If balanced cold water supply is required a connection 

can be taken from the bottom of the inlet group. 

6.2.3  Balanced Cold Water Supply

It is also recommended to install a drain valve (not 

supplied) in the lowest point of the cold water feed to 

the water heater. This allows the water heater to be 

drained in a controlled manner should this become 

necessary. 

6.2.4  Drain Valve

6.3  Hot Water Outlet

The hot water pipework is to be directly connected to 

the hot water outlet connection on the water heater.

A thermostatic mixing valve may be required to limit 

the outlet temperature. In this case, the valve should 

be installed following the manufacturer’s instructions, 

ensuring none of the safety equipment has been 

isolated, (i.e. make sure the connection to the 

thermostatic mixing valve is taken after the safety 

equipment of the inlet group).

6.3.1  Thermostatic Mixing Valve

6.4  Discharge Pipes from  Safety 

 Devices

6.4.1  Discharge Pipe D1

The temperature and pressure relief valve must be 

discharged directly or by way of a manifold via a short 

length of metal pipe (D1) into a tundish; and the 

discharge pipe must be installed in a continuously 

downward direction and in a frost free environment. 

Water may drip from the discharge pipe of the 

pressure relief device and this pipe must be left open to 

the atmosphere.

The diameter of discharge pipe (D1) should not be less 

than the nominal outlet size of the safety device, e.g. 

temperature relief valve.

6.4.2  Discharge Pipe D2

For a detailed description of the discharge pipework D2  

(see Section 5.8.1).

6.4.3 Tundish

The tundish should be vertical, located in the same 

space as the unvented hot water storage system and be 

fitted as close as possible to, and lower than, the safety 

device, with no more than 600mm of pipe between the 

valve outlet and the tundish (see Figure 2). 

Where discharge may not be apparent, e.g. in dwellings 

occupied by people with impaired vision or mobility, 

consideration should be given to the installation of a 

suitable safety device to warn when discharge takes 

place, e.g. electronically operated.

Note: To comply with the Water Supply (Water Fittings) 

Regulations, the tundish should incorporate a suitable 

air gap.

Note: It is important that the tundish is 

positioned away from any electrical components.

6.5  Immersion Heater

The water heater must be filled with water 

before switching on the immersion heater. Failure 

to do so will damage the element and void any 

guarantee on the product.

It is recommended to insulate the hot water pipework 

from the water heater to the outlets, to reduce the 

energy requirements for providing hot water. It is also 

recommended to insulate all other exposed pipework, 

such as the T&P to the tundish, the coil flow and return 

and the cold water inlet pipes.

6.3.2  Pipe Insulation

The Edel Air Source Heat Pump Water Heater comes 

with the immersion heater factory fitted and wired. The 

immersion heater incorporates an independent non-self 

resetting over temperature cut-out. Should this 

operate, please investigate the cause of the cut out 

before resetting (See Troubleshooting).

Cold water 

from Mains

Balanced Cold 

Water Supply

Expansion Vessel 

Connection

Cold Water Inlet

Expansion Relief 

Valve

Figure 4: Detail showing the connection of the expansion 

vessel to the inlet group

 

Where a manifold is used it should be sized to accept 

and discharge the total discharge from all the D1 

discharge pipes connected to it.

The discharge pipework from the expansion relief valve 

must be installed constantly falling to an open point of 

discharge. It is recommended to combine it with the 

discharge of the temperature and pressure relief valve.

Note: The T&P valve is pre-sealed and if moved the 

seal will be broken, should this occur, it will need to 

be resealed with an appropriate sealant (Dimplex part 

number R00836-1).

Installation

Dial to adjust

water temperature

Earth (green/yellow)

Live (brown)

Neutral (blue)

Figure 5: Wiring diagram for Immersion Heater

!

Содержание Edel EDL200UK-630

Страница 1: ...Air Source Heat Pump Water Heater Installation and User Instructions RD00662 5 Important This manual must be left with user after Installation ...

Страница 2: ...uture reference Installers are required to carry out installation commissioning and ser vicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot Water Industry Council who manage and promote the Scheme Visit www benchmark org uk for more infor mation The Hot Water Association HWA Charter is a code of Practice which requires that all members adhere t...

Страница 3: ...ns 11 6 9 1 Accessing Electrical Connections 11 6 9 1 1 Electricity Provider Contact 11 6 9 1 2 Connecting the PV Function 11 7 Set Up and Use 12 7 1 Commissioning 12 7 2 Using your Hot Water Heat Pump 13 7 3 Control Box 13 7 4 Setting the Language 13 7 5 Setting the Time 13 7 6 Setting the Water Temperature 14 7 7 Standby Mode 14 7 8 Boost Function 14 7 9 Electric Mode 14 7 10 Programming 15 7 11...

Страница 4: ...r and or user This appliance can be used by children aged 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of appliance in a safe way and understanding the hazards involved some parts of this product can be come hot and cause burns Children shall not play with the...

Страница 5: ...lations standards and codes of practice will void the guarantee of this product Please note that handling installation and use of this product is subject to the Health and Safety at Work Act If the unit is not installed immediately it should remain in its protective packaging with all pipe protectors end caps applied to prevent damage and dirt deposit inside the water heater and the coil i Dimplex...

Страница 6: ...In humid rooms which have a lot of steam or vapour for example a bathroom The water heater may be located on any flat and level surface provided it is sufficiently robust to support the weight of the water heater when full of water please see technical data and suitably accessible for replacement maintenance without specialist tools or lifting equipment as this will void the warranty conditions Pa...

Страница 7: ...ple Note An alternative approach for sizing discharge pipes would be to follow Annex D section D 2 of BS 6700 2006 A1 2009 This example is for a G temperature relief valve with a discharge pipe D2 having 4 No 22mm elbows and length of 7m from the tundish to the point of discharge From Table 2 the maximum resistance allowed for a straight length of 22mm copper discharge pipe D2 from a G temperature...

Страница 8: ... No isolating device should be fitted between the water heater and the cold water inlet group Furthermore it is recommended to mount the vessel higher than the water heater to avoid having to drain the water heater when maintaining and replacing the expansion vessel It is important to check the pre charge pressure of the expansion vessel membrane before filling the cylinder The pre charge should b...

Страница 9: ...ngs occupied by people with impaired vision or mobility consideration should be given to the installation of a suitable safety device to warn when discharge takes place e g electronically operated Note To comply with the Water Supply Water Fittings Regulations the tundish should incorporate a suitable air gap Note It is important that the tundish is positioned away from any electrical components 6...

Страница 10: ...ake 2m straight X 5 4 8 24 0 90 bend X 3 12 5 37 5 External terminal X 1 51 0 51 0 Air Exhaust 2m straight X 4 4 8 19 2 90 bend X 2 12 5 25 0 External terminal X 1 51 0 51 0 Total System Calculated Pressure Drop 320m3 hr 207 7 Pa 6 7 1 Worked Example The pressure drop information provided is for 160mm semi rigid Ubbink ducting other ducting manufacturers components may be used howev er the total m...

Страница 11: ...choose load shedding level 1 the electrical back up is prevented from running If you choose load shedding level 0 both the electrical back up and the heat pump will be prevented from running see Section 7 10 2 4 To prevent electrical backup operating during peak hours if a volt free output is not available from the meter a timer switch should be used if Switch off backup not allowed Switch on back...

Страница 12: ...ischarge and check after closing that valve is not dripping 9 Open expansion relief valve to ensure proper discharge and check after closing that valve is not dripping 10 Check all shower outlets toilet cisterns and other draw off points for leaks or dripping especially when replacing a vented unit Open all water outlets to purge air from pipework and ensure proper operation 11 Instruct user in th...

Страница 13: ...rature remains in the authorised 7 C to 35 C range Outside of this range electrical backup ensures that the domestic hot water is heated The domestic hot water temperature provided by the heat pump is adjustable up to 60 C In case of high domestic hot water consumption the domestic hot water heater has a comfort function which increases the heating capacity when there is less than 1 3 of the tank ...

Страница 14: ...e This function can be programmed to run between 1 and 99 days and is effective as soon as the number of days has been confirmed HOLIDAYS HOLI RETURN 8 Set number of days in standby mode Enter HOLIDAY mode switches off automatically at the same time when the number of days set has ended Throughout the holiday period the heat pump water heater shows Holi Return on the display screen as well as a co...

Страница 15: ... exisitng programme MONDAY Set Up and Use Frost PT Frost Protection Mode ECO Heat Pump Only Running CONF Heat Pump Only Running electrical back up if needed 7 10 Programming Heating time for the tank varies according to the outdoor temperature Programming enables you to define the periods of time the appliance runs in Economy Comfort or Off mode freeze protection mode Electrical backup is not allo...

Страница 16: ...ial until the screen displays Inst Menu Press the Clock and Menu buttons simultaneously Keep both buttons pressed down until the screen goes blank 7 11 1 PV Mode Setting Description Unit Range Factory setting mode pv Photovoltaic mode activated yes no no priority Anti legionellosis cycle time intervals yes no yes Yes the signals from connectors 1 and 2 take precedence over eco holiday and frost pr...

Страница 17: ...temperature reaches 43o C The heat pump will complete the remaining charge to set temperature 7 11 2 3 Minimum Temperature To C Min No To C Min 43 o c Select Mode Enter It is possible to allow the operation of the immersion heater along with the heat pump to prevent the water temperature falling below a minimum comfort temperature of 38 C The immersion will then heat the water to 43 C once this te...

Страница 18: ...of locking for accessing the menus In the Installer menu turn the dial to Locking LOCKING LOCKING NO Select No Enter NO Locking is not activated but manual locking is possible by pressing Menu for 3 seconds 50oC UNLOCK NO Select Yes Enter Press for 3 secs AUTO To lock menu access with temporary unlocking 60 sec press Menu for 3 seconds Without gaining access through the installer menu and provided...

Страница 19: ... inspection can be carried out by removing the immersion heater and using an endoscope to examine the heater When draining the tank ensure that there is a large enough air inlet at the top to avoid any depression in the tank Products such as brushes with steel bristles scouring powder and any bleach based product or chlorinated derivative should be avoided Waste electrical product should not be di...

Страница 20: ... higher than the volume in the tank The time period the appliance operates is not too short 12hrs minimum if connected to piping The water temperature is not set too low Condensates are not drain ing The draining system for dirt or blockages Remove the cover see Section 6 9 1 and check the opening That tubes do not have bends or U shapes that can collect water That the end of the tube is not block...

Страница 21: ...sel fixing kit R00094 2 DN16 3 4 BSP x 1000 flex pipe R00095 1 1 2 BSP T P valve R00020 1 15 x 22 straight PE tundish R00047 1 Temp sensor 25 C 1243950 C3S PCB Controller 1244096 70 85 C Thermostat 4992886 1200W electric heating element 1243926 Electric heating seal 1657452 PCB Display PGM Cable 4592570 Display Screen Dial 1758866 Thread sealant R00836 1 Air Source Heat Pump Water Heater Instal la...

Страница 22: ...maintained continuously at the standard set temperature if no signal or control is connected to the external control switch OVER PRESS Heat pump pressure too high No water in tank Water is too hot 75 C Water sensor removed from tank Defective water sensor Check that the tank has been properly filled with water and purged of air Change the water sensor Check that the water sensor is in the right po...

Страница 23: ...t being in contact with a part which vibrates Replace expansion valve The compressor is not working and safety temperature is activated Weakness in compressor Replace compressor ERR 02 Incorrect temperature sensor readings The air and water sensors are the wrong way round on the electronics board The de icing sensor is connected to the air input the air sensor is connected to the water input the w...

Страница 24: ...rmation 9 1 Warranty Limits Please read the following statements carefully as it affects your warranty Please ensure that the installer has fully completed the Benchmark Checklist on the inside back pages of this document and that you have signed it to say that you have received a full and clear explanation of its operation The installer is legally required to complete a commissioning checklist as...

Страница 25: ...id Water supply being other than cold domestic water such as rainwater or water from a well or which has particularly hostile or abnormal properties which do not comply with the national rules and current standards DTU 60 1 additional clause 4 hot water The appliance being switched on before it is filled 9 1 2 2 Handling Cases unlimited where warranty is void Any damage sustained by impacts or fal...

Страница 26: ...26 B C D E A 152 Figure 11 Edel Air Source Water Heater Dimensions for reference only Technical Data and Product Fiche 10 Technical Data and Product Fiche Air Intake Air Discharge ...

Страница 27: ...d Product Fiche Cylinder is tested in accordance with EN12897 2006 GDC Group Ltd Edel Air Source Water Heater Product Fiche Reference EDL200UK 630 EDL270UK 630 Load Profile Primary M L Energy Rating A A COP 3 37 3 14 Thermostat Setting 55 C 55 C Sound Level Indoors dB 48 48 Sound Level Outdoors dB 40 40 Average Climatic Conditions Average Energy Consumption kWh 377 746 Water Heating Efficiency 136...

Страница 28: ...SP 1 2 kW 240V Ventilation Air flow rate 325 m3 h Air temperature 7 C to 35 C Max air pipe length rigid piping 20m in total intake and rejection Condensates flow rate 0 3 L h Condensates drainage pipe 18 23 mm Safety Components Pressure reducing valve and strainer 3 bar Expansion relief valve 6 bar Temperature and pressure relief valve 7 bar 90 C 1 2 BSP Factory pressure test 12 bar Integrated ele...

Страница 29: ...29 Power Supply Green Yellow Black Blue Brown Black Blue Blue Black Sensors Black Black Black Black Blue Black Blue Brown Black Brown Communication Bus Display 1 2 Red Fan B1244454 F HPS DV ...

Страница 30: ...2 Red Blue Blue Black Brown Blue Green Yellow Blue Black Blue Blue Red Red Blue HTS WTS HPS High Pressure Switch C25 Compressor Start Capacitor C2 Fan Capacitor C4 Valve F Fan DV Defrost Valve RE Immersion Heater LTS Immersion Heater Safety Cut out WTS Immersion Heater Water Temp Stat 30 ...

Страница 31: ...31 Notes ...

Страница 32: ...32 Notes ...

Страница 33: ...33 Notes ...

Страница 34: ...e and pressure relief valve and expansion valve been fitted and discharge tested Yes No The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes Are all energy sources fitted with a cut out device Yes No Has the expansion vessel or internal air space been checked Yes No THERMAL STORES ONLY What store temperature is achievable C What is the max...

Страница 35: ...omments Signature SERVICE 3 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 4 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 5 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 6 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 7 Date Engineer Name Company Name Telephone Number Comments Si...

Страница 36: ...len Dimplex reserve the right to revise products literature and guarantee terms without prior notice due to a policy of continuous improvement www KIWA co uk www HWA co uk To speak to customer services please contact GDC Group Ltd Millbrook House Grange Drive Hedge End Southampton SO30 2DF Telephone 0844 879 3588 Fax 0844 879 3583 Email customer services gdcgroup co uk ...

Отзывы: