LIA 0608HWCF M - LIA 0911HWCF M
8
Additional model features
8.1
Type of defrosting
Reverse circulation
Reverse circulation
8.2
Frost protection, condensate tray /
Water in device protected against freezing
2
Yes / Yes
Yes / Yes
8.3
Max. operating overpressure (heat source/heat sink)
bar
3
3
9
Heat output / cooling capacity / coefficients of performance
(COP)
9.1
Heat output / coefficient of performance (COP)
EN 14511
EN 14511
at A-15 / W35
kW / ---
4.0 / 2.34
6.43 / 2.46
at A-7 / W35
kW / ---
6.21 / 2.86
8.31 / 3.11
at A-7 / W55
kW / ---
5.22 / 1.96
7.05 / 1.97
at A2 / W35
kW / ---
5.5 / 3.95
8.2 / 4.05
at A7 / W35
kW / ---
6.2 / 5.0
10.0 / 5.0
at A7 / W45
kW / ---
6.35 / 3.75
10.0 / 3.8
at A7 / W55
kW / ---
6.9 / 2.91
9.72 / 3.04
at A10 / W35
kW / ---
7.35 / 5.02
10.0 / 5.13
at A20 / W35
kW / ---
6.98 / 5.91
10.7 / 6.72
at A20 / W55
kW / ---
6.81 / 3.6
9.85 / 3.88
9.2
Cooling capacity / coefficient of performance (COP)
at A25 / W10
kW / ---
7.37 / 4.17
8.26 / 4.56
at A25 / W20
kW / ---
8.52 / 6.40
12.0 / 5.79
at A35 / W7
kW / ---
6.55 / 3.0
8.2 / 3.3
at A35 / W18
kW / ---
7.00 / 4.90
10.0 / 4.8
1. Please note that additional space is required for pipe connections, operation and maintenance.
2. The heat circulating pump and the heat pump controller must always be ready for operation.