Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating sys-
tem. This can be accomplished, for example, by installing a dual
differential pressureless manifold. When the minimum flow rate
is undershot, the plate steel exchanger in the refrigerating cycle
can freeze, which can lead to total loss of the heat pump.
Antifreeze
A method of manual drainage (see illustration) should be pro-
vided for heat pumps which are exposed to frost. The antifreeze
function of the heat pump manager is active whenever the heat
pump manager and the heat circulating pump are ready for oper-
ation. If the heat pump is taken out of service or in the event of a
power failure, the system has to be drained. The heating circuit
should be operated with a suitable antifreeze if heat pump sys-
tems are implemented in buildings where a power failure can not
be detected (holiday home).
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
External temperature sensor (R1) supplied (NTC-2)
Return temperature sensor (R2) installed (NTC-10)
Flow temperature (R9) installed (NTC-10)
7.4.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump man-
ager must correspond to the sensor characteristic curve illus-
trated in Fig.7.1 on pag. 6. The only exception is the external
temperature sensor included in the scope of supply of the heat
pump (see Fig.7.2 on pag. 6)
Fig. 7.1: Sensor characteristic curve NTC-10
Fig. 7.2: Sensor characteristic curve, NTC-2 according to
DIN 44574 External temperature sensor
7.4.2 Mounting the external
temperature sensor
The temperature sensor must be mounted in such a way that all
weather conditions are taken into consideration and the meas-
ured value is not falsified.
On the external wall of a heated room used as living space,
if possible on the north or north-west side of the building
Do not install in a “sheltered position” (e.g. in a wall niche or
under a balcony)
Not in the vicinity of windows, doors, exhaust air vents, ex-
ternal lighting or heat pumps
Not to be exposed to direct sunlight at any time of year
Sensor lead:
Max. length 40 m; min. core cross-section
0.75 mm²; external diameter of the cable 4-8 mm.
Temperature in °C
-20
-15
-10
-5
0
5
10
NTC-2 in k
14.6
11.4
8.9
7.1
5.6
4.5
3.7
NTC-10 in k
67.7
53.4
42.3
33.9
27.3
22.1
18.0
15
20
25
30
35
40
45
50
55
60
2.9
2.4
2.0
1.7
1.4
1.1
1.0
0.8
0.7
0.6
14.9
12.1
10.0
8.4
7.0
5.9
5.0
4.2
3.6
3.1
([WHUQDOWHPSHUDWXUHLQ>&@
5HVLVWDQFHYDOXHLQ
>N2KP@
([WHUQDOWHPSHUDWXUHLQ>&@
5HVLVWDQFHYDOXHLQ
>N2KP@
Содержание LIH 26TE
Страница 2: ......
Страница 26: ...EN 11 452160 66 15 FD 9310 www dimplex de English LIH 26TE ...
Страница 53: ...www dimplex de 452160 66 15 FD 9310 A XIV Anhang Appendix Annexes LIH 26TE ...
Страница 54: ...A XV 452160 66 15 FD 9310 www dimplex de Anhang Appendix Annexes LIH 26TE ...
Страница 55: ...www dimplex de 452160 66 15 FD 9310 A XVI Anhang Appendix Annexes LIH 26TE ...