REK31ED/REK33 (CK-G/BK)
Parameter
Description
REK31
REK33
d1
Main Set point
0 ºC
0 ºC
d2
Differential ( hysteresis )
3 ºC
3 ºC
d3
lower limit of main set point
-2 ºC
-2 ºC
d4
Upper limit of main set point
10 ºC
10 ºC
d5
Minimum time interval between the disactivation and successive activation on compressor
99sec.
300sec.
d6
Max temperature alarm differential
50 ºC
50 ºC
d7
Maximum or minimum temperature alarm delay
0
99
d8
Time interval between defrost cycle
6h
6h
d9
Max defrost cycle time
20min
20min
d10
Defrost –end temperature
5 ºC
7 ºC
d11
Time interval for supplementary defrost cycles
2min
2min
d12
Real temperature display delay at defrost end
30 min
30 min
d13
Compressor function during defrost
0
0
d14
Dripping time
1min
1min
d15
Fan operating mode during normal controller
1
d16
Fan activation delay at controller startup and after defrost
1min
d17
Fan activation temperature at controller startup and after defrosting
6 ºC
d19
Offset ?
-4 ºC
-4 ºC
d22
Unit of measure, 0=C, 1=F
0
0
d23
Compressor function during o probe failure
2
2
d24
Compressor on-time during probe failure
10 min
10 min
d25
Compressor off-time during by probe failure
10 min
10 min
d27
Serial line address
0
d34
First defrost cycle after controller startup
1
1
d38
Minimum temperature alarm differential
40 ºC
40 ºC