Safety notes

Fasten the Home Control Smoke Detector on the ceiling in the centre of the room or
at least 50 cm away from walls, ceiling joists or fixtures. The room may be up to 6 m
in height.

Fasten the Home Control Smoke Detector as horizontally as possible (inclination an-
gle no more than 20° if there is roof slope). 

Pockets of hot air can form in the ceiling ridge in rooms with ceiling slope > 20°. In
this case, fasten the Home Control Smoke Detector at least 50 cm and no more than
1 m below a roof/ceiling ridge.

Install additional Home Control Smoke Detectors if the available joists are > 20 cm
and the room to be monitored has separated areas > 36 m². If the joists are < 20 cm,
fasten the Home Control Smoke Detector to the ceiling or a joist.

Avoid fastening the Home Control Smoke Detector near air conditioners, air shafts
and other products/areas with strong draughts.

Do not fasten the Home Control Smoke Detector in rooms where there is usually
heavy steam, smoke or dust, for example in the kitchen or bathroom.

Содержание Home Control Smoke Detector

Страница 1: ...HomeControl SmokeDetector first steps...

Страница 2: ...figuration tips for your device Intended use Use the Home Control Smoke Detector as described in these instructions and in the Home Control online help to prevent damage and injuries CE conformity Whe...

Страница 3: ...tral Unit through the my devolo app and at www mydevolo com in a browser For more information about setting up the Home Control Central Unit please refer to the instal lation guide and or Home Control...

Страница 4: ...4...

Страница 5: ...respond immediately even when on the go When combined with other Home Control devices the Home Control Smoke Detector can for example addi tionally turn on the lights and open the shades via the Cent...

Страница 6: ...s case fasten the Home Control Smoke Detector at least 50 cm and no more than 1 m below a roof ceiling ridge Install additional Home Control Smoke Detectors if the available joists are 20 cm and the r...

Страница 7: ...if the surface to be moni tored is 60 m or is interrupted by ceiling joists If you install the Home Control Smoke Detector on a balcony of 2 m length and width and a surface 16 m an additional Home C...

Страница 8: ...ther the Home Control Smoke Detector is functioning properly Cigarette smoke clogs the ventilation slots and smoke inlets making the device incapable of working properly Using the test button regularl...

Страница 9: ...nd damage the device Do not use rechargeable batteries When inserting the battery make sure the polarity is correct Using the battery in correctly can damage the device After each battery change the s...

Страница 10: ...ctor Only use the Home Control Smoke Detector indoors Turn the detector anti clockwise to unscrew it from the housing backplate and access the battery com partment Battery compartment Test button with...

Страница 11: ...battery in the correct position see marking in the battery compartment in the Home Control Smoke Detector When you insert the battery it pushes down the red locking pin without the use of force This p...

Страница 12: ...Control Portal of the Home Control Central Unit For more information on the control and configuration of all devolo Home Control devices as well as application examples please refer to the Home Contro...

Страница 13: ...smoke is blown directly into the ventilation slots and smoke inlets the alarm tone sounds Steam and smoke from cooking can also trigger an alarm Therefore the Home Control Smoke Detector may not be i...

Страница 14: ...information about the actual costs of the telephone calls can be found on the devolo website Disposal Neither the Home Control Smoke Detector nor the battery may be disposed of with the household wast...

Страница 15: ...o uk documents Smoke Detector To view the documents on your computer laptop you need a PDF reader such as Acrobat Reader from Adobe You can dowload the latest version of the software at https get adob...

Страница 16: ...devolo AG Charlottenburger Allee 60 52068 Aachen Germany www devolo com 40654 0716...

Отзывы: