LI 9TES
12 Device Information
1
Type and order code
LI 9TES
2
Design
Heat source
Air
2.1
Model
Universal
2.2
Controller
Integrated
2.3
Thermal energy metering
Optional (as an accessory)
2.4
Installation location
Indoors
2.5
Performance levels
1
3
Operating limits
3.1
Heating water flow / return
° C
up to 60
1
± 2 / from 18
3.2
Air °
C
-20 bis +35
4
Flow / sound
4.1
Heating water flow internal pressure differential
Nominal flow according to EN 14511 at A7 / W35-30
m³/h / Pa
1,4 / 15300
at A7 / W45-40
m³/h / Pa
1,3 / 13200
at A7 / W55-47
m³/h / Pa
0,8 / 5000
Minimum heating water flow
m³/h / Pa
0,8 / 5000
4.2
Sound power level according to EN 12102
device/external
2
dB(A)
53 / 60
4.3
Sound pressure level at a distance of 1 m indoors
3
dB(A)
48
4.4
Heating water flow
m³/h / Pa
with an internal pressure differential of
m³/h / Pa
3500 / 0
2800 / 25
5
Dimensions, weight and filling quantities
5.1
Device dimensions
4
H x B x T mm
1250 x 750 x 680
5.2
Weight of the transportable unit(s) incl. packaging
kg
181
5.3
Device connections for heating system
Inches
R 1“
5.4
Air duct connection (air intake side)
mm
440 x 440
Air duct connection (air outlet side)
mm
440 x 440
5.5
Refrigerant / total filling weight
type / kg
R410A / 1,9
5.6
Lubricant; total filling quantity
type / litres
Polyolester (POE) / 1,2
5.7
Volume of heating water in device
litres
3,2
6
Electrical connection
6.1
Supply voltage / fuse protection
separate infeed:
heat pump
3~/PE 400 V (50 Hz) / C10 A
separate infeed:
2nd heat generator
3~/PE 400 V (50 Hz) / C10 A
combined infeed:
heat pump + 2nd heat generator
3~/PE 400 V (50 Hz) / C16 A
RCD-Type
A
6.2
Control voltage / fuse protection
1~/N/PE 230 V (50 Hz) / C13 A
6.3
Degree of protection according to EN 60 529
IP 21
6.4
Starting current limiter
Soft starter
6.5
Rotary field monitoring
yes
6.6
Starting current
A
17
6.7
Nominal power consumption at A7/W35 / max. consumption
5
(without 2nd heat generator)
kW
1,93 / 3,5
6.8
Nominal current at A7/W35 / cos?
A / --
3,47 / 0,8
6.9
Power consumption of compressor protection (per compressor)W
6.10 Power consumption of fan
W
up to 230
6.11 Output of electric heating element (2nd heat generator)
kW
6
Содержание LI 9TES
Страница 2: ......
Страница 34: ...EN 16 452161 66 02 FD 9601 www dimplex de English LI 9TES ...
Страница 50: ...FR 16 452161 66 02 FD 9601 www dimplex de Français LI 9TES ...
Страница 57: ...www dimplex de 452161 66 02 FD 9601 A VII Anhang Appendix Annexes LI 9TES 3 2 Last Load Charge ...
Страница 66: ...A XVI 452161 66 02 FD 9601 www dimplex de Anhang Appendix Annexes LI 9TES ...
Страница 67: ...www dimplex de 452161 66 02 FD 9601 A XVII Anhang Appendix Annexes LI 9TES ...