background image

EN-8                                                           452231.66.22 · FD 9204

www.dimplex.de

English

SIKH 9ME

7.5 Electrical connection 

7.5.1 General

During start-up, observe the respective national safety regula-
tions and the applicable VDE safety regulations, particularly
VDE 0100, as well as the technical connection requirements of
the utility companies (EVU) and network operators!
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain connected
to the power supply and the flow must be maintained through the
heat pump at all times.
The switching contacts of the output relay are interference-sup-
pressed. Therefore, depending on the internal resistance of the
measuring instrument, a voltage can also be measured when the
contacts are open. However, this will be much lower than the line
voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J24 and terminal strip X2;  X3. If, due to a wiring er-
ror, the line voltage is mistakenly connected to these terminals,
the heat pump manager will be destroyed.

7.5.2 Electrical installation

1)

The supply cable for the output section of the heat pump (up
to 3-core) are fed from the electricity meter of the heat pump
via the utility blocking contactor (if required) into the heat
pump (see heat pump operating instructions for supply volt-
age).
Connection of the mains cable to the control panel of the
heat pump via terminal X1: L/N//PE.
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for
all external conductors must be installed in the power supply
for the heat pump (tripping current and characteristic in com-
pliance with the device information).

2)

The three-core supply cable for the heat pump manager
(heating controller N1) is fed into the heat pump . Connec-
tion of the control line to the control panel of the heat pump
via terminal X2: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking contac-
tor or be connected to the household current, as important
protection functions could otherwise be lost during a utility
block.

3)

The utility blocking contactor(K22) with  main contacts  and
an auxiliary contact should be dimensioned according to the
heat pump output and must be supplied by the customer.
The NO contact of the utility blocking contactor is looped
from terminal strip X3/G  to connector terminal J5/ID3. 

CAU-

TION! Extra-low voltage!

4)

The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG2) should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals X2/N and N1-J13/NO4.

5)

The contactor (K21) for the flange heater (E9) in the hot
water cylinder should be dimensioned according to the radi-
ator output and must be supplied by the customer. It is con-
trolled (230 V AC) by the heat pump manager via terminals
X2/N and N1-J16/NO 10.

6)

The contactors mentioned above in points 3, 4 and 5 are in-
stalled in the electrical distribution system. The mains cables
for the heating elements should be dimensioned and pro-
tected according to DIN VDE 0100.

7)

All cables must be installed as permanent wiring.

8)

The heat circulating pump (M13) is connected to terminals
X2/N and N1-J13/NO 5.

9)

The DHW loading pump (M18) is connected to terminals X2/
N and N1-J13/NO 6.

10) The brine or well pump is connected to terminals X2/N and

N1-J13/NO 3.

11) The return sensor (R2) is integrated into  heat pumps for in-

door installation. 
The heat pump manager is connected via the following ter-
minals: X3/GND and N1-J2/B2.

12) The external sensor (R1) is connected to terminals X3/GND

and N1-J2/B1.

13) The domestic hot water sensor (R3) is included with the do-

mestic hot water cylinder and is connected to terminals X3/
GND and N1 - J2/B3.

8 Start-up

8.1 General Information

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by the
manufacturer. This may be a condition for extending the guaran-
tee (see Warranty Service).

8.2 Preparation

The following items need to be checked prior to start-up:

The heat pump must be fully connected, as described in
Chapter 7.

The heat source system and the heating circuit must have
been filled and checked.

Dirt traps and breathers must be inserted in the brine inlet of
the heat pump.

All valves that could impair proper flow in the brine and heat-
ing circuits must be open.

The heat pump manager must be adapted to the heating
system in accordance with the controller’s operating instruc-
tions.

Ensure the condensate outflow functions.

The outflows of the brine and heating water pressure relief
valves must not be impaired.

Содержание SIKH 9 ME

Страница 1: ...or Indoor Installation Pompe chaleur eau glycol e eau pour installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installation and...

Страница 2: ......

Страница 3: ...ge DE 6 7 1 Allgemein DE 6 7 2 Heizungsseitiger Anschluss DE 6 7 3 W rmequellenseitiger Anschluss DE 6 7 4 Temperaturf hler DE 6 7 5 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 8 8 1 Allgemein DE...

Страница 4: ...erliegt damit den Anforde rungen der EG Richtlinie 2006 95 EC Niederspannungsrichtli nie Sie ist damit ebenfalls f r die Benutzung durch Laien zur Beheizung von L den B ros und anderen hnlichen Arbeit...

Страница 5: ...s Temperaturniveau ge pumpt Die bei diesem Vorgang zugef hrte elektrische Antriebs leistung geht nicht verloren sondern wird gr tenteils dem K ltemittel zugef hrt Daraufhin gelangt das K ltemittel in...

Страница 6: ...Verdichters bei fehlendem Volumenstrom verhindert 4 5 W rmemengenz hler WMZ 4 5 1 Allgemeine Beschreibung Der W rmemengenz hler WMZ 25 32 dient dazu die angege bene W rmemenge zu erfassen Er ist als...

Страница 7: ...Rohr dienen ACHTUNG Ger t nicht an den Bohrungen in den Verkleidungsblechen anheben 6 Aufstellung 6 1 Allgemeine Hinweise Das Ger t ist grunds tzlich in Innenr umen auf einer ebenen glatten und waagr...

Страница 8: ...ahme erkl rt HINWEIS Der Einsatz eines berstr mventils ist nur bei Fl chenheizungen und einem max Heizwasserdurchsatz von 1 3 m h ratsam Bei Nichtbeachten kann es zu St rungen der Anlage f hren Frosts...

Страница 9: ...gesetzt werden Montage als Rohranlagef hler Heizungsrohr von Lack Rost und Zunder s ubern Gereinigte Fl che mit W rmeleitpaste bestreichen d nn auftragen F hler mit Schlauchschelle befestigen gut fest...

Страница 10: ...tellen Der Schlie er Kontakt des EVU Sperrsch tz wird von Klemmleiste X3 G zur Steckerklemme J5 ID3 geschleift VORSICHT Kleinspannung 4 Das Sch tz K20 f r den Tauchheizk rper E10 ist bei monoenergetis...

Страница 11: ...tstoff rohre in das Heizsystem Deshalb sollte besonders bei den Rohren der Fu bodenheizung auf eine diffusionsdichte Installa tion geachtet werden HINWEIS Zur Vermeidung von Ablagerungen z B Rost im K...

Страница 12: ...endienst ACHTUNG Arbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden ACHTUNG Vor ffnen des Ger tes sind alle Stromkreise spannungsfrei zu schalten...

Страница 13: ...zwasserdurchfluss bei interner Druckdifferenz m h Pa 0 75 1800 1 6 7000 3 6 Freie Pressung Heizungsumw lzpumpe max Stufe Pa 47500 36000 3 7 Soledurchsatz bei interner Druckdifferenz W rmequelle m h Pa...

Страница 14: ...erer bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird de...

Страница 15: ...7 Installation EN 6 7 1 General Information EN 6 7 2 Heating System Connection EN 6 7 3 Heat Source Connection EN 6 7 4 Temperature sensor EN 7 7 5 Electrical connection EN 8 8 Start up EN 8 8 1 Gene...

Страница 16: ...ve 2006 42 EC machinery directive and is thus subject to the requirements of EC directive 2006 95 EC low voltage directive It is thus also in tended for use by non professionals for heating shops offi...

Страница 17: ...needed to run the compressor is not lost in this process Most of it is absorbed by the refrigerant The refrigerant subsequently passes through the liquifier where it transfers its thermal energy to t...

Страница 18: ...there is no volume flow 4 5 Thermal energy meter WMZ 4 5 1 General description The thermal energy meter WMZ 25 32 is used for measuring the quantity of thermal energy supplied It is available as an ac...

Страница 19: ...h of pipe can be used as a carrying aid ATTENTION Do not use the holes in the panel assemblies for lifting the device 6 Set up 6 1 General Information The unit must be installed indoors on a level smo...

Страница 20: ...ual differential pressureless manifold or an overflow valve The procedure for adjusting an overflow valve is described in the Chapter Start Up NOTE The use of an overflow valve is only recommended for...

Страница 21: ...the heat pump but have not yet been installed The strap on sensors can be fitted as pipe mounted sensors or installed in the immersion sleeve of the compact manifold Mounting as a pipe mounted sensor...

Страница 22: ...contact should be dimensioned according to the heat pump output and must be supplied by the customer The NO contact of the utility blocking contactor is looped from terminal strip X3 G to connector t...

Страница 23: ...em via the valves the circulating pumps and or plastic pipes It is therefore essential in particular with respect to the piping of un derfloor heating systems that only diffusion proof materials are u...

Страница 24: ...ON Any work on the heat pump may only be performed by authorised and qualified after sales service technicians ATTENTION Disconnect all electrical circuits from the power source prior to opening the d...

Страница 25: ...h an internal pressure differential of m h Pa 0 75 1800 1 6 7000 3 6 Free compression of heat circulating pump max level Pa 47500 36000 3 7 Brine throughput with an internal pressure differential heat...

Страница 26: ...EN 12 452231 66 22 FD 9204 www dimplex de English SIKH 9ME...

Страница 27: ...5 7 1 Remarques d ordre g n ral FR 5 7 2 Branchement c t installation de chauffage FR 6 7 3 Raccordement c t source de chaleur FR 6 7 4 Sonde de temp rature FR 6 7 5 Branchements lectriques FR 8 8 Mis...

Страница 28: ...ective Basse Tension Elle est donc galement pr vue pour l utilisation par des personnes non initi es des fins de chauf fage de boutiques bureaux et autres environnements de travail quivalents dans les...

Страница 29: ...temp rature plus lev L nergie lectrique mise disposition tout au long de ce proc d n est pas perdue elle est transf r e au contraire galement en grande partie au fluide frigorig ne Le fluide frigorig...

Страница 30: ...bsence de d bit 4 5 Calorim tre WMZ 4 5 1 Description g n rale Le calorim tre WMZ 25 32 sert r pertorier la quantit de cha leur d gag e Ce calorim tre est disponible comme accessoire Deux calorim tres...

Страница 31: ...pompe chaleur doit adh rer au sol sur toute sa circonf rence afin de ga rantir une isolation acoustique appropri e Si tel n est pas le cas des mesures d absorption acoustique compl mentaires seront v...

Страница 32: ...ntra ner des d fauts de fonctionnement de l installation Protection antigel dans le cas d une mise en place expos e au gel La fonction de protection antigel du gestionnaire de pompe chaleur est activ...

Страница 33: ...ur ne pas exposer aux rayons directs du soleil quelle que soit la saison C ble de sonde longueur max 40 m section de fils min 0 75 mm diam tre ext rieur du c ble 4 8 mm 7 4 3 Montage des sondes d appl...

Страница 34: ...olaire avec au moins 3 mm d carte ment d ouverture de contact p ex contacteur de blocage de la soci t d lectricit ou contacteur de puissance ainsi qu un coupe circuit automatique omnipolaire avec d cl...

Страница 35: ...s effectuer conform ment aux instructions de montage et d utilisation du gestionnaire de pompe chaleur Les niveaux de puissance des circulateurs doivent tre adapt s l installation de chauffage Le r gl...

Страница 36: ...ement rincer l aide de produits neutralisants ad quats afin d viter tous dom mages provoqu s par d ventuels restes de produits de net toyage dans le syst me Les acides doivent tre utilis s avec pr cau...

Страница 37: ...pression diff int m h Pa 0 75 1800 1 6 7000 3 6 Compression libre circulateur de chauffage degr max Pa 47500 36000 3 7 D bit eau glycol e avec pression diff int source chaleur m h Pa 2 0 7500 2 0 750...

Страница 38: ...FR 12 452231 66 22 FD 9204 www dimplex de Fran ais SIKH 9ME...

Страница 39: ...ram Diagramme des seuils d utilisation A IV 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques A V 3 1 Steuerung Control Commande A V 3 2 Last Load Charge A VI 3 3 Anschlussplan Circuit Diagram Sch...

Страница 40: ...LH GH OD 3 LOHWDJH H WpULHXU OOHU HDX GH FKDXIIDJH 6RUWLH GH OD 3 LOHWDJH H WpULHXU 6RXSDSH GH WURS SOHLQ LOHWDJH H WpULHXU JHPHLQVDPHU 5 FNODXI LQJDQJ LQ 3 X HQJHZLQGH QVFKOXVV XVlW OLFKHV XVGHKQXQJV...

Страница 41: ...HLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ...

Страница 42: ...seuils d utilisation 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 10 5 0 5 10 15 20 25 30 Heizwassertemperatur C Heating water temperature C Temp rature d eau de chauffage C W rmequelleneintrittstemp...

Страница 43: ...SIKH 9ME 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande 9 9 1 95 9 WHUP 9 1 G 5 G 1 5 12 12 12 5 7 5 7 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 7 7 7 DDDD EEEE FFFF...

Страница 44: ...A VI 452231 66 22 FD 9204 www dimplex de Anhang Appendix Annexes SIKH 9ME 3 2 Last Load Charge...

Страница 45: ...lan Circuit Diagram Sch ma lectrique 9 9 9 1 95 9 WHUP 9 1 1 G 5 3 3 G 1 5 G G 5 7 7 0 1 7 7 12 12 12 5 7 5 7 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 7 7 7 DDDD EEEE FFFF GGG HHH IIII JJJ 1 0 1 1 3 0...

Страница 46: ...ktron Relais f r Schwimmbadwasserumw lz pumpe Electronic relay for swimming pool water circulating pump Relais lectronique pour circulateur eau de piscine K20 Sch tz 2 W rmeerzeuger E10 Contactor for...

Страница 47: ...nnected on site if required raccorder par le client si besoin ACHTUNG An den Steckklemmen J1 bis J7 J9 bis J11 J24 und der Klemmleiste X3 liegt Kleinspannung an Auf keinen Fall darf hier eine h here S...

Страница 48: ...A X 452231 66 22 FD 9204 www dimplex de Anhang Appendix Annexes SIKH 9ME 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique 4 1 Darstellung Schematic View Repr sentation...

Страница 49: ...lt under buffer tank R servoir tampon sous jacent Warmwasserspeicher Hot water cylinder Ballon d eau chaude Kondensatablauf Condensate outflow Ecoulement des condensats berdruck Heizung Sole Overpress...

Страница 50: ...ung W rmepumpen Designation Heat pumps D signation Pompes chaleur Typ SIKH 9ME Type s Type s EG Richtlinien Niederspannungsrichtlinie 2006 96 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23...

Страница 51: ...www dimplex de 452231 66 22 FD 9204 A XIII Anhang Appendix Annexes SIKH 9ME...

Страница 52: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: