15
11. Pilot flame adjustment
The Pilot flame must be regulated for earthgas. This is done as follows:
Pilot flame ignite covering screw (10) with washer (11). Remove with small
screw driver, nozzle (C) adjust that main burner ignites well. Turn
Uclockwise reduce gas flow, anti clockwise increases gas quantity.
When operated with liquid gas, nozzle (C) turn clockwise towards stroke.
After regulating washer (11) and covering screw (10) fix gas tight.
12. Primary air adjustment
The primary air is fixed and sealed by the producer according to the country
of use and the gas type required. The adjustment is mentioned on the
packing and the type shield.
If a gas change must be undertaken, the primary gas adjustment must
follow the table below:
Type
Earth gas E(H)
20mbar
Earth gas L (LL)
20 mbar
Earth gas L
25 mbar
Liquid gas
28-30/37 mbar
Liquid gas
50 mbar
TP-JG.../G
(H) =
14 mm
14 mm
14 mm
16 mm
14 mm
TP.../G
Nut
(B) =
15 mm
15 mm
15 mm
15 mm
15 mm
Injector
(A) =
closed
closed
closed
closed
closed
Primary air adjustment types TP-JG ... / G
Primary air adjustment types TP ... / G
13. Tests
After a conversion the following requirements must be fulfilled:
Nozzle diameter and pressure must be identical to the indication of the producer
The tightness of all gas pipes and parts must be secure
Ignition, through ignition, over ignition must be guaranteed for full combustion and small
combustion operation
The flame may not lift off nor beat back to the nozzles
All burners, ignition and control arrangements must be checked for dirt, secureness and function
The closing time of the thermo electric ignition control may not exceed 60 seconds
14. Sticker
After a conversion of a gas type has been carried out a new sticker must be placed on the appliance which shows
clearly the new gas type and gas pressure.