background image

DTK-DF240S12 (12 Circuit 240VAC 20A Series Surge Protective Device)

CAUTION:  Risk  of  Electric  Shock-Only  intended  for installation in accordance 

with National Electric Code, ANSI/NFPA-70, Article 398.

Warning: 

Turn  power  off  at  the  main circuit  breaker  panel  before beginning install.

Note:  Connect  this  device in series between the 240VAC power supply and the loads 

that require protection.   Use 12 AWG Stranded,  Cu only conductors with  a  3/8”  strip 

length when terminating the wires at the power lugs.  The conductors used  to connect 

the SPD, to the supply or buss and to ground, shall not be any longer than necessary 

and shall avoid unnecessary bends.

1. Remove (4) screws securing the safety barrier, save screws.

2. Remove safety barrier.

3. Connect a Ground (green or bare conductor) from the EARTH terminal at the bottom 

of the board to the multi-position grounding buss located at the bottom of the enclosure.

4. Connect the Grounds, (green or bare conductors) from the distribution panel to the 

multi-position grounding buss located at the top of the enclosure.

5. Connect the Neutral (white conductor) supply wire from the distribution panel to the 

NEUTRAL terminal at the 

N1 IN

 lug. 

6. Connect the Phase (black conductor) supply wire from the distribution panel  to the 

Phase terminal at the 

L1 IN

 lug.

Note: Circuit 1 must be connected first. The diagnostic circuits get their power from 

this input.

7. Connect the Neutral (white conductor) for the connected load to the 

N1 OUT

 lug. 

8. Connect the Phase (black conductor) for the connected load to the 

L1 OUT

 lug.

9. Connect the Grounds, (green or bare conductors) for the connected loads to the 

multi-position grounding buss located at the bottom of the enclosure.

10. Repeat the above steps for circuits 2 through 12

Note: Tightening torque for the 240VAC power connections is 20 in-lb.

11. Use 1-1/2” conduit fittings for the AC circuits and a 1/2” conduit fitting for dry contacts.

12. After all connections have been made and no hazards exist, replace safety barrier 

and secure with screws. 

13. Insert DTK-DF240M surge modules, starting with circuit 1, then restore power.

L1

N1

IN

L1

N1

OUT

L2

N2

IN

L2

N2

OUT

Отзывы: