5.6 Ba�ery Setup Menu
Batt Mode
Lithium
Use Batt V
Battery Setting
Activate Battery1
Parallel bat1&bat2
Activate Battery2
Max A Charge
Batt Capacity
Max A Discharge
0A
0A
0Ah
Batt
Mode
Use Batt %
No Batt
Ba�ery capacity:
it shows your ba�ery bank size to
Deye hybrid inverter.
Use Ba� V:
Use Ba�ery Voltage for all the se�ngs (V).
Use Ba� %:
Use Ba�ery SOC for all the se�ngs (%).
Max. A charge/discharge:
Max ba�ery charge/discharge
current(0-37A for 5/6/8/10/12/15/20KW model).
For AGM and Flooded, we recommend Ah ba�ery
size x 20%= Charge/Discharge amps.
. For Lithium, we recommend Ah ba�ery size x 50% =
Charge/Discharge amps.
. For Gel, follow manufacturer' s instruc�ons.
No Ba�:
�ck this item if no ba�ery is connected
to the system.
Ac�ve ba�ery:
This feature will help recover a
ba�ery that is over discharged by slowly charging
from the solar array or grid.
This is Ba�ery Setup page.
Start =30%:
Percent S.O.C at 30% system will AutoStart a
connected generator to charge the ba�ery bank.
A = 30A:
Charge rate of 30A from the a�ached
generator in Amps.
Gen Charge:
uses the gen input of the system to charge
ba�ery bank from an a�ached generator.
Gen Signal:
Normally open relay that closes when the
Gen Start signal state is ac�ve.
Gen Force:
When the generator is connected, it is forced
to start the generator without mee�ng other condi�ons.
①②
07/08/2021 11:11:10 Thu
76%
2.00
KW
-1.39
KW
0.00
KW
KW
0
15
0
15
0
8
0
8
ON
Signal
on
2.00
This page tells the PV and diesel generator
power the load and ba�ery.
Gen Charge
Gen Signal
Gen Force
Battery Setting
Start
A
30%
30A
Batt
Set2
①
②