ECx-4XX Series I/O Extension Module Specific Troubleshooting
Network Guide
121
CHAPTER 8
ECx-4XX Series I/O Extension Module
Specific Troubleshooting
For general troubleshooting of an ECx-4XX Series I/O Extension Module, first follow the trou-
bleshooting for a controller - see
on page 115. Then follow the troubleshooting tips shown below.
Table 37: Troubleshooting ECx-4XX Series I/O Extension Module Device Specific Symptoms
Symptom
Possible Cause
Solution
Device does not com-
municate on the BAC-
net MS/TP network
Absent or incorrect supply voltage
1. Check power supply voltage between 24VAC/DC ±15% and
24V COM pins and ensure that it is within acceptable limits (for
24V controllers).
3. Check for tripped fuse or circuit breaker.
Cut or broken wire.
Isolate the location of the break and pull a new cable.
Overloaded power transformer
Verify that the transformer used is powerful enough to supply all
controllers. See
ECx-4XX I/O Extension Module Power Supply
Network not wired properly
Double check that the wire connections are correct.
Absent or incorrect network termina-
tion
Check the network termination(s). See
Bus Topology and End-of-Line (EOL) Terminations
There is another controller with the
same Subnet ID on the subnetwork
data bis
Each I/O Extension Module on the subnetwork data bus must have
a unique Subnet ID. Look at the Subnet ID DIP switch on the face-
plate of each I/O Extension Module. See
Network length
Check that the total wire length does not exceed the specifications
of the Network Guide. See
on
page 70.
Wire type
Check that the wire type agrees with the specification shown in
Wire Subnetwork Data Bus Physical Specifications and Cable
Requirements
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...