DTK-DF120S1 (120V 20A Series Surge Protective Device)
CAUTION: Risk of Electric Shock-Only intended for installation in accordance
with National Electric Code, ANSI/NFPA-70, Article 398.
Warning:
Turn power off at the main circuit breaker panel before beginning install.
Note: Connect this device in series between the 120VAC power supply and the alarm
panel, or branch panel 120VAC inputs. Use 12 AWG Stranded, Cu only conductors
with a 3/8” strip length when terminating the wires at the power lugs. The conductors
used to connect the SPD, to the line or bus and to ground, shall not be any longer than
necessary and shall avoid unnecessary bends.
1. Remove cover and save screws.
2. Connect the Ground (green or bare) to the EARTH terminal.
3. Connect the Neutral (white) supply wire to the NEUTRAL terminal on LINE-IN side.
4. Connect the Phase (black) supply wire to the LINE terminal on LINE-IN side.
5. Connect the Ground, Neutral and Phase wires from the LOAD-OUT side to the alarm
panel, or branch panel AC inputs.
Note: Tightening torque for the 120VAC power connections is 20 in. lbs.
6. Use appropriately sized conduit fittings and conduit to protect wiring, replace cover.
7. After all connections have been made and no hazards exist, insert DTK-DF120M
surge module and restore power.
NO C NC
DRY CONTACT
(+)
(-)
LOAD: 48VDC, 0.6AMP (MAX)
EXAMPLE MONITORING CIRCUIT
EXAMPLE REMOTE MONITORING
USING FACP FOR NOTIFICATION
DRY CONTACT CIRCUIT INFORMATION
DITEK
Surge Protection
IN
OUT
SW1
A
B
BUZZER SWITCH
POSITION
B
Y
P
A
S
S
N
O
R
M
A
L
A
B
BUZ1
TB2
NC C NO
TB1
EARTH
NEUTRAL
LINE
EARTH
NEUTRAL
LINE
OUT TO CONNECTED
EQUIPTMENT(LOAD)
LINE IN 120VAC
NO
C
NC
3’ Of Conductor Length
UNPROTECTED
PROTECTED
Dry Contact Circuit
Power Lugs:
Use 12 AWG Str,
Cu only, 3/8” strip.
20 in. lbs. torque
120VAC Input/Output