background image

 

1

Operating and Installation Instructions

 

 

KBE   Wall Convectors

 

453321.66.85gb  

 

07/04/A

 

 

1. Important Information

 

Please read with care all of the information provided in  
these instructions in a safe place for future reference. Pass 
them on to any subsequent purchaser of the unit. 

− 

The unit is suitable solely for heating the air in a closed 
room. 

− 

Only a qualified electrician should install or repair this 
unit. 

− 

In the event of a fault, disconnect the unit from the 
main power supply (switch off or unscrew fuse) 

− 

Do not cover the unit - fire hazard! 

− 

Caution! The unit is hot to the touch when in operation. 

− 

Do not operate the unit unattended if there are small 
children in the vicinity. 

− 

Do not insert objects of any kind through the apertures 
in the unit. 

− 

The unit should be installed so that its controls are out 
of reach of anyone in the bathtub or under the shower. 
VDE 0100 Part 701 specifies that the unit may not be 
installed in the protection zone. Keep the flap over the 
controls closed. 

− 

An isolating device must be provided in the electrical 
wiring specified (for example, a miniature circuit-
breaker). It must have a contact gap of at least 3 mm 
at each pole. 

− 

Substances which could lead to ignition or thermal 
decomposition inside the unit (for example, carpet or 
floor tile adhesives) must not be used unless you are 
certain the unit has cooled down to room temperature. 

 

2. Installation, Wiring, Minimum Clearances

 

The convector may only be installed in a horizontal 
position (the control panel must always be at the top). 
The convector must be installed in such a way that 
flammable objects cannot ignite. 
It is permissible to mount the convector on a wooden wall. 
The convector must not be mounted directly beneath a 
wall power socket. 
It is essential that you observe the minimum clearances A, 
B and C specified in the installation diagram, particularly 
as regards clearances from easily flammable objects. 
Make sure that air can flow into or out of the convector 
without being obstructed. 

Minimum clearances 

 

mm 

150 

150 

150 

 

 
The convector is not mounted directly on the wall but 
installed in a wall frame. 
-  Drill the mounting holes for the wall frame. 
-  Screw the wall frame to the wall. 
-  Fit the convector in the wall frame using the slots on 

the back of the unit. 

-  Swing the unit up and against the wall, latching it into 

the top part of the wall frame. 

 
3. Electrical Connection

 

In addition to the leads for the electrical power supply (L1 
= brown, N = blue, PE = green / yellow) a marked control 
wire (black) is provided for external temperature reduction 
via an external timer or pilot unit, for example.  

See section 8 for circuit diagram. 

 

4. Heating

 

Switch On/Off 

A = Off, no function. 
M = On. Thermostat regulates the room temperature to the 

value specified at the thermostat knob. 

 

Thermostat 

The Heater is equipped with a thermostat which you can use 
to set the room temperature you want. The 

 setting

 of the 

thermostat is for frost protection. Here the thermostat keeps 
the room temperature at around 7°C. A room temperature of 
about 21 °C corresponds to a ‘6’ setting on the thermostat 
knob. 
 

B

A

500

B

A

Min.

C

 

 

 

GB 

Switch On/Off 

Thermostat 

Отзывы: