APPENDIX: 12.2 EQUIPMENT DATA
Equipment Data
EQUIPMENT DATA for Brine-to-Water Heat Pumps for Heating
1
TYPE AND COMMERCIAL DESCRIPTION
..7KS
..9KS
..11KS
..14KS
2
MODEL
2.1
Type
compact
compact
compact
compact
2.2
Enclosure type acc. to EN 60 529
IP 20
IP 20
IP 20
IP 20
2.3
Installation site
indoors
indoors
indoors
indoors
3
PERFORMANCE DATA
3.1
Operating temperature limits:
Heating water supply
°C
max. 55
max. 55
max. 55
max. 55
Brine (heat source)
°C
-5 to +25
-5 to +25
-5 to +25
-5 to +25
Antifreeze agent
monoethylene glycol
monoethylene glycol
monoethylene glycol
monoethylene glycol
Minimum brine concentration (-13°C freezing temperature)
25%
25%
25%
25%
3.2
Heating water temperature difference at B0 / W35
K
9,9
10,5
10,1
9,6
3.3
Heating capacity / coeff.of perform.
at B-5 / W55
1)
kW / ---
5,6 / 2,2
7,7 / 2,3
9,4 / 2,4
12,5 / 2,6
at B0 / W50
1)
kW / ---
6,7 / 2,9
9,0 / 3,1
11,3 / 3,0
14,2 / 3,4
at B0 / W35
1)
kW / ---
6,9 / 4,3
9,2 / 4,4
11,8 / 4,4
14,5 / 4,5
3.4
Sound power level
dB(A)
51
51
51
51
3.5
Heating water flow rate at internal pressure difference
m³/h / Pa
0,6 / 2500
0,75 / 4500
1,0 / 3500
1,3 / 3500
3.6
Free presssure, heating circulating pump (stage 3)
Pa
47500
43500
65500
64500
3.7
Brine flow rate at internal pressure difference (heat source)
m³/h / Pa
1,7 / 10000
2,3 / 16000
3,0 / 13000
3,5 / 13000
3.8
Free pressure, brine pump (stage 3)
Pa
55000
44000
40000
34000
3.9
Refrigerant; total charge weight
type / kg
R407C / 1,5
R407C / 1,8
R407C / 2,0
R407C / 2,3
4
DIMENSIONS, CONNECTIONS AND WEIGHT
4.1
Equipment dimensions without connections
4)
H x W x L mm
1110
×
652
×
653
1110
×
652
×
653
1110
×
652
×
653
1110
×
652
×
653
4.2
Equipment connections for heating system
inches
R 1¼" ext.
R 1¼" ext.
R 1¼" ext.
R 1¼" ext.
4.3
Equipment connections for heat source
inches
R 1¼" ext.
R 1¼" ext.
R 1¼" ext.
R 1¼" ext.
4.4
Weight of transport unit(s) incl. packaging
kg
179
180
191
203
5
ELECTRICAL CONNECTION
5.1
Nominal voltage; fusing
V / A
400 / 16
400 / 16
400 / 16
400 / 16
5.2
Nominal power consumption
1)
B0 W35
kW
1,6
2,07
2,66
3,22
5.3
Starting current with soft starter
A
30 (no soft starter)
15
26
26
5.4
Nominal current B0 W35 / cos
ϕ
A / ---
2,89
3,77
4,84
5,81
6
COMPLIES WITH EUROPEAN SAFETY REGULATIONS
3)
3)
3)
3)
7
OTHER DESIGN CHARACTERISTICS
7.1
Water inside equipment protected against freezing
2)
yes
yes
yes
yes
7.2
Performance settings
1
1
1
1
7.3
Controller internal / external
internal
internal
internal
internal
1)
2)
The heating circulating pump and the controller of the heat pump must be ready for operation at all times.
3)
s. EC Declaration of Conformity
4)
Please keep in mind that more space is required for pipe connection, operation and maintenanc.
Subject to technical modifications
Issued: 23.04.2004
These
data
characterize
the
size
and
performance
capability
of
the
system.
For
economic
and
energetic
reasons,
additional
factors such as balance point and control need to be taken into consideration. Abbreviations have the following meaning, e.g. B10 /
W55: heat source temperature 10 °C and heating water supply temperature 55 °C.