2.  Installation and operation 

1.  Inspection 

Remove the UPS from its packaging and inspect it for damage 
that  may  have  occurred  during  shipping.  If  any  damage  is 
discovered,  repack  the  unit  and  return  it  to  the  place  of 
purchase. 

 

2.  Charging

 

This unit is shipped from the factory with its internal battery fully 
charged,  however,  some  charge  may  be  lost  during  shipping 
and the battery should be recharged prior to use. Plug the unit 
into an appropriate power supply and allow the UPS to charge 
fully by leaving it plugged in for at least 10 hours with no load 
(no  electrical  devices  such  as  computers,  monitors,  etc.) 
connected.

 

10 hours

 

3.  Placement 

Install the UPS unit in any protected environment that provides 
adequate airflow around the unit, and is free from excessive 
dust, corrosive fumes and conductive contaminants. Do not 
operate your UPS in an environment where the ambient 
temperature or humidity is high.     

 

4.   Computer Connection 

Plug  the  UPS  into  a  2-pole,  3-wire  grounded  receptacle.  Then 
connect  one  computer-related  device  into  each  of  the  power 
receptacles supplied on the back of the UPS.

 

 

5.   phone  system,  computer,  monitor  against  surges  and           

spikes Connection (Option) 

Plug incoming  I

nternet line into the “In” socket at the back of the 

UPS.  Use  one  more  Internet  line  cable  and  plug  one  end  of  the 
Internet line cable to the “Out” socket at the back of the UPS. Plug 
the other end to the modem input socket as shown. 

 

 

6.   Turn On/Off 

Press  the  switch  of  the  UPS  continuously  for  1  second  and  the 
UPS  turns  into  its  normal  state  (the  green  light  is  on  and  the 
beeper is off) after it performs a self-diagnosis (the beeper and the 
red and green indicator lights are on) for several seconds. At this 
time, user may turn on the PC and other loads. Press the switch of 
the UPS continuously for 1 second to turn off the UPS. 
 

Note:

 

1.  For  the  convenience  of  maintenance,  please  turn  on  the  UPS  first 

before turning on the PC and the other loads, and turn off the UPS 
after the loads are turned off. 

2.  At  ordinary  times,  we  recommend  to  remain  the  UPS  on  with  the 

battery charging (even if the loads are turned off), which is benefit to 
the maintenance of the battery.

 

3.  Trouble Shooting 
 

Symptom 

Possible Cause 

Remedy 

No LED display 
on the front 
panel. 

1. Battery weak 

1.  Re-charge  battery 

up to 8 hours. 

2. Battery defect. 

2. Replace with the 

same type of 
battery. 

3. Power switch is not 

pressed. 

3. Press power switch 

again. 

4. Battery connector loosed 
 

4. Check the internal 

battery connection 

When power 
failure, backup 
time is short. 

1. Overload of the UPS. 

1. 

Remove 

some 

non-critical load. 

2. Battery voltage is too low.  2.  Charge  battery  8 

hours or more. 

3. Battery defect due to high 

temperature operation 
environment, or improper 
operation to battery. 

3. Replace with the 

same type of battery. 

Mains normal 
but LED is 
flashing. 

1. Fuse is blown. 

1.  Replace  the  same 

type of fuse. 

2. Power cord is loose. 

2. Reconnect the 

power cord properly. 

If any abnormal situations occur that are not listed above, please 
call service people immediately.

 

4. Specification 

MODEL 

 

 

DP 400 

DP 600 

DP 1000 

CAPACITY   

VA/W 

400VA/200W 

600VA/300W 

1000VA/600W 

INPUT 

Voltage 

110/120VAC or 220/230/240VAC 

 

 

Voltage Range 

90-145VAC    /      170-270VAC 

OUTPUT 

Voltage 

110/120VAC or 220/230/240VAC 

 

 

Voltage Regulation 

(Batt. Mode) 

±10% 

 

 

Frequency 

50Hz or 60Hz 

 

 

Frequency Regulation (Batt. 

Mode) 

+/-1 Hz 

 

 

Output Waveform 

(Batt. Mode) 

Modified Sinewave 

BATTERY 

Battery Type & Number 

12V/4.5Ah x 1pc  12V/7.2AH x 1pc  12V/7.2AH x 2pc 

 

 

Back up Time (at a PC load 

with 15" monitor) 

5 minutes 

8 minutes 

20 minutes 

 

 

Recharge Time 

10 hours to 90% after complete discharge 

TRANSFER TIME 

Typical 

2-6ms 

INDICATOR 

AC Mode 

Green LED lighting 

Battery Mode 

Green LED flashing every 4 seconds 

Low Battery at Battery Mode 

Green LED flashing every second 

Fault 

Red LED lighting 

Battery Weak at AC Mode 

Red LED flashing every 2 seconds for 30 seconds 

Battery Fault at AC Mode 

Red LED flashing three times every 2 seconds 

AUDIBLE ALARM 

Battery Mode 

Sounding every 4 seconds 

Low Battery at Battery Mode 

Sounding every second 

Fault 

Continuously sounding 

Battery Charging at AC Mode 

Sounding every 2 seconds for 30 seconds 

Battery Weak at AC Mode 

Sounding three times every 2 seconds 

PROTECTION 

Full Protection 

Discharge, overcharge 

PHYSICAL 

Dimension, DXWXH (mm) 

176.5x80x230 

Net Weight (kgs) 

2.5 

3.1 

6.5 

ENVIRONMENT 

Operating Environment 

0- 40°C, 0-90 % relative humidity (non-condensing) 

Noise Level 

Less than 45dB 

 

Incoming Internet Line 