Document No: 9100-127-1452-00 Rev B
Page 3 of 7
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
Conduit thru Mount (Figure 2) Installation Steps:
•
For maximum long term reliability and light output, the light must be installed in free air.
o
The Linear fixture design incorporates an over-temperature control circuit that
reduces input power should internal temperatures reach a maximum level. In this
event, light output may be reduced.
•
The Linear fixture is threaded for 3/4” NPT, at the center and each end of the Power
Supply Housing, in order to be assembled to conduit.
o
Attach conduit as shown in figure 2. Use conductive pipe sealant for all fittings and
conduit.
o
Fixture is factory wired for both Pendant and Through wiring. Remove the Power
Supply Covers to attach incoming power to the white wire and black wire leads
with wire nuts at the end of the fixture. Attach the ground wire to the green ground
lead supplied at the end of the fixture. Repeat this procedure for the opposite end.
Ensure that the o-rings are properly seated in the grooves, reattach the Cover
using the screws previously removed. Tighten all screws to 15 in/lbs.
•
Connect incoming power as follows:
o
Green to Safety Ground using green ground lead supplied at the end of the fixture.
o
Neutral to white
o
Line to black
•
Restore power and verify operation.
Figure 2.
¾ NPT Plug in center
Conduit through
mounting