Dimplex Burgate BRG20 Скачать руководство пользователя страница 7

Symptom

Cause

Corrective Action

The fl ame effect will 
not start.

Mains plug is not plugged in.

Low water level.
 

Low voltage connector not connected 
properly. (See Fig.5)

The Transducer Unit is not sitting correctly in 
the sump

Check plug is connected to wall socket 
correctly.

Check that the water tank is full and there is 
water in the sump.

Check that the connector is inserted 
correctly. (See Fig.5)

Ensure the Transducer in sitting down into 
the moulded recess in the  sump

The fl ame effect is too 
low.

Flame effect control knob is set too low.
(See Fig.10)

The Metal Disc in the transducer might be 
dirty (See Fig.14)

The wire from the Transducer Unit is sitting 
over the metal disc

Increase level of fl ame by turning Control 
knob ‘D’ to the left slowly. (See Fig.10)

Clean the Metal Disc with soft brush 
supplied. (See Fig.14) See ‘Maintenance.’ for 
a step by step procedure.

Direct the wire to the back of the sump and 
make sure it sits into the side slot exiting the 
sump.

Unpleasant smell 
when unit is used.

Dirty or stale water.

Using unfi ltered tap water.

Clean the unit as described under 
maintenance.

Use only fi ltered tap water.

The fl ame effect has 
too much smoke.

Flame effect setting is too high.

Turn the fl ame effect  Control knob ‘D’ to 
the right, about ¼ a turn, at a time. Give the 
fl ame generator some time to adjust to the 
new setting. (See Fig.10)

Main lamps are not 
working and there are 
no fl ames or smoke.

There is no water in the water tank

Follow instructions under 

Maintenance

,  ‘Filling the water tank’.

Check the plug is connected to the wall 
socket correctly and that Switch ‘A’ Fig. 10 is 
in the ‘ON’  ( 

) position.

Troubleshooting

Содержание Burgate BRG20

Страница 1: ...Standards EN60335 2 30 and the European Standard Electromagnetic Compatibility EMC EN55014 EN60555 2 and EN60555 3 These cover the essential requirements of EEC Directives 2006 95 EC and 2004 108 EC 0...

Страница 2: ...s with a thermal control a program controller a timer or any other device that switches on the heat automatically since a fire risk exists when the heater is accidentally covered or displaced 6 UNPLUG...

Страница 3: ...he heating unit and will also reduce heat loss up the chimney BEFORE YOU START 1 Ensure that all packing items are removed read any warning labels carefully and retain all packing for possible future...

Страница 4: ...being higher then the thermostat setting THERMAL SAFETY CUT OUT A thermal safety cut out is incorporated in the fan heater to prevent damage due to overheating This can happen if the heat outlet was...

Страница 5: ...tank 2 It should be possible to view the lamps with the nozzle in place and observe which one needs to be changed 3 Put Switch A in the OFF position and unplug the fire from the mains 4 Leave the appl...

Страница 6: ...35 9 China CN 101883953 CN 200980128666 2 CN 101057105 CN 101438104 Australia AU 2009248743 AU 2007224634 Canada CA 2725214 CA 2579444 CA 2645939 International Patent Application WO 2006027272 South A...

Страница 7: ...ing Control knob D to the left slowly See Fig 10 Clean the Metal Disc with soft brush supplied See Fig 14 See Maintenance for a step by step procedure Direct the wire to the back of the sump and make...

Страница 8: ...33 33 62 39 66 Fig 1 Fig 4 Fig 4a Fig 2 Fig 3...

Страница 9: ...Fig 5 Fig 5a Fig 5b Fig 6 Fig 7 Fig 8...

Страница 10: ...Fig 9 Fig 10 Fig 11 Fig 12 Fig 13 Fig 14...

Страница 11: ...Fig 15 Fig 16 Fig 17 REMOTE CONTROL SENSOR 30 60 90...

Страница 12: ...PTON SO30 2DF TEL 0844 879 3588 FAX 0844 879 3583 WEBSITE www dimplex co uk Republic of Ireland Tel 01 8424833 c GDC Group Ltd All rights reserved Material contained in this publication may not be rep...

Отзывы: