RE & Stationary Applications

Tubular OPzV Gel - 2V, 6V and 12V Cells & Blocks

Tubular Gel OPzV 

Operating Manual

Содержание Tubular Gel OPzV

Страница 1: ...1 Crestwood Place Richmond BC V6V 2E9 Canada 1 778 776 3288 info discoverbattery com discoverbattery com RE Stationary Applications Tubular OPzV Gel 2V 6V and 12V Cells Blocks Tubular Gel OPzV Operating Manual ...

Страница 2: ...re secure installation Use only suitable handling equipment and lifting gear Dangerous Voltage Batteries with this symbol can be recycled Do not mix with other industrial or household waste Contact your servicing Discover dealer for proper battery return and recycling Use protective glasses gloves and clothing when working on batteries Always make safe working practices a priority No Smoking Do no...

Страница 3: ...Discharge Protection 6 Array to Load Ratios for Stand alone Systems 6 Low voltage Re Connect LVR for Stand alone Systems 6 3 2 Charging 6 3 2 1 Balance or Complete Charge 6 3 2 2 Equilizing charge 7 3 2 2 1 Functional Equalizing 7 3 2 2 2 Corrective Equalizing 7 3 2 3 Normal Operation Charging 7 3 2 3 1 Settings for Stand Alone Systems 7 3 2 3 2 Settings for Hybrid Systems 8 3 3 Operation at Very ...

Страница 4: ...een cells or blocks The layout of the battery room or installation area must allow for easy access to the batteries The recommended minimum distance between battery rows is 1 5 times the depth of the row Racks or cabinets shall be located 100mm 4in from the wall Be sure to provide adequate space and lighting for inspection maintenance testing and cell block replacement Space should also be provide...

Страница 5: ...voltage directive 73 23 EEC which confirms that the CE marking is applied to the battery The company installing the battery is responsible for the declaration and applying the CE marking For future identification apply individual cell block numbers in sequence starting from one end of the series string Also apply identification letters or numbers for the parallel strings Only connect the battery t...

Страница 6: ...the supervisor nearby It lasts until certain charge criteria are fulfilled but not outside certain minimum and maximum time limits It is mainly used as Commissioning charge after installation Sec 2 8 Corrective equalizing charge Sec 3 2 2 2 Preparation charge before a capacity test Sec 6 Refresh charge during long storage period Sec 1 2 7 The battery temperature must be monitored during charge It ...

Страница 7: ...l generators mainly telecom hybrid systems the charging source is always available but the boost charging time is restricted to favor a more efficient utilization of the diesel In both cases a scheduled functional equalizing charge shall be performed at regular intervals Sec 3 2 3 to protect the battery from acid stratification sulphation and loss of capacity Functional Equalizing frequency is adj...

Страница 8: ...and alone systems with oversized PV array and very low MDDoD 5 e g remote telecom transmitters In these circumstances use the following settings The temperatures are average over one month Stand Alone Systems Hybrid Systems When only the PV is engaged use settings shown in Constant Voltage One Step When only the diesel is engaged continuously use Constant Voltage Two Step and reduce the settings b...

Страница 9: ...phs BatteryVoltage in relation to DoD as guidance for the initial LVD settings first try settings 25 C 77 F reference temperature 25ºC reference temperature DoD100 DoD90 DoD80 DoD70 DoD60 DoD50 DoD40 DoD30 DoD20 Minimum for Standby use MINIMUM FOR SOLAR USE 1 75 1 80 1 85 1 90 1 95 2 00 2 05 2 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Battery Voltage Vpc Extracted Amperhours per 100A...

Страница 10: ...ischarge or how deeply the battery has been dis charged Like the fuel gauge of your car DoD is the measure of how much fuel you have used I10 The constant current I discharge rate that can be maintain for 10 hours 10 MDDoD Maximum Daily Depth of Discharge allowable MDoD Maximum allowable Depth of Discharge OCV Open Circuit Voltage The voltage across the cell block or battery terminals with no load...