 EC-NPB-2X-485 Option

Updated: September 2014

05DI-HI2X485-13

Mounting

Mounting

 

2

  •

from RS-485 “–” to Ground.

Biasing sometimes improves RS-485 communications 
by eliminating “indeterminate” idle states. 

In general, only 

one device

 on an RS-485 trunk 

should be biased. Otherwise, undue loading of the 
circuit may result, with fewer devices supported.

Note

RS-485 bias resistors are 

different

 than 

“termination resistors”, externally installed at 
the two physical ends of a daisychained 
RS-485 trunk, across the “+” and “–” 
terminals. Termination resistors are typically 
100 or 120 ohm value resistors.

Whenever termination resistors are used, RS-485 
biasing is typically required.

To enable biasing, install two 2-pin jumper blocks on 
that port’s jumper header, as shown in 

Figure 2

. To 

turn off biasing, 

remove

 both 2-pin jumper blocks from 

that port’s header ( the factory-shipped state).

Mounting

Warning

Power to the controller must be OFF when 
installing or removing option cards, or 
damage will occur! Also, you must be very 
careful to plug any option card into its 
connector properly (pins aligned).

Mount the EC-NPB-2X-485 option card in either of the 
option card slots of the EC-BOS

AX

, as needed. 

See 

“Preparation,”

 page 1 for details about RS-485 

resistor biasing, available on newer option cards.

See 

“COM Port Usage,”

 page 3 for details about 

EC-BOS

AX

 COM port assignments.

Procedure 1

Mounting EC-NPB-2X-485 option card on an 
EC-BOS

AX

.

1.

Remove power

 from the EC-BOS

AX

—see the 

previous 

Warning

. Wait for all LEDs on the unit to 

be Off.

Note

If accessory modules are plugged into the 
EC-BOS

AX

, you may need to slide them away 

from the unit to get to the cover tabs.

2.

If an EC-BOS-2/3/6

AX

 series or EC-BOS

AX

Security

remove the battery and bracket assembly by 
taking out the screws holding it in place, setting 
screws aside for later. See 

Figure 3

.

Figure 3

Remove screws and battery assembly.

Note

The tie wrap on the battery pack should have 
its lock “knot” on 

top

, as shown in 

Figure 3

 

If not, cut and 

remove

 the tie, then 

re-install

 

another tie wrap with its lock tab on top. 

 

(

Tie lock at bottom interferes with option card

).

3.

Remove the blanking end plate for the slot you are 
installing the option card into.

 

(Retain the blanking end plate in case the option 
card must be removed at a later date.)

Note

Slot 2 option card installation in an 
EC-BOS-7

AX

 controller requires careful 

attention! See the 

EC-BOS-7

AX

 Hardware 

Installation Guide

 for more details. This 

document focuses on installation in an 
EC-BOS-2/3/6

AX

 series controller.

4.

Carefully insert the pins of the EC-NPB-2X-485 
into the socket of the appropriate option card slot. 
The mounting holes on the option board should 
line up with the standoffs on the base board. If 
they do not, the connector is not properly aligned. 
Press until the option card is completely seated.

5.

Place the custom end plate that came with the 
EC-NPB-2X-485 over its connector (see 

Figure 4

).

Screws (4)

Option 

Slot 2

 

Area

EC-BOS-2/3/6

AX

 

Blanking 

End Plate

Battery 
Assembly

 

(includes

 

cable and 
bracket)

Unplug 
battery here

Option 

Slot 1

 Area

Tie Wrap 

Lock 