11.4.4 Legend .. 9CS TO .. 22CS

APPENDIX: 11.4 WIRING DIAGRAMS

A1

Wire jumper, must be removed upon installation of a utility company disable contactor

A2

Wire jumper, must be removed if 2nd disable input is used

B3*

Thermostat, hot water

B4*

Thermostat, swimming pool water

E9*

Electr. immersion heater, hot water

E10*

Suppl. heat source (boiler or electr. heating element

F2

Load fuse for N1 relay outputs across J12 at J13

4.0 A slow-acting

F3

Load fuse for N1 relay outputs across J15 to J18

4.0 A slow-acting

F4

Pressostat high pressure

F5

Pressostat low pressure (from ..22CS, F5 is a limiter with manual reset)

F10

Flow control switch

F15

Overload relay for M11 / the overload relay is designed for the pump included in the brine kit

H5*

Fault indicator lamp

J1...J18

Terminal connector at N1

K1

Contactor, compressor

K5

Contactor, primary pump

K11*

Electron. relay remote fault indicator (on relay module)

K12*

Electron. relay, swimming pool water circulating pump (on relay module)

K20*

Contactor for E10

K21*

Contactor for E9

K22*

Utility company disable contactor

K23*

SPR auxiliary relay

M1

Compressor

M11*

Primary pump

M13*

Heating circulating pump

M15*

Heating circulating pump

M16*

Auxiliary circulating pump

M18*

Hot water circulating pump

M19*

Swimming pool water circulating pump

M21*

Mixer, primary circuit

M22*

Mixer heating circuit 2

N1

Heat pump controller

N7

Soft start control (not in WI 9CS units)

N10*

Remote control station

N11*

Relay module

R1

External sensor

R2

Return sensor

R3

Hot water sensor (as an alternative to the hot water thermostat)

R5

Sensor for heating circuit 2

R6

Freeze protection sensor

R7

Coding resistor 10k

T1

Safety isolating transformer 230/24VAC-28VA

X1

Terminal strip mains control L/N/PE-230VAC-50Hz/fuses/N and PE terminal block

X2

Terminal strip 24VAC terminal block

X3

Terminal strip GND terminal block for sensors R1/-2 and -3 at J2

X4

Terminal strip GND terminal block for sensors R5 and -6 at J6

X5

Terminal strip power supply 3L/PE-400VAC-50Hz

Abbreviations:

EVS

Utility company disable input

SPR

Supplementary disable input

MA*

Mixer OPEN - primary heating circuit

MZ

Mixer CLOSED - primary heating circuit

* Components to be supplied by the customer, or available as accessories

Содержание WI 14CS

Страница 1: ...1 MOUNTING and OPERATING MANUAL Water to Water Heat Pump for Indoor Installation WI 9CS WI 14CS WI 22CS WI 27CS CE Order No 452230 67 03 FD 8404...

Страница 2: ...General Information 5 2 Sound Emissions 6 MOUNTING 6 6 1 General 6 2 Heating Side Connection 6 3 Heat Source Side Connection 6 4 Electrical Connection 7 COMMISSIONING 7 7 1 General 7 2 Preparation 7...

Страница 3: ...should therefore be suitable for low flow temperatures A 1 K higher heating water temperature corresponds to an increase in power consumption of approx 2 5 Underfloor heating systems with flow temper...

Страница 4: ...stems Water which can be supplied from wells or the like is used as the heat carrier To prevent any corrosion damage to the eva porator the well water must be evaluated in accordance with DIN 50930 as...

Страница 5: ...nsulation To prevent noise transmission to the foundation a suitable sound dampening rubber mat should be placed underneath the base frame of the heat pump The transmission of noise to the heating sys...

Страница 6: ...er must meet the required water quality standard 6 4 Electrical Connection The following electrical connections must be established on the heat pump Connection of the control wire to the control panel...

Страница 7: ...are displayed on the heat pump controller and can be corrected as described in the operating manual of the heat pump controller CARE CLEANING 8 1 Care The heat pump is maintenance free To prevent malf...

Страница 8: ...be complied with The use of surface water or saline water bodies is not permitted Consult your local waterworks for some general information about any possible ground water usage Water analyses are pr...

Страница 9: ...3 5 Performance Curves 22CS 16 11 3 6 Pressure Losses 22CS 17 11 3 7 Performance Curves 27CS 18 11 3 8 Pressure Losses 27CS 19 11 4 Wiring Diagrams 11 4 1 Control 9CS to 22CS 20 11 4 2 Load 9CS to 22...

Страница 10: ...rnal thread 22 27CS 1 1 4 internal 1 external thread Heat source side connections 9 14CS 1 1 4 internal external thread 22 27CS 1 1 2 internal external thread Heating water return Heat pump inlet Heat...

Страница 11: ...ch G 1 int ext G 1 int ext G1 int G1 ext G 1 i G 1 a 4 3 Equipment connections for heat source inch G 1 int ext G 1 int ext G 1 int ext G 1 int ext 4 4 Weight of transport unit s incl packaging kg 147...

Страница 12: ...l Der anteiligen Pumpenleistungen Bedingungen Heizwasserdurchsatz 0 75 m h Kaltwasserdurchsatz 2 0 m h 35 50 11 3 1 Performance Curves 9CS APPENDIX 11 3 PERFORMANCE CURVES PRESSURE LOSSES Conditions H...

Страница 13: ...rchflu in m h Druckverlust in Pa Druckverluste Verfl ssiger bei 35 C Druckverlust 7 kPa bei Heizwasser Nenndurchflu 0 75 m h 11 3 2 Pressure Losses 9CS APPENDIX 11 3 PERFORMANCE CURVES PRESSURE LOSSES...

Страница 14: ...n kW incl Der anteiligen Pumpenleistungen Bedingungen Heizwasserdurchsatz 1 3 m h Kaltwasserdurchsatz 3 3 m h 35 50 11 3 3 Performance Curves 14CS APPENDIX 11 3 PERFORMANCE CURVES PRESSURE LOSSES Heat...

Страница 15: ...urchflu in m h Druckverlust in Pa Druckverluste Verfl ssiger bei 35 C Druckverlust 7 kPa bei Heizwasser Nenndurchflu 1 3 m h 11 3 4 Pressure Losses 14CS APPENDIX 11 3 PERFORMANCE CURVES PRESSURE LOSSE...

Страница 16: ...gsaufnahme in kW incl Der anteiligen Pumpenleistungen Bedingungen Heizwasserdurchsatz 2 0 m h Kaltwasserdurchsatz 5 0 m h 35 50 11 3 5 Performance Curves 22CS APPENDIXG 11 3 PERFORMANCE CURVES PRESSUR...

Страница 17: ...durchflu in m h Druckverlust in Pa Druckverluste Verfl ssiger bei 35 C Druckverlust 8 kPa bei Heizwasser Nenndurchflu 2 0 m h 11 3 6 Pressure Losses 22CS APPENDIX 11 3 PERFORMANCE CURVES PRESSURE LOSS...

Страница 18: ...aufnahme in kW incl Der anteiligen Pumpenleistungen Bedingungen Heizwasserdurchsatz 2 4 m h Kaltwasserdurchsatz 7 0 m h 35 50 11 3 7 Performance Curves 27CS APPENDIX 11 3 PERFORMANCE CURVES PRESSURE L...

Страница 19: ...rdurchflu in m h Druckverlust in Pa Druckverluste Verfl ssiger bei 35 C Druckverlust 12 5 kPa bei Heizwasser Nenndurchflu 2 4 m h APPENDIX 11 3 PERFORMANCE CURVES PRESSURE LOSSES 11 3 8 Pressure Losse...

Страница 20: ...M 1 X 2 2 4 V A C S t M 1 1 A 2 I D 7 A 1 J 1 G E V S S P R J 5 I D 6 I D 3 I D 2 I D 1 I D 4 I D 5 N O 6 N O 3 J 1 3 N O 5 N O 4 C 4 K 5 A 1 C 1 C 4 F 3 L F 4 A 1 K 1 A 2 K 5 A 1 F 1 5 A 2 0 V A C J...

Страница 21: ...5 A 4 1 4 A H e r s t e l l e r G r u n d f o s P u m p e n T y p N e n n s t r o m 1 4 2 0 A W I 9 C S b i s 2 2 C S 2 2 3 5 A W I 2 7 C S M 1 1 F 1 5 6 4 9 6 I n A n l a g e n o h n e E V U S p e r...

Страница 22: ...8 J 1 4 J 1 5 J 1 6 J 1 7 J 1 8 0 V A C J 1 G 0 2 4 V A C K o n t a k t o f f e n W P g e s p e r r t 2 t e r S p e r r e i n g a n g X 2 0 V A C R 5 J 1 G 0 I D C 1 B 6 J 1 G X 4 I D C 9 B 7 J 6 B 8...

Страница 23: ...or for E9 K22 Utility company disable contactor K23 SPR auxiliary relay M1 Compressor M11 Primary pump M13 Heating circulating pump M15 Heating circulating pump M16 Auxiliary circulating pump M18 Hot...

Страница 24: ...X 2 2 4 V A C A 2 A 1 J 5 I D 7 I D 6 I D 3 I D 2 I D 1 I D 4 I D 5 S P R E V S J 1 3 N O 3 C 1 K 5 A 1 C 4 N O 4 X 1 1 F 3 L N O 6 N O 5 C 4 T 1 T 2 Q 2 F 1 4 F 1 2 K 1 2 A 1 A 2 K 1 1 K 1 A 1 A 2 A...

Страница 25: ...4 0 0 V A C 5 0 H z 3 N e t z V e r d r a h t u n g b e i A u s l i e f e r u n g P E L 3 1 L 2 1 X 5 L 1 1 3 L 2 3 P E L 3 X 5 L 1 N 7 1 1 1 M 1 3 M M 1 1 1 3 5 P E K 5 2 4 6 1 8 2 4 6 1 4 I I I 1 2...

Страница 26: ...1 X 1 N P E 1 N e t z M 1 8 M 1 3 J 1 4 J 1 5 J 1 6 J 1 7 J 1 8 0 V A C J 1 G 0 K o n t a k t o f f e n W P g e s p e r r t 2 t e r S p e r r e i n g a n g J 6 0 V A C X 2 2 4 V A C R 5 B 6 J 1 G 0 I...

Страница 27: ...y M1 Compressor M11 Primary pump M13 Heating circulating pump M15 Circulating pump heating circuit 2 M16 Auxiliary circulating pump M18 Hot water circulating pump M19 Swimming pool water circulating p...

Страница 28: ...tion well Shut off valve Shut off valve with drain Overflow valve Safety valve Circulating pump Expansion vessel Thermostat manual valve Check valve Shut off valve with check valve Heat consumer Strai...

Страница 29: ...cations are made to the product s without our prior authorization Designation of the product s EC Directives Brine to water heat pumps EC Low Voltage Directive for indoor installation withR407C 73 23...

Страница 30: ...Notes...

Страница 31: ...Notes...

Страница 32: ...32 KKW Kulmbacher Klimager te Werk GmbH Subject to technical modifications Division Dimplex Fax 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Отзывы: