3 Assembly 

3.1 Hydraulic integration of the flow meter

NOTE

º

The sensors are only installed after the hydraulic integration has been
completed.

ATTENTION!

!!

Please observe the flow direction of the plastic tube (VFS measuring
tube). The flow direction is indicated by an arrow on the outside of the
plastic pipe.

ATTENTION!

!!

All components of the DFM 1988 must be installed in a dry and frost-free
location. Ensure that no condensation forms on the electronics module.

The  VFS  measuring  tube  must  be  mounted  close  to  the  cold
water inlet of the cylinder. The domestic hot water outlet sensor

(R3.2) must be mounted close to the domestic hot water cylinder
and adequately insulated.
Please observe the direction of flow  when installing  the plastic
pipe (VFS measuring tube). The flow direction is indicated by an
arrow on the outside of the pipe.
The screw connections included in the scope of supply enable
simple integration into the domestic hot water circuit, and can be
used.

ATTENTION!

!!

The electronics module must be mounted on a wall in the immediate
vicinity. The sensor lines are approx. 1.2 m long and must not be
extended.

Fig. 3.1:Integration diagram for activating the electric flange heat-
er in the domestic hot water cylinder

M

Fig. 3.2:Domestic hot water outlet with temperature sensor

Fig. 3.3:

Cold water inlet domestic hot water cylinder

for the electric flange heater
in the domestic hot water cylinder

 

R1“ external thread
domestic hot water outlet
on the domestic hot water cylinder

R1“ external thread
cold water inlet cylinder

Reducing sleeve      1“ -

Transition sleeve ¾“ -->
in accordance with the 
connection pipe diameter
(16 / 18 or 22)
(not included in the scope of supply)   

Calming section 
approx. 200 mm

O-rings (x 2, see image for installation, 
surrounding groove must remain free) for 
sensor sealing and mounting clip for affixing 
sensor included in the scope of supply 

Screw connection      ¾“ – 1“ 

VFS-Sensor 5-100 mounted 
with O-rings and mounting clip. 
Ensure that the VFS sensor is installed 
the right way round! (with cable outlet 
upwards in the direction of flow - as 
shown here. Moisten the O-rings for 
installation with water or, for preference, 
O-ring grease. 

VFS measuring tube 5-100 

Screw connection   ¾“ – 1“ 

 ¾“

Содержание DFM 1988

Страница 1: ...ion d installation et d utilisation Bestell Nr Order no No de commande 452114 66 95 DE EN FR FD 9801 Durchfluss mengenmessung f r Warmwasser speicher Flow rate measurement for domestic hot water cylin...

Страница 2: ......

Страница 3: ...Allgemeine Beschreibung DE 3 2 2 Lieferumfang DE 3 3 Montage DE 4 3 1 Hydraulische Einbindung des Durchflussmessers DE 4 3 2 Elektrischer Anschluss DE 5 3 3 Anschlussplan allgemein DE 8 4 Betrieb DE 9...

Страница 4: ...ber 60 erreicht werden kann 1 2 Bestimmungsgem er Gebrauch Dieses Ger t ist nur f r den vom Hersteller vorgesehenen Ver wendungszweck freigegeben Das Ger t dient der Erfassung und Auswertung der Durc...

Страница 5: ...mwasserspeichers z B mit einer W rme pumpe zu erm glichen HINWEIS Durch regelm ige Pr fungen ist die Funktion der elektrischen Zusatzheizung und des DFM 1988 durch den Anlagenbetreiber sicherzustellen...

Страница 6: ...ungen erm glichen eine einfache Einbindung in den Warmwasserkreis ACHTUNG Das Elektronikmodul ist in unmittelbarer N he an der Wand zu befestigen Die Sensorleitungen sind ca 1 2 m lang und d rfen nich...

Страница 7: ...er Seite des Str mungsaustritts des Messrohrs befindet Abb 3 4 Schaltplan mit Ansteuerung einer elektrischen Zusatzheizung Legende Ex Elektroheizung F1 Steuersicherung 230 V 2 5 AT J1 Stecker von N20...

Страница 8: ...ID6 ID7 ID8 IDC1 B6 B7 B8 GND ID9 ID10 ID11 ID12 IDC9 field card serial card service card M13 M16 M18 K20 K21 J2 J3 J24 J1 J5 J19 J6 J4 J7 J8 J20 2 3 3 3 input 24 V m 50 to 60 Hz max power_ 40 VA 15 1...

Страница 9: ...452114 66 95 FD 9801 DE 7 DFM 1988 Deutsch Abb 3 6 Anschlussplan mit W rmepumpenmanager Flanschheizung FLH und Einschraubheizk rper CEHK...

Страница 10: ...1 N PE 230 V AC 50 Hz Warmwasser austrittsf hler Steuerleitung FLH U Durchflusssensor Kaltwassereintrittsf hler CEHK Spannungsversorgung Bauseits 1 N PE 230 V AC 50 Hz CEHK 25 3 N PE 230 V AC 50 Hz C...

Страница 11: ...chaltet den Code weiter Codeeinstellung ber Zapfmenge Code 1 Zapfmenge innerhalb von 3 Tagen muss gr er als 350 l sein Code 2 Zapfmenge innerhalb von 3 Tagen muss gr er als 450 l sein Code 3 Zapfmenge...

Страница 12: ...zeigen LED 1 Ein Anforderung 2 W rmeerzeuger aktiv LED 2 Blinkt im 1 Sekunden Takt Betrieb LED 3 Blink Code Einstellung Speichervolumen 5 1 Ger teinformation ACHTUNG Die Heizleistung der elektrischen...

Страница 13: ...male Abweichungen Volumenstrom 5 3 Druckverlustkurve Abb 5 3 Druckverlustkurve 5 4 Abmessungen Abb 5 4 Abmessungen Messrohr VFS 5 100 Volumenstrom l min 30 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50...

Страница 14: ...DE 12 452114 66 95 FD 9801 Deutsch DFM 1988...

Страница 15: ...l description EN 3 2 2 Scope of supply EN 3 3 Assembly EN 4 3 1 Hydraulic integration of the flow meter EN 4 3 2 Electrical connection EN 5 3 3 Connection diagram general EN 8 4 Operation EN 9 4 1 Mod...

Страница 16: ...mperature of over 60 can be achieved 1 2 Intended use This device is only intended for use as specified by the manufac turer The device is used to record and evaluate the flow or with drawal quantity...

Страница 17: ...t water cylinder to be heated more efficiently with a heat pump for example NOTE The function of the electric supplementary heater and the DFM 1988 must be ensured by the system operator through regul...

Страница 18: ...NTION The electronics module must be mounted on a wall in the immediate vicinity The sensor lines are approx 1 2 m long and must not be extended Fig 3 1 Integration diagram for activating the electric...

Страница 19: ...s on the outflow side of the measuring tube Fig 3 4 Circuit diagram with electric supplementary heater control Legend Ex Electric heater F1 control fuse 230 V 2 5 AT J1 plug N20 J3 terminal strip N20...

Страница 20: ...5 ID6 ID7 ID8 IDC1 B6 B7 B8 GND ID9 ID10 ID11 ID12 IDC9 field card serial card service card M13 M16 M18 K20 K21 J2 J3 J24 J1 J5 J19 J6 J4 J7 J8 J20 2 3 3 3 input 24 V m 50 to 60 Hz max power_ 40 VA 15...

Страница 21: ...452114 66 95 FD 9801 EN 7 DFM 1988 English Fig 3 6 Connection diagram with heat pump manager flange heater FLH and screw in radiator CEHK...

Страница 22: ...supply 1 N PE 230 V AC 50 Hz Domestic hot water outlet sensor Control cable FLH U Flow sensor cold water inlet sensor CEHK Power supply on site 1 N PE 230 V AC 50 Hz CEHK 25 3 N PE 230 V AC 50 Hz CEHK...

Страница 23: ...er to be drawn Code 1 volume of water to be drawn within 3 days must be greater than 350 l Code 2 volume of water to be drawn within 3 days must be greater than 450 l Code 3 volume of water to be draw...

Страница 24: ...LED 2 Flashes in 1 second cycle Operation LED 3 Flash code Setting cylinder volume 5 1 Device information ATTENTION The heat output of the electric supplementary heater must be designed so that when t...

Страница 25: ...m deviations volume flow 5 3 Pressure loss curve Fig 5 3 Pressure loss curve 5 4 Dimensions Fig 5 4 Dimensions measuring tube VFS 5 100 Volume flow l min 30 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 5...

Страница 26: ...EN 12 452114 66 95 FD 9801 English DFM 1988...

Страница 27: ...2 Fournitures FR 3 3 Montage FR 4 3 1 Int gration hydraulique du d bitm tre FR 4 3 2 Branchements lectriques FR 5 3 3 Plan de branchement g n ral FR 8 4 Mode de fonctionnement FR 9 4 1 Fonctionnement...

Страница 28: ...istribution minimale 1 2 Utilisation conforme Cet appareil ne doit tre employ que pour l affectation pr vue par le fabricant L appareil sert relever et analyser la quantit de d bit ou de pr l vement d...

Страница 29: ...au chaude sanitaire avec p ex une pompe chaleur REMARQUE Le fonctionnement du chauffage d appoint lectrique et du DFM 1988 doit tre assur par l exploitant de l installation par des contr les r guliers...

Страница 30: ...te Les c bles des capteurs sont d une longueur approximative de 1 2m et il est interdit de les rallonger Fig 3 1 Sch ma d int gration pour la commande de la cartouche chauffante lectrique dans le ball...

Страница 31: ...du tube de mesure Fig 3 4 Sch ma des connexions avec commande d un chauffage d ap point lectrique L gende Ex Chauffage lectrique F1 fusible de commande 230 V 2 5 AT J1 fiche de N20 J3 bornier de N20...

Страница 32: ...ID3 ID4 ID5 ID6 ID7 ID8 IDC1 B6 B7 B8 GND ID9 ID10 ID11 ID12 IDC9 field card serial card service card M13 M16 M18 K20 K21 J2 J3 J24 J1 J5 J19 J6 J4 J7 J8 J20 2 3 3 3 input 24 V m 50 to 60 Hz max powe...

Страница 33: ...452114 66 95 FD 9801 FR 7 DFM 1988 Fran ais Fig 3 6 Plan de branchement avec le gestionnaire de pompe chaleur la cartouche chauffante FLH et le chauffage viss CEHK...

Страница 34: ...V CA 50 Hz Sonde de la sortie d eau chaude Ligne de commande FLH U Capteur de d bit sonde d entr e d eau froide CEHK alimentation en tension par le client 1 N PE 230 V CA 50 Hz CEHK 25 3 N PE 230 V AC...

Страница 35: ...tion Code 1 la quantit de distribution en 3 jours doit d passer 350l Code 2 la quantit de distribution en 3 jours doit d passer 450l Code 3 la quantit de distribution en 3 jours doit d passer 800l Cod...

Страница 36: ...de chaleur ac tive LED 2 clignote toutes les secondes marche LED 3 Code de clignotement r glage du volume du ballon 5 1 Informations sur les appareils ATTENTION La puissance calorifique du chauffage d...

Страница 37: ...flux volumique 5 3 Courbe des pertes de pression Fig 5 3 Courbe des pertes de pression 5 4 Dimensions Fig 5 4 Dimensions du tube de mesure VFS 5 100 Flux volumique l min 30 25 20 15 10 5 0 5 10 15 20...

Страница 38: ...FR 12 452114 66 95 FD 9801 Fran ais DFM1988...

Страница 39: ...452114 66 95 FD 9801 FR 13 DFM 1988 Fran ais...

Страница 40: ...sales service addres ses please refer to the Installation and Operating Instructions for Heat Pumps Pour les conditions de garantie et les adresses SAV se r f rer aux instructions de montage et d tili...

Отзывы: