ECx-Light/Blind Series Troubleshooting
Network Guide
127
CHAPTER 10
ECx-Light/Blind Series Troubleshoot-
ing
Table 41: Troubleshooting ECx-Light / Blind Series Symptoms
Symptom
Possible Cause
Solution
Allure EC-Smart-Vue sen-
sor screen is blank & back
light is off
Is the Allure EC-Smart-Vue
sensor connected to the
controller?
Verify that the Allure EC-Smart-Vue sensor is connected to the control-
ler and that the patch cables are plugged-in to the connectors. See
on page 79 for more information.
Is power being supplied to
the controller?
There may be no power being supplied from the controller. Check if the
controller has power or if the controller's internal fuses have blown or
tripped.
Is the cable connected to
the controller and Allure
EC-Smart-Vue sensor?
Verify wiring.
Was the patch cable made
onsite?
Verify that the RJ-45 crimp connectors were installed on the cable cor-
rectly. See
Cat 5e Cable Subnetwork Data Bus Cable Requirements
on page 79.
Expansion module is not
communicating with control-
ler
Is the address correctly set
to a unique address?
Each expansion module must be set to a unique address for each con-
troller. See
Commissioning a Controller with an Allure EC-Smart-Vue
Is the device too far from
controller?
Verify the distance between the device and the controller. See
Is there a configuration
problem?
With EC-
gfx
Program, check the configuration of the sensor, for exam-
ple, is it enabled? Refer to the EC-
gfx
Program User Guide for more
information.
Have the subnetwork EOL
settings been correctly set?
Only the last module on the subnetwork data bus must have its EOL
termination set to ON. See
, and
. When
one or more ECx-400 Series IO Extension modules are connected to
the controller, only the last ECx-400 must have its EOL termination set
to ON. See
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...