13
Table 3-2 Pipe size recommended
Model
Tube length (equivalent)
10 m
20 m
30 m
ØD
(mm)
ØL
(mm)
ØD
(mm)
ØL
(mm)
ØD
(mm)
ØL
(mm)
DN-97332
13
10
13
10
13
10
DN-97333
13
10
13
10
13
10
DN-97334
16
13
16
13
19
13
Table 3-3 Equivalent length of the sub-assembly
Fluid tube
diameter (mm)
Equivalent length (m)
Elbow 90°
Elbow 45°
T-piece
10
0.21
0.10
0.76
13
0.24
0.12
0.76
16
0.27
0.15
0.76
19
0.30
0.18
0.76
22
0.44
0.24
1.1
28
0.56
0.30
1.4
Be careful when installing quick nipple before operation, please read the
following precautions.
1.
Remove the dust cover of the valve connector.
2.
Carefully wipe with a clean cloth and the connecting base flanks.
3.
Refrigerating oil lubricated surface mating connector.
4.
The coupling nut screwed onto a threaded joint and ensure positive
fit.
5.
The hex nut and connected to a valve body fastened until significant
resistance until the felt.
6.
Strokes with oil from a longitudinal line connecting the nut to the
ferrule; then two wrenches to tighten the nut with a quarter-turn in
order to ensure airtightness. Crossed dislocation has shown that tight
junctions. The installation process must use two wrench engagement
Содержание DN-97332