background image

www.dimplex.com

2

Supply Entry 
Knockouts

Remove 

screw, from 

each side

Figure 2

   WARNING: 

This  heater  must  be  properly  installed  before  it  is 

used.

CONTROLS

 (Factory installed)

• 

Fan delay

 - The heater is equipped with a fan delay control. The 

fan will remain on for a few moments after the elements are de-

energized.

• 

Automatic High Limit

 - Each heater is equipped with automatic 

reset thermal cutouts located above the elements. Should these 

safety switches operate, they will automatically reset once the ele

-

ment reaches a safe operating temperature, however the cause 

of the high limit condition should be determined and corrected to 

insure satisfactory operation.

• 

Thermostat

 - All heaters are equipped with a hydraulic type ther

-

mostat which has a nominal operating range of 40°F (5°C) (low) to 

100°F (38°C) (high).

OPTIONAL CONTROLS

 (Field installed) 

• 

Remote line voltage thermostat

 - An optional remote line vol

-

tage thermostat may be used to control the unit. Field connections 

may simply be connected to the control terminal block located in 

the  wiring  compartment  in  accordance  with  with  the  wiring  dia

-

gram attached to the access door. 

 CAUTION: Disconnect the built-in thermostat

• 

Remote Low voltage thermostat with relay

  - An  optional  low 

voltage thermostat/relay kit may be used to control the unit (Cata

-

logue #EUAR11, 120V primary; EUAR21, 208V primary; EUAR31, 

240V  primary;  EUAR41,  277V  primary).  The  relay  is  installed 

through  the  hole  provided  in  the  back  left  corner  of  the  blower 

deck. Power connections are made to the control terminal block 

located in the wiring compartment in accordance with the wiring 

diagram attached to the access door. A knockout is provided on 

the left side of the heater for the 24 volt thermostat control wiring. 

It is important that the plastic insulation bushing be installed into 

the knockout hole before running low voltage control wiring. The 

thermostat is installed and wired in accordance with the instruc

-

tions packaged with the kit. 

 CAUTION: Disconnect the built-in thermostat

• 

Fan only Switch

 - An optional “Fan only” switch kit (Catalogue 

EUAF2) is available for field installation in the unit. The fan switch 

is mounted in the space provided adjacent to the built-in thermos

-

tat located at the front of the unit. Field connections are made at 

the control terminal block in accordance with the unit wiring dia

-

gram.

START-UP:

1. 

Before the unit is energized, the discharge louvers should be be 

adjusted for desired air deflection. Louvers may be adjusted for 

either  horizontal  or  vertical  air  deflection  by  rotating  the  louvre 

frame. (See figure 3)

2.  Check to see that all controls and optional accessories are ope-

rating properly.

 Operation

Figure 3

Wiring

!

NOTE: 

This is a sample wiring diagram for the wiring diagram for your 

specific model see the wiring diagram located on the inner panel.

 

Maintenance

 CAUTION: 

Before removing the front cover for cleaning, make 

certain the power has been turned off at the circuit breaker panel.

 CAUTION: 

Allow adequate time for the element and body casing 

to cool before attempting to work on the heater.

1. 

Under normal conditions, the heater should be cleaned once a 

year. 

DISCONNECT ALL POWER

 before cleaning or servicing 

the heater.

2. 

All motors are lubricated for extended life operation, and will not 

have to be oiled.

Отзывы: