2.3. Maximum Wire Run
100’ (30 m) using 18 AWG (0.75 mm) solid core direct burial irrigation wire
200’ (60 m) using 14 AWG (2.5 mm) solid core direct burial irrigation wire
300’ (90 m) using 12 AWG (4 mm) solid core direct burial irrigation wire
3.
Initial Communication
3.1 Initiating Communication for the First Time
Use the 2 yellow-colored, sealed sensor wires on the controller to signal to
the LEIT-2 controller that it is about to be programmed. Splice the 2 yellow
sensor wires together using waterproof connectors. This splice will distinguish
that the controller is ready to commnicate with a LEIT RC2 handset. Use the
handset to connect to the controller via the Radio Uplink icon using the default
address.
3.2 Connecting to the LEIT-2 Controller for the First Time Using the
LEIT RC2 Handset
In the LEIT RC2 handset’s main menu press and highlight the RADIO UPLINK
icon. Press
and the RADIO UPLINK screen will appear. This is the default
address screen. The description in this screen is: CONTROL ID: 00, DEFAULT
SETUP.
Press
to connect to the controller. The ARE YOU SURE? screen will appear
with the Radio Uplink icon selected. Press
to connect to the controller
without an ID. After establishing communication, CONNECTED will appear
momentarily and then, CONNECTED TO: CONTROLLER ID: 00, DEFAULT SETUP.
Press
again. The UPLOADING screen appears momentarily then, CONT.
SETUP with CONTROL ID: XX (digits flashing), which means the controller’s ID
is available for modification.
To modify the controller ID, press
or
and enter a number (1-9) for the
first digit. Press
and repeat the steps with the second digit. Press
to
continue to the next step, setting controller address (the default is
DESCRIPTION). Repeat the steps for selecting the controller address or name.
The final step is to select a Client ID (A-Z) using the same steps. When
17
Option C: Valve Mounting (model 30-832)
1. Slide the wires from the controller into the valve-mounting bracket and
connect the valve-mounting bracket to the controller using the 4 screws
included (see 1).
2. Connect the incoming station wire (V1 red) to the hot wires (red) on the
solenoid using conventional dry-splice waterproof connectors. Connects the
controller incoming station common wire (V1 white) to the white wire on
the solenoid using conventional dry-splice waterproof connectors and if
needed repeat for the second valve and sensor. Leave slack on each side of
the wires so that repairs, if needed can be carried out easily (see 2).
NOTE:
V1 may be identified by label or striped wires.
3. Attach the controller into place on the top of the solenoid (see 3).
16
2
1
Detailed Installation
b
c
d