4 Configuring Victron Products
4.1 VE.Configure Settings
You will need the latest firmware on all connected devices. This section presumes familiarity with VEConfigure software.
These settings are for an off-grid application. These parameters once set will become the default values used if
communication with the AES battery is interrupted for some reason. During normal operation the charge characteristics are
governed automatically by the CCGX via DVCC, with instructions from the connected AES battery. However it is necessary
to set the discharging parameters for DC input low shut-down found under the Inverter Tab. After setting the parameters,
‘send’ all parameters to the inverter and CCGX. Restart the CCGX after completion.
General Tab
44-24-2800
42-48-6650
Overruled by remote
(1)
Enable
Enable
Enable battery monitor
Enable
Enable
SoC when Bulk finished
(2)
95%
95%
Total battery capacity (per battery installed)
installed x 110 Ah
installed x 130 Ah
Charge efficiency
(2)
95%
95%
Inverter Tab
44-24-2800
42-48-6650
DC input low shut-down
(3)
24.0 V
48.0 V
DC Input low restart
(4)
26.0 V
52.0 V
DC input low pre-alarm
(5)
25.5 V
51.0 V
Enable AES
(6)
Disable
Disable
Charger Tab
44-24-2800
42-48-6650
Enable charger
Enable
Enable
Battery Type
(2)
Blank
Blank
Lithium batteries
(2)
Enable
Enable
Charge curve
(2)
Select: Fixed
Select: Fixed
Absorption voltage
(2)
27.2 V
54.4 V
Float voltage
(2)
26.8 V
53.6 V
Charge current per battery installed
(Recommended < Maximum)
installed x
(78 A < 110 A)
installed x
(92 A < 130 A)
Repeated absorption time
(2) (7)
1.0 < 3.0 Hr
1.0 < 3.0 Hr
Repeated absorption interval
(2)
7.0 Days
7.0 Days
Absorption time
(2) (7)
1.0 < 3.0 Hr
1.0 < 3.0 Hr
(1) Enabled is recommended.
(2) Precautionary setting as they are ignored during normal operation and communication with AES Battery.
(3) The lowest operating voltage allowed, increase voltage as required.
(4) Restart voltage after DC input low shut-down, recommended to be set to the minimum value (minimum varies according to
the DC Input low shut-down value).
(5) 51.0 V value (approximately 15% SoC) will trigger low battery warning, increase or decrease as preferred.
(6) ‘Enable AES’ has no relation to the AES Battery, refer to Victron manuals for information on setting and function.
(7) The recommended minimum is 1.0 hour. A longer period of time may be required to compensate for multiple batteries to
achieve a smooth completion of charge.
▲
NOTE
•
Confirm the Float Voltage after completing the installation of any Victron
‘Assistants’, and if necessary reset the Float Voltage back to 26.8 V / 53.6 V.
M8” bolt (supplied with battery)
Copper compression lug
Shrink-wrap to
color-code the cable
Terminal surface
Lock washer (supplied with battery)
Flat washer (supplied with battery)
Battery cable lug
Ensure nothing is between
the terminal surface and the
battery cable lug