5.9 Generator Port Use Setup Menu
Generator input rated power:
allowed Max. power from diesel
generator.
GEN connect to grid input:
connect the diesel generator to the
grid input port.
Smart Load Output:
This mode u�lizes the Gen input connec�on
as an output which only receives power when the ba�ery SOC
and PV power is above a user programmable threshold.
e.g. ON: 100%, OFF: 95%:
When the PV power
exceeds 500W, and ba�ery bank SOC reaches 100%, Smart Load
Port will switch on automa�cally and power the load connected.
When the ba�ery bank SOC < 95% , the Smart Load Port will
switch off automa�cally.
Mode
OFF
ON
Generator Input
SmartLoad Output
Micro Inv Input
On Grid always on
GEN connect to Grid input
Ml export to Grid cutoff
GEN PORT USE
55.00Hz
164.0V
161.0V
Rated Power
AC Couple Fre High
8000W
PORT
Set1
Smart Load OFF Ba�
• Ba�ery SOC at which the Smart load will switch off.
Smart Load ON Ba�
• Ba�ery SOC at which the Smart load will switch on. simultaneously and then the Smart load will switch on.
On Grid always on:
When click "on Grid always on" the smart load will switch on when the grid is present.
Micro Inv Input:
To use the Generator input port as a micro-inverter on grid inverter input (AC coupled), this feature will
also work with "Grid-Tied" inverters.
*
Micro Inv Input OFF
: when the ba�ery SOC exceeds se�ng value, Microinveter or grid-�ed inverter will shut down.
*
Micro Inv Input ON
: when the ba�ery SOC is lower than se�ng value, Microinveter or grid-�ed inverter will start to
work.
AC Couple Fre High:
If choosing“Micro Inv input”, as the ba�ery SOC reaches gradually se�ng value (OFF), during the
process, the microinverter output power will decrease linear. When the ba�ery SOC equals to the se�ng value (OFF),
the system frequency will become the se�ng value (AC couple Fre high) and the Microinverter will stop working.
MI export to grid cutsoff: Stop expor�ng power produced by the microinverter to the grid.
*
Note
: Micro Inv Input OFF and On is valid for some certain FW version only.
- 38 -
5.10 Advanced Func�on Setup Menu
Solar Arc Fault ON
Clear Arc_Fault
System selfcheck
BMS_Err_Stop
CEI Report
0s
2000
:
1
Backup Delay
Advanced Function
Func
Set1
DRM
Gen peak-shaving
CT Ratio
Signal Island Mode
Asymmetric phase feeding
Solar Arc Fault ON:
This is only for US.
System selfcheck:
Disable. this is only for factory.
Gen Peak-shaving:
Enable When the power of the
generator exceeds the rated value of it, the inverter will
provide the redundant part to ensure that the generator
will not overload.
DRM:
For AS4777 standard
Backup Delay:
Reserved
BMS_Err_Stop:
When it is ac�ve, if the ba�ery BMS failed
to communicate with inverter, the inverter will stop
working and report fault.
L1 L2 L3 N
Load port
Inverter
Shell
Relay
Ground cable
Signal island mode:
If "Signal island mode" is checked and When inverter is in off-grid mode, the relay on
the Neutral line (load port N line) will switch ON then the N line (load port N line) will bind to inverter ground.
Asymmetric phase feeding:
The power that the inverter of PV feeds into the grid will be balanced.