background image

www.gdts.one

452237.66.50 · FD 9912

EN-9

SI 50TU - SI 75TU 

English

7.5 Electrical connection 

7.5.1 General

All electrical installation work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the 

installation and operating instructions, 

country-specific installation regulations (e.g. VDE 0100),

technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and

local conditions. 

To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J19 to N1-J20; N1-J23 to N1-J26 and the terminal
strips X3. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will be
destroyed.

NOTE

º

For installation work on the switch box, ensure that the mains
cable and signal cables are inserted separately into the switch
box. The specially arranged switch box inlets must be used for
this purpose (see Fig.7.4 on pag. 9). 
The mains cables and signal cables must also always be laid
separately in the switch box during wiring work.

Fig. 7.4:Cable inlet switch box

7.5.2 Electrical installation work 

1) The four-core electrical supply cable for the heat pump

power part is fed from the heat pump electricity meter into
the heat pump via the utility company blocking contactor
(if required) (for supply voltage, see heat pump manual).
The mains cable is connected to the heat pump contact
plate via terminals X1: L1/L2/L3/PE.

ATTENTION!

!!

Ensure that there is a clockwise rotating field: With incorrect
wiring the starting of the heat pump is prevented. A
corresponding warning is indicated on the display of the heat
pump manager (adjust wiring).

An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility company blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for all
external conductors must be installed in the power supply for
the heat pump (tripping current and characteristic in compli-
ance with the device information).
2) The three-core supply cable for the heat pump manager

(heating controller N1) is fed into the heat pump. Connec-
tion of the control cable to the contact plate of the heat
pump via terminal X2: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a continuous voltage. For this reason,
it  should  be  tapped  upstream  from  the  utility  company
blocking contactor or be connected to the household cur-
rent, as important protection functions could otherwise be
lost during a utility block.

3) The utility company blocking contactor (K22) with main

contacts and an auxiliary contact must be designed and
provided by the customer in accordance with the heat
pump output.
The NO contact of the utility company blocking contactor
is looped from the terminal strip X3/G to the plug-in termi-
nal X3/ID3. 

CAUTION! Extra-low voltage

!

4) The contactor (K20) for the immersion heater (E10) of

mono energy systems (HG2) should be dimensioned ac-
cording to the radiator output and must be supplied by the
customer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K20.

5) The contactor (K21) for the flange heater (E9) in the do-

mestic hot water cylinder should be dimensioned accord-
ing to the radiator output and must be supplied by the cus-
tomer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K21.

6) The contactors mentioned above in points 3, 4 and 5 are

installed in the electrical distribution system. 

7) All installed electric cables must have permanent wiring.
8) The heat circulating pump (M13) is activated via the con-

tact N1-J13/NO5. The connection points for the pump are
X2/M13 and X2/N. When using pumps where the switch-
ing capacity exceeds the output, a coupling relay must be
interposed.

9) The auxiliary circulating pump (M16) is activated via the

contact N1-J16/NO9. The connection points for the pump
are X2/M16 and X2/N. A coupling relay is already inte-
grated in this output.

10) The domestic hot water circulating pump (M18) is acti-

vated via the contact N1-J13/NO6. The connection points
for the pump are X2/M18 and X2/N. When using pumps
where the switching capacity exceeds the output, a cou-
pling relay must be interposed.

A

A

Supply mains cable 
line voltage

Supply signal cable 
extra-low voltage

Содержание SI 50TU

Страница 1: ...Gebrauchsanweisung Sole Wasser W rmepumpe f r Innenaufstellung Installation and Operating Instruction Brine to Water Heat Pump for Indoor Installation Instuctionsd installation et d utilisation Pompe...

Страница 2: ......

Страница 3: ...eitiger Anschluss DE 7 7 4 Temperaturf hler DE 7 7 5 Elektrischer Anschluss DE 9 8 Inbetriebnahme DE 10 8 1 Allgemeine Hinweise DE 10 8 2 Vorbereitung DE 10 8 3 Vorgehensweise bei Inbetriebnahme DE 10...

Страница 4: ...ine Unterschreitung kann zur Zerst rung der W rmepumpe f hren ACHTUNG Im W rmequellenkreis ist ein geeigneter Luftabscheider Mikroluftblasenabscheider bauseits vorzusehen ACHTUNG Im W rmequelleneintri...

Страница 5: ...nal zu ber pr fen und zu protokollieren N here Angaben dazu befinden sich im beiliegenden Logbuch 1 4 Energiesparende Handhabung der W rmepumpe Durch das Betreiben dieser W rmepumpe tragen Sie zur Sch...

Страница 6: ...Betrieb der W rmepumpe not wendigen Bauteile angebracht Ein F hler f r die Au entempe ratur mit Befestigungsmaterial sowie ein Schmutzf nger liegen der W rmepumpe bei Die Zuleitung f r Last und Steue...

Страница 7: ...ACHTUNG Bei einer externen Ansteuerung der W rmepumpe bzw der Umw lzpumpen ist ein Durchflussschalter vorzusehen der das Einschalten des Verdichters bei fehlendem Volumenstrom verhindert 5 Transport Z...

Страница 8: ...heizungsseitiger Installation ist die Heizungsan lage zu f llen zu entl ften und abzudr cken ACHTUNG Der maximale Pr fdruck betr gt heiz und soleseitig 6 0 bar Dieser Wert darf nicht berschritten werd...

Страница 9: ...opylenglykolbasis bestehen und ist vor dem Bef llen zu mischen HINWEIS Bei Bedarf kann der Einsatzbereich bis zu einer Soleeintrittstemperatur von 10 C erweitert werden In diesem Fall ist die minimale...

Страница 10: ...it Schlauchschelle befestigen gut festziehen lose F hler f hren zu Fehlfunktionen und thermisch isolieren 7 4 4 Verteilsystem Hydraulik Kompaktverteiler und doppelt differenzdruckloser Verteiler fungi...

Страница 11: ...tens 3 mm Kontakt ffnungsab stand z B EVU Sperrsch tz Leistungssch tz sowie ein allpo liger Sicherungsautomat mit gemeinsamer Ausl sung aller Au enleiter vorzusehen Ausl sestrom und Charakteristik gem...

Страница 12: ...12 A der elektronisch geregelten Umw lzpumpe nicht berschritten wird oder es liegt eine ausdr ckliche Freigabe des Pumpenherstellers vor ACHTUNG Es ist nicht zul ssig ber einen Relaisausgang mehr als...

Страница 13: ...t geeigneten neutralisierenden Mitteln gr nd lich nachgesp lt werden um Besch digungen durch eventuell im System verbliebene Reinigungsmittelreste zu verhindern Die S uren sind mit Vorsicht anzuwenden...

Страница 14: ...6 72000 14 3 87000 4 3 Schall Leistungspegel nach EN 12102 dB A 61 62 4 4 Schalldruck Pegel in 1 m Entfernung3 dB A 45 46 5 Abmessungen Gewicht und F llmenge 5 1 Ger teabmessungen4 H x B x L mm 1660...

Страница 15: ...zu einer Soleeintrittstemperatur von 35 C m glich Bei Soleeintrittstemperaturen von 25 C bis 35 C Vorlauftemperatur von 62 C bis 58 C fallend 3 Der angegebene Schalldruckpegel entspricht dem Betriebsg...

Страница 16: ...stungspegel innen au en LWA 61 dB 9 0 m h Stickoxidaussto NOx mg kWh Angegebenes Lastprofil Warmwasserbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qf...

Страница 17: ...rbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qfuel kWh Kontakt Wird der Cdh Wert nicht durch Messung bestimmt gilt f r den Minderungsfaktor der Vorg...

Страница 18: ...e Teile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert verg ten...

Страница 19: ...7 3 Heat source connection EN 7 7 4 Temperature sensor EN 7 7 5 Electrical connection EN 9 8 Commissioning EN 10 8 1 General Information EN 10 8 2 Preparation EN 10 8 3 Commissioning procedure EN 10 9...

Страница 20: ...n the heat pump being destroyed ATTENTION A suitable de aerator micro bubble air separator must be installed in the heat source circuit by the customer ATTENTION The supplied dirt trap must be inserte...

Страница 21: ...ation can be found in the accompanying log book 1 4 Energy efficient use of the heat pump By operating this heat pump you are helping to protect our en vironment Both the heating system and the heat s...

Страница 22: ...eat pump are located in the switch box An outside temperature sensor in cluding fixing accessories and a dirt trap are supplied with the heat pump The supply for the supply voltage and the control vol...

Страница 23: ...et ATTENTION If the heat pump or circulating pumps are controlled externally a flow rate switch is required to prevent the compressor from being switched on when there is no volume flow 5 Transport A...

Страница 24: ...t be filled de aerated and pressure tested ATTENTION The maximum test pressure in the heating circuit and the brine circuit is 6 0 bar This value must not be exceeded The following points must be obse...

Страница 25: ...be mixed before filling NOTE If necessary the operating range can be extended to a brine inlet temperature of 10 C In this case the minimum brine concentration must be adjusted to 30 Freezing temperat...

Страница 26: ...n firmly as loose sensors can cause malfunctions and thermally insulate 7 4 4 Hydraulic distribution system The compact manifold and the dual differential pressureless manifold function as an interfac...

Страница 27: ...pole circuit breaker with common tripping for all external conductors must be installed in the power supply for the heat pump tripping current and characteristic in compli ance with the device inform...

Страница 28: ...current of 12 A are not exceeded in the electronically regulated circulating pump or if express approval has been is sued by the pump manufacturer ATTENTION It is not permitted to connect more than o...

Страница 29: ...rn of the liquefier of the heat pump It is then important that the system be thoroughly flushed using appropriate neutralising agents to prevent any damage from being caused by cleaning agent residue...

Страница 30: ...dB A 61 62 4 4 Sound pressure level at a distance of 1m3 dB A 45 46 5 Dimensions weight and filling quantity 5 1 Device dimensions 4 H x W x L mm 1660 x 1000 x 750 1890 x 1350 x 750 5 2 Weight of the...

Страница 31: ...es of 25 C to 35 C flow temperature decreasing from 62 C to 58 C 3 The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation at 55 C flow temperature...

Страница 32: ...Emissions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not...

Страница 33: ...Wh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen the d...

Страница 34: ...EN 16 452237 66 50 FD 9912 www gdts one English SI 50TU SI 75TU...

Страница 35: ...dement c t source de chaleur FR 7 7 4 Sonde de temp rature FR 7 7 5 Branchements lectriques FR 9 8 Mise en service FR 10 8 1 Remarques d ordre g n ral FR 10 8 2 Pr paratifs FR 10 8 3 Proc dures suivre...

Страница 36: ...sement peut entra ner la destruction de la pompe chaleur ATTENTION Il appartient au client de pr voir un s parateur d air appropri s parateur microbulles d air dans le circuit de source de chaleur ATT...

Страница 37: ...ord ci joint 1 4 Utilisation de la pompe chaleur pour conomiser de l nergie En utilisant cette pompe chaleur vous contribuez pr server l environnement Pour obtenir un fonctionnement efficace il est tr...

Страница 38: ...saires l utilisation de la pompe chaleur Une sonde de mesure de la temp rature ext rieure et son mat riel de fixation ainsi qu un collecteur d impuret s sont livr s avec la pompe chaleur Le c ble d al...

Страница 39: ...TENTION En cas de commande externe de la pompe chaleur ou des circulateurs pr voir un commutateur de d bit servant emp cher la mise en marche du compresseur en cas d absence de flux volumique 5 Transp...

Страница 40: ...remplie purg e et prouv e la pression ATTENTION La pression d preuve maximale s l ve c t chauffage et c t eau glycol e 6 0bars Cette valeur ne doit pas tre d pass e Respecter les consignes suivantes l...

Страница 41: ...col doit tre d au moins 25 et le m lange doit tre effectu avant le remplissage REMARQUE En cas de besoin la plage d exploitation peut tre largie jusqu une temp rature d entr e de l eau glycol e de 10...

Страница 42: ...La sonde doit tre fix e avec un collier serrer fond des sondes mal fix es engendrent des d fauts et isol e ther miquement 7 4 4 Syst me de distribution hydraulique Le distributeur compact et le distri...

Страница 43: ...blage est mal effectu la pompe chaleur ne peut pas d marrer Un avertissement correspondant s affiche sur le gestionnaire de pompe chaleur changer le c blage Sur l alimentation de puissance de la pompe...

Страница 44: ...gestionnaire de pompe chaleur C est la raison pour laquelle un relais de couplage est install doit tre install entre la sortie du gestionnaire de pompe chaleur et le circulateur r gulation lectroniqu...

Страница 45: ...aleur Il faut ensuite soigneusement rincer les tuyauteries l aide de produits neutralisants ad quats afin d viter tous dommages provoqu s par d ventuels restes de produit de nettoyage dans le syst me...

Страница 46: ...ique selon EN 12102 dB A 61 62 4 4 Niveau de pression sonore 1m de distance3 dB A 45 46 5 Dimensions poids et capacit 5 1 Dimensions de l appareil4 H x l x L mm 1660 x 1000 x 750 1890 x 1350 x 750 5 2...

Страница 47: ...de l eau glycol e de 35 C une temp rature d entr e de l eau glycol e comprise entre 25 C et 35 C temp rature d part d croissante de 62 C 58 C 3 Le niveau de pression sonore indiqu correspond au bruit...

Страница 48: ...nsommation journali re de combustible Qfuel kWh Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Pour les disposi...

Страница 49: ...h Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Exigences d information pour les dispositifs de chauffage des...

Страница 50: ...FR 16 452237 66 50 FD 9912 www gdts one Fran ais SI 50TU SI 75TU...

Страница 51: ...splan Connection Plan Sch ma de connexion SI 50TU SI 75TU A X 3 5 Anschlussplan Connection Plan Sch ma de connexion SI 50TU SI 75TU A XI 3 6 Legende Legend L gende SI 50TU SI 75TU A XII 4 Hydraulische...

Страница 52: ...n faible tension 1 1 Heizungsvorlauf Ausgang aus W rmepumpe Rp 1 1 2 1 2 Heizungsr cklauf Eingang in W rmepumpe Rp 1 1 2 1 5 W rmequellenvorlauf Eingang in W rmepumpe Rp 2 1 2 1 6 W rmequellenr cklauf...

Страница 53: ...ension 1 1 Heizungsvorlauf Ausgang aus W rmepumpe Rp 2 1 2 Heizungsr cklauf Eingang in W rmepumpe Rp 2 1 5 W rmequellenvorlauf Eingang in W rmepumpe Rp 2 1 2 1 6 W rmequellenr cklauf Ausgang aus W rme...

Страница 54: ...ut to pump Consommation de puissance in kW y compris part de consommation de la pompe Druckverlust in Pa Pressure loss in Pa Perte de pression en Pa Verdampfer Evaporator Evaporateur Druckverlust in P...

Страница 55: ...er input to pump Consommation de puissance in kW y compris part de consommation de la pompe Druckverlust in Pa Pressure loss in Pa Perte de pression en Pa Verdampfer Evaporator Evaporateur Druckverlus...

Страница 56: ...45 50 55 60 65 10 5 0 5 10 15 20 25 30 Heizwassertemperatur C Heating water temperatur e C Temp rature d eau chauffage C W rmequelleneintrittstemperatur C Heat source inlet temperature C Temp rature...

Страница 57: ...www gdts one 452237 66 50 FD 9912 A VII SI 50TU SI 75TU Anhang Appendix Annexes 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande SI 50TU SI 75TU...

Страница 58: ...A VIII 452237 66 50 FD 9912 www gdts one Anhang Appendix Annexes SI 50TU SI 75TU 3 2 Steuerung Control Commande SI 50TU SI 75TU...

Страница 59: ...www gdts one 452237 66 50 FD 9912 A IX SI 50TU SI 75TU Anhang Appendix Annexes 3 3 Last Load Charge SI 50TU SI 75TU...

Страница 60: ...A X 452237 66 50 FD 9912 www gdts one Anhang Appendix Annexes SI 50TU SI 75TU 3 4 Anschlussplan Connection Plan Sch ma de connexion SI 50TU SI 75TU...

Страница 61: ...www gdts one 452237 66 50 FD 9912 A XI SI 50TU SI 75TU Anhang Appendix Annexes 3 5 Anschlussplan Connection Plan Sch ma de connexion SI 50TU SI 75TU...

Страница 62: ...ter heat pump Pressostat basse pression pompe chaleur eau eau F7 Hei gasthermostat Hot gas thermostat Thermostat gaz chaud F10 1 Durchflussschalter Prim rkreis Flow rate switch for primary circuit Com...

Страница 63: ...rucksensor K ltekreis Niederdruck pO Pressure sensor for refrigerating circuit low pressure pO Capteur de pression circuit r frig rant basse pression pO R26 Drucksensor K ltekreis Hochdruck pc Pressur...

Страница 64: ...sserbereitung Monovalent heat pump system with three heating circuits and domestic hot water preparation Installation monovalente de pompe chaleur avec trois circuits de chauffage et production d eau...

Страница 65: ...nt system with two heating circuits and domestic hot water preparation Installation bivalente avec deux circuits de chauffage et production d eau chaude sanitaire R1T DDV X3 R1 X2 M18 M18 K2 K21 E9 R3...

Страница 66: ...lon tampon en s rie Warmwasserspeicher Hot water cylinder Ballon d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 2 l Gaskessel Oil gas boiler C...

Страница 67: ...ng Declaration of Conformity D claration de conformit Die aktuelle CE Konformit tserkl rung finden sie als Download unter You can find and download the current CE conformity declaration at Vous pouvez...

Страница 68: ...tschland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 9245...

Отзывы: