The DeZURIK Level Sensor Knife Gate Valve is a resilient seated valve de-
signed specifically for mounting a level sensor to a stock chest. The valve, when 
closed, allows the level sensor to be removed without draining the stock chest. 
A ratcheting lever actuator requires minimum clearance to operate the valve. 
Two purge connections for flushing the inside of the valve are included. 
 
Install the valve with the seat end away from the stock chest, and toward the 
level sensor. Refer to Installation Drawing A-42347 for dimensional information. 
Flange gaskets are required. Before installation, remove foreign material such 
as weld spatter, oil, grease, and dirt from the valve and pipeline. Tighten the 
flange bolts evenly, in a crisscross pattern, to prevent distortion of the body and 
gate. 
 
Approximately monthly, lubricate the fitting on the valve actuator with a lithium-
based grease. 
 
The gate packing is contained and compressed by the packing gland. If packing 
leakage occurs, tighten the adjustment nuts on top of the packing gland. Tighten 
the nuts evenly and gently — just enough to stop the leakage. Over tightening 
will cause excessive operating forces, and will decrease the life of the packing. 
 
1.  Relieve the pressure in the pipeline and close the valve. 

 

2.  Remove the two screws and nuts near the top of the gate and disengage 

the actuator stem from the gate by stroking the actuator (not the valve) to 
the open position. 

3.  Remove the gland nuts, washers, and packing gland. 
4.  Remove the used packing from the packing chamber. 

5. 

With the gate closed, center the gate in the body opening below the packing 
chamber.

 

6. 

Cut 3 new packing rings in 8-3/4" lengths. Assemble and pack the rings one 
at a time with the ends together, but not overlapped, first ring type CD, sec-
ond ring type ZJ, last ring type CD. Stagger the joints, on the long sides of 
the packing chamber. A square-end wood or plastic tool, driven by a ham-
mer or mallet, is recommended for packing the rings. The inside and outside 
edges of each ring are to be packed against the gate and packing chamber, 
so that each ring is compressed flat and evenly. 

 

7.  Replace the packing gland, washers, and nuts. Tighten the nuts evenly and 

finger tight, plus 1/2 turn. 

8.  Reconnect the actuator stem to the gate with the two screws and nuts. 
9.  The valve may now be pressurized. If packing leakage occurs, tighten the 

adjustment nuts on top of the packing gland. Tighten the nuts evenly and 
slowly, just enough to stop the leakage. Over tightening will cause excessive 
operating forces, and will decrease the life of the packing. 

Description 

Installation 

Lubrication 

Packing  

Adjustment 

D10107 

     Page 

2     

 

 

 

 

 

 

 

 

August 

2009 

Packing  

Replacement 

DeZURIK 

3” Level Sensor Knife Gate Valve 

WARNING! 
Pipeline pressure can propel the loose flange bolts and 
flanges, and can cause personal injury or equipment dam-
age. Relieve pipeline pressure before removing flange bolts 
and flanges.

 