www.dimplex.com

2

Supply Entry 
Knockouts

Remove 

screw, from 

each side

Figure 2

   WARNING: 

This heater must be properly installed before 

it is used.

CONTROLS

 (Factory installed)

• 

Fan delay

 - The heater is equipped with a fan delay control. 

The fan will remain on for a few moments after the elements 

are de-energized.

• 

Automatic High Limit

 - Each heater is equipped with auto-

matic  reset  thermal  cutouts  located  above  the  elements. 

Should  these  safety  switches  operate,  they  will  automa-

tically  reset  once  the  element  reaches  a  safe  operating 

temperature, however the cause of the high limit condition 

should be determined and corrected to insure satisfactory 

operation.

• 

Thermostat

 - All heaters are equipped with a hydraulic type 

thermostat  which  has  a  nominal  operating  range  of  40°F 

(5°C) (low) to 100°F (38°F) (high).

OPTIONAL CONTROLS

 (Field installed) 

• 

Remote line voltage thermostat

 - An optional remote line 

voltage thermostat may be used to control the unit. Field 

connections may simply be connected to the control termi-

nal block located in the wiring compartment in accordance 

with with the wiring diagram attached to the access door. 

 CAUTION: Disconnect the built-in thermostat

• 

Remote Low voltage thermostat with relay

 - An optional 

low voltage thermostat/relay kit may be used to control the 

unit (Catalogue #EUAR11, 120V primary; EUAR21, 208V 

primary; EUAR31, 240V primary; EUAR41, 277V primary). 

The relay is installed through the hole provided in the back 

left corner of the blower deck. Power connections are made 

to the control terminal block located in the wiring compart-

ment in accordance with the wiring diagram attached to the 

access door. A knockout is provided on the left side of the 

heater for the 24 volt thermostat control wiring. It is impor-

tant that the plastic insulation bushing be installed into the 

knockout  hole  before  running  low  voltage  control  wiring. 

The  thermostat  is  installed  and  wired  in  accordance  with 

the instructions packaged with the kit. 

 CAUTION: Disconnect the built-in thermostat

• 

Fan only Switch

 - An optional “Fan only” switch kit (Cata-

logue EUAF2) is available for field installation in the unit. 

The fan switch is mounted in the space provided adjacent to 

the built-in thermostat located at the front of the unit. Field 

connections are made at the control terminal block in accor-

dance with the unit wiring diagram.

START-UP:

1. 

Before the unit is energized, the discharge louvers should 

be be adjusted for desired air deflection. Louvers may be 

adjusted  for  either  horizontal  or  vertical  air  deflection  by 

rotating the louvre frame. (See figure 3)

2.  Check to see that all controls and optional accessories are 

operating properly.

 Operation

Figure 3

tric codes.

3. 

Remove two screws securing the access door (See Figu-

re 2) and swing the door down to expose the wiring and 

control compartment.

4. 

Three knockouts are provided at the back of the heater for 

power and control wiring. (See Figure 2)

5. 

Rough-in  branch  circuit  wiring  to  the  heater  using  wire 

rated  for  167°F  (75°C).  Wire  heater  supply  according  to 

diagram attached to the access door.

Wiring

!

NOTE: 

This is a sample wiring diagram for the wiring diagram for your 

specific model see the wiring diagram located on the inner panel.