery Functional Indicator

 

When the DRP16 is powered up by the master switch, it 
performs a self-test to determine battery condition. If the audible 
alarm sounds for 30 seconds, the DRP16 needs to charge for 24 
hours. Then, retest the battery by depressing the Battery Test 
Switch. The indicator should light as the switch is depressed. If, 
after charging, the indicator fails to light when the switch is 
depressed, the battery needs to be replaced. Contact you 
authorized DITEK dealer. 

5. 

Wiring Functional Indicator Light

  

This indicator instantly alerts you of incorrect outlet wiring at your 
facility (either no ground circuit or a reversed polarity in the 
building wiring). If this light is off, consult a qualified electrician to 
examine your building wiring. 

6. 

Surge Protection Functional Indicator Light

  

This indicator shows the status of your AC surge protection 
circuitry. This indicator is lighted when the unit has active surge 
protection on the AC power circuit. Should one or more of your 
camera circuits lose surge protection, it will be evidenced by 
signal degradation appearing on the monitor screen for that 
particular camera. Should the surge protector self sacrifice on 
the data line circuit, it will be evidenced by “noise” on that line.  

7. 

On/Off Master Switch

  

The main power switch controls the power to all of the outlets. “I” 
means ON and “O” means OFF. 

 
 

DRP16 - 

User Guide 

DRP16T 

 

Electrical Specifications

 

Class: Digital Recorder Protector / Battery Back-Up 
Installation Point: Audio-video Point of Use  
Connection Method: 6 Foot Power Cord 
Continuous Current: 12 Amps 
Response Time: <5 nS 
MCOV: 130VAC 
Operating Frequency: 50 – 60 Hz 
AC Protection Modes: L – G, L – N, N - G 
Service Voltage: 125 VAC

 

Diagnostics: Surge Protection Active, Line Fault, Dry Contact (120 VAC, 1A Max) 
EMI/RFI Noise Filtering:

 

150KHz – 100mHz up to 58dB

 

Max. Surge Current: 58,500Amps (Peak) 
Max. Energy Dissipation: 1665 Joules (Single Pulse) 
Features: 4 AC Outlets, 16 - In / 16 - Out Coax, and 2 In/2Out RJ Connectors 
Battery Backup Rating: 450VA / 250W (Max.) 
Battery Output Voltage: -5% 
Battery Charge Mode: Full Time 
Battery Recharge Time: 12 Hours from total discharge (Typical) 
Battery Life: 3-6 Years (Typical) 
Battery Back up Response Time: 4 mS 

Phone/Fax/Modem Protection Specifications 

Connection Method: RJ11 
Max. Spike Energy: 160 Joules 
Clamping Voltage: 395V 
 

Data Line Protection Specifications 

Class: CAT5e Data Line Protector 
Connection Method: Modular Plug RJ45 
Continuous Current: 0.3 Amps 
Response time: <1nSec 
MCOV: 8VDC 
Peak Pulse Power Dissipation: 3KW (10/1000uS) 
Nominal Clamp Voltage: 6.8V 

DVR Protection Specifications 

Designed for baseband video channel signal transmission over UTP cable. 
Can be used for either NTSC, SECAM or PAL video signal. 
Built-in impedance matching device and filter for video signal transmission  
Compatible with qualified cameras with Built-in UTP transmitter. 
Class: UTP Video Protector 
Connection Method: Pluggable Terminal Block 
Wire size: 26-12 AWG 
Peak Pulse Power Dissipation: 4.5KW (10/1000uS) per module 
Nominal Clamp Voltage: 6.8V (L-G) 2.8V (L-L) 
Frequency: DC-10 MHZ 
Typical Insertion Loss: <0.1 dB 
Characteristic Impedance:  100 Ohms  
Mating Transceiver: DTK-DPBP, DTK-PVP-TPV, DTK-DP4P-TPV 
 

 

 

14 

Содержание DTK-DRP16

Страница 1: ...1720 Starkey Road Largo FL 33771 1 800 753 2345 www ditekcorp com INT 100084 001 Rev 7 06 10 08 191004 DRP16 Series DVR Surge Protector UPS User Guide DITEK CORPORATION One DITEK Center 1720 Starkey...

Страница 2: ...e Digital Recording equipment and welcome to a growing group of value conscious people who use DITEK Surge Protection products This User Guide explains the features of the DRP16 DRP16C DRP16B and the...

Страница 3: ...tery Functional Indicator 5 Wiring Functional Indicator 6 Surge Protection Functional Indicator 7 On Off Master Switch 8 1 set of RJ11 Tele Data Line Jacks Surge Protected 9 1 set of RJ45 Category 5 D...

Страница 4: ...s Surge Protected 9 1 set of RJ45 Category 5 Data Jacks Surge Protected 10 16 UTP Input and 16 BNC Output ports Surge Protected 11 Dry Contacts 12 Power Cord 13 15A Resettable Circuit Breaker 14 Surge...

Страница 5: ...materials are readily available DITEK provides the industry s most comprehensive line of surge protection devices for power video voice and data signals in industrial commercial institutional and res...

Страница 6: ...otection on the AC power circuit Should one or more of your camera circuits lose surge protection it will be evidenced by signal degradation appearing on the monitor screen for that particular camera...

Страница 7: ...to the equipment 9 Category 5 Data Jacks These jacks are marked IN and OUT Connect the incoming 100 Base T cable to the jack marked IN Use a Cat 5 patch cable not supplied to connect the OUT jack to t...

Страница 8: ...cause premature failure and excessive heat Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions MAKE SURE THE DRP16 IS IN THE O...

Страница 9: ...d negative leads making sure the negative terminal is facing towards the rear and right of the unit place the battery strap above the battery and gently slide the battery inside making sure that it sl...

Страница 10: ...s 1 000 to 5 000 feet Actual transmission ranges may be higher or lower than these distances and will depend upon the baluns being used Consult the balun manufacturers specifications for your applicat...

Отзывы: