DRY LOCATION

1 OF 4

IG040617-5.0

DMX DECODER

 INSTALLATION GUIDE

®

DIMMABLE

12VDC

INSTALLATION GUIDE

DMX 4-CHANNEL DECODER

24VDC

1. 

Install  in  accordance  with  national  and  local  electrical  code 

regulations. 

2. 

This product is intended to be installed and serviced by a qualified, 

licensed electrician.

3. DO NOT connect directly to high voltage power. Install with a 

compatible Class 2 constant voltage LED driver (power supply).

4. 

This  product  is  rated  for  indoor  installation  and  is  not  protected 

against moisture.

5. 

Install appropriately rated wire between driver, decoder, and fixture. 

When choosing wire, factor in voltage drop, amperage rating, and 

type (in-wall rated, etc.) Inadequate wire installation may cause fire.

6. 

Do  not  modify  or  disassemble  product  beyond  instructions  or 

warranty will be void. 

SAFETY & WARNINGS

QUICK SPECS / MODELS

INSTALLATION

1

TURN POWER OFF AT CIRCUIT BREAKER

2

Input

Output

Max Load

DI-1810

(also DI-1918) 12 - 24VDC

12 - 24VDC

4CH x 5A 

4CH x 96W (12V)

4CH x 192W (24V)

SHOCK HAZARD!

 

May result in serious injury or death.

Turn power OFF at circuit breaker prior to installalation.

DETERMINE LOCATION TO INSTALL COMPONENTS

V+
V-

V+

CH1 - R
CH2 - G
CH3 - B
CH4 - W

0-5 0-9 0-9

Data IN

Data OUT

1) Driver

2) DMX 

Controller

3) DMX

Decoder

4) Fixture(s)

CONNECT DECODER TO DRIVER. ATTACH LED 

FIXTURE. ONLY USE COPPER WIRING.

 

Reference SYSTEM DIAGRAM located further in guide for 

visual. 

CONNECT DECODER TO MASTER DMX 

CONTROLLER

.

3

INSTALL ADDITIONAL COMPONENTS, VERIFY 

CONNECTIONS, TURN MAIN POWER ON AT 

BREAKER. 

4

5

MAXIMUM DAISY-CHAIN DMX DECODERS

A maximum of 10x DMX Decoders may be connected together via 

RJ45 DMX Connection Ports. DMX signal may be extended further 

by installing a DMX 8-Way Splitter (DI-1804) after the 10th DMX 

Decoder. 

Содержание DI-1810

Страница 1: ...ctions or warranty will be void SAFETY WARNINGS QUICK SPECS MODELS INSTALLATION 1 TURN POWER OFF AT CIRCUIT BREAKER 2 Input Output Max Load DI 1810 also DI 1918 12 24VDC 12 24VDC 4CH x 5A 4CH x 96W 12V 4CH x 192W 24V SHOCK HAZARD May result in serious injury or death Turn power OFF at circuit breaker prior to installalation DETERMINE LOCATION TO INSTALL COMPONENTS V V V CH1 R CH2 G CH3 B CH4 W 0 5...

Страница 2: ...annel Address CH1 001 CH2 002 CH3 003 CH4 004 1cH 001 Only Channel Address CH1 001 CH2 001 CH3 001 CH4 001 2cH 001 002 Only Channel Address CH1 001 CH2 002 CH3 001 CH4 002 3cH 001 003 Only Channel Address CH1 001 CH2 002 CH3 003 CH4 001 OPERATION PROFESSIONAL USE ONLY SETTING PWM FREQUENCY DIMMING TYPE The PWM frequency dimming type can be adjusted for special applications 0 5 0 9 0 9 1 2 3 0 5 0 ...

Страница 3: ...o driver specifications for additional information InstallacompatibleClass2constantvoltagedriver Itisrecommended to load the driver no more than 80 its labeled rating for maximum longevity Refer to driver specifications for a compatible junction box See fixture specifications for maximum series run limits The following diagram is provided as an example system design CAT5 RJ45 connections data cabl...

Страница 4: ...5 A 40 W 3 3 A 50 W 2 1 A 60 W 4 2 A 18 AWG 34 ft 17 ft 11 ft 8 ft 6 ft 5 ft 16 AWG 54 ft 27 ft 18 ft 13 ft 10 ft 9 ft 14 AWG 86 ft 43 ft 29 ft 21 ft 17 ft 14 ft 12 AWG 134 ft 68 ft 45 ft 34 ft 27 ft 22 ft 10 AWG 199 ft 99 ft 66 ft 49 ft 39 ft 33 ft 24V Voltage Drop Wire Length Distance Chart 12V Voltage Drop Wire Length Distance Chart Wire Gauge 10 W 83 A 20 W 1 7 A 30 W 2 5 A 40 W 3 3 A 50 W 2 1...

Отзывы: