EN-10
452163.66.65 · FD 9702
www.dimplex.de
English
LA 6S-TU - LA 6S-TUR
11 Device information
1
Type and order code
LA 6S-TU
2
Design
Heat source
Air
2.1
Model
Universal
2.2
Controller
WPM wall-mounted
2.3
Installation location
Outdoors
2.4
Thermal energy metering
Integrated
2.5
Performance levels
1
3
Operating limits
3.1
Heating water flow / return
1
°C
up to 60 ± 2 / from 18
3.2
Air (heating)
°C
-22 to +35
4
Flow
2
/ sound
4.1
Heating water flow / internal pressure differential
Nominal flow according to EN 14511 with A7 / W35...30
m³/h / Pa
1,15 / 12000
with A7 / W45...40
m³/h / Pa
1,08 / 10600
with A7 / W55...47
m³/h / Pa
0,66 / 4000
4.2
Minimum heating water flow rate
m³/h / Pa
0,66 / 4000
4.3
Sound power level according to EN 12102
Normal operation/reduced operation
3
4
dB(A)
56 / 52
4.4
Sound pressure level at a distance of 10 m (air outlet side)
5
Normal operation/reduced operation
dB(A)
28 / 24
4.5
Air flow
Normal operation
m³/h
2700
5
Dimensions, weight and filling quantities
5.1
Device dimensions without connections
H x W x L mm
945 x 1350 x 600
5.2
Device connections for heating
inches
G 1“ A
5.3
Weight of the transportable unit(s) incl. packaging
kg
185
5.4
Refrigerant / total filling weight
Type / kg
R410A / 3,4
5.5
GWP value / CO
2
equivalent
--- / t
2088 / 7
5.6
Refrigeration circuit hermetically sealed
yes
5.7
Lubricant / total filling weight
Type / litres
Polyolester (POE)/0.7
5.8
Volume of heating water in device
Litres
1,9
6
Electrical connection
6.1
Supply voltage / fusing / RCD type
3~/N/PE 400 V (50 Hz) / C10 A / A
6.2
Control voltage / fusing via WPM
1~/N/PE 230 V (50 Hz) / 4 AT
6.3
Degree of protection according to EN 60529
IP 24
6.4
Starting current limiter
no
6.5
Rotary field monitoring
no
6.6
Starting current with soft starter
A
28
6.7
Nominal power consumption A7/ W35/ max. power consumption
kW
1,4 / 2,93
6.8
Nominal current A7 /W35 / cos
ϕ
A / ---
2,88 / 0,8
6.9
Power consumption of compressor protection (per compressor)
W
--
6.10 Power consumption fan
W
< 125
7
Complies with the European safety regulations
6
8
Additional model features
8.1
Type of defrosting
Reverse circulation
8.2
Condensate tray frost protection / water in device is protected from freezing
7
yes
8.3
Max. operating pressure (heat sink)
bar
3,0