12 Device Information
Device information for brine-to-water heat pumps (heating only)
1
Type and order code
SI 5BS
SI 7BS
SI 9BS
SI 11BS
SI 14BS
2
Design
2.1
Degree of protection according to EN 60 529
IP 20
IP 20
IP 20
IP 20
IP 20
2.2
Installation location
Indoors
Indoors
Indoors
Indoors
Indoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow
°C
Up to 55
Up to 55
Up to 55
Up to 55
Up to 55
Brine (heat source)
°C
-5 to +25
-5 to +25
-5 to +25
-5 to +25
-5 to +25
Antifreeze
Monoethyl-
ene glycol
Monoethyl-
ene glycol
Monoethyl-
ene glycol
Monoethyl-
ene glycol
Monoethyl-
ene glycol
Minimum brine concentration (-13 °C freezing temperature)
25%
25%
25%
25%
25%
3.2
Temperature spread of heating water (flow/return flow) at B0 / W35K
10.1
9.9
10.5
10.1
9.6
3.3
Heat output / COP
at B-5 / W55
1
kW / ---
1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation should
also be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
3.8 / 1.96
5.6 / 2.2
7.7 / 2.3
9.4 / 2.4
12.5 / 2.6
at B0 / W50
1
kW / ---
4.8 / 2.75
6.7 / 2.9
9.0 / 3.1
11.3 / 3.0
14.2 / 3.4
at B0 / W35
1
kW / ---
5.3 / 4.3
6.9 / 4.3
9.2 / 4.4
11.8 / 4.4
14.5 / 4.5
3.4
Sound power level
dB(A)
54
55
56
56
56
3.5
Heating water flow with an internal pressure differential of m³/h / Pa
0.45 / 1900
0.6 / 3300
0.75 / 2300
1.0 / 4100
1.3 / 4800
3.6
Brine throughput with an internal pressure differential (heat source) of m³/
h / Pa
1.2 / 16000
1.7 / 29500
2.3 / 25000
3.0 / 24000
3.5 / 20000
3.7
Refrigerant; total filling weight
type / kg
R407C / 1.0
R407C / 0.9
R407C / 1.3
R407C / 1.4
R407C / 1.7
4
Dimensions, connections and weight
4.1
Device dimensions without connections
2
H x W x L mm
2. Note that additional space is required for pipe connections, operation and maintenance.
800 x 600 x
480
800 x 600 x
480
800 x 600 x
480
800 x 600 x
480
800 x 600 x
480
4.2
Device connections to heating system
Inch
G 1¼"
external
G 1¼"
external
G 1¼"
external
G 1¼"
external
G 1¼"
external
4.3
Device connections to heat source
Inch
G 1¼"
external
G 1¼"
external
G 1¼"
external
G 1¼"
external
G 1¼"
external
4.4
Weight of the transportable unit(s) incl. packing
kg
97
100
106
110
122
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
400 / 16
400 / 16
400 / 16
400 / 16
400 / 16
5.2
Nominal power consumption
1
B0 W35
kW
1.23
1.6
2.07
2.66
3.22
5.3
Starting current with soft starter
A
22
(without
SS)
30
(without
SS)
15
26
26
5.4
Nominal current B0 W35 / cos
ϕ
A / ---
2.22
2.89
3.77
4.84
5.81
6
Complies with the European safety regulations
3
3. See CE declaration of conformity
3
3
3
3
7
Additional model features
7.1
Water in device protected against freezing
4
4. The heat circulating pump and the heat pump controller must always be ready for operation.
No
No
No
No
No
7.2
Performance levels
1
1
1
1
1
7.3
Controller internal/external
Internal
Internal
Internal
Internal
Internal