Generel installation instructions

The following instructions must be 

observed when installing devifl ex

™ 

DTIV heating cables:

The heating cable should be 

properly connected to the main 

electrical source.

Connection of the heating cable 

must be made by an authorized 

electrician.

The maximum effect for the 

different installations and operating 

effects must be observed.

The heating cable must not be 

pulled through valves and must 

be protected against excess strain 

and tension.

The heating cable’s bending 

diameter must not be less than 6 x 

the cables own diameter.

The heating cable’s screen must 

be earthed in accordance with the 

local electricity laws.

The heating cable must not be cut 

or exposed to strain in the areas 

of the cold cable coupling or end 

coupling.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12

13.

14

The whole heating cable, except 

the connection box and cold cable 

must be placed inside the water 

pipe.

When turning on the heating cable 

ensure that the pipe is containing 

water.

The heating cable’s resistance 

value should be measured after 

the installation. The heating cable’s 

resistance value should be as 

stated on the coupling label: -5 

- +10%.

Heating cables installed in water 

pipes must be connected via a 

RCD. 

It must be possible to turn the 

heating cable off. We recommend 

a devireg

 thermostat (see later).

A piece of non conductive tape 

must be placed between the 

sensor and the pipe

The cable must be installed accor-

ding to local installation regulation.

devireg

 610

Sensor

1" or 3/4"stuffi ng box

Heating cable

Содержание deviflex DTIV-9

Страница 1: ...nstallation Instructions deviflex DTIV drinking water cable deviflex heating cable 9 W m for frost protection of drinking water pipes drinking water pipes drinking water pipes drinking water pipes GB DAS ...

Страница 2: ...Notes ...

Страница 3: ...l specifications deviflex DTIV is delivered fully assembled with coupling and 2 5 m cold tail The effect is approx 9 W m heating cable The cabel is approved by VTT in Finland and does not con tain PVC or Halogen Cable type Conductor insulation Outer sheath Supply voltage Effect Surface temp Ambient temp when on Diameter Bending radius Cold tail Nipple Max pull DTIV Twin conductor with screen XLPE ...

Страница 4: ...The heating cable must not be cut or exposed to strain in the areas of the cold cable coupling or end coupling 1 2 3 4 5 6 7 8 9 10 11 12 13 14 The whole heating cable except the connection box and cold cable must be placed inside the water pipe When turning on the heating cable ensure that the pipe is containing water The heating cable s resistance value should be measured after the installation ...

Страница 5: ... insulated Pipe not insulated Pipe not insulated mm Insulation in mm Soil depth in cm 25 40 50 50 80 100 Insulated pipe Insulated pipe Pipe not insulated Pipe not insulated 26 32 39 52 78 104 5 0 7 0 8 0 10 0 12 0 14 0 5 0 6 0 7 0 7 5 9 0 11 0 4 5 5 5 6 5 7 0 7 5 9 0 6 0 7 5 8 0 10 0 16 0 20 0 5 5 7 0 7 5 8 0 13 0 16 0 5 0 6 0 6 5 7 0 11 0 14 0 14 0 T 20ºC ...

Страница 6: ...he optimal control of deviflex heating cables is achieved by using devireg electronic thermostat devireg thermostats give a quick and effective regulation and take into consideration both comfort and economy There are a wide variety of devireg thermostats which can be chosen according to the demands of the indi vidual installation The sensor cable can be exten ded with up to 50 m with a 0 75 mm ca...

Страница 7: ...economy If however contrary to all expecta tions a problem should occur with your heating system we at with manufacturing units in Denmark are as European Union suppliers are subject to general product liability rules as stated in Directive 85 374 CEE and all relevant national laws which implies that provides a warranty for deviflex heating cables for a 10 year period and all other products for a ...

Страница 8: ...d in See other conditions on the overleaf Cable layout contractor Cable layout contractor Lay out date Installation date Electrical Installation by Cable length Stock code Cable code Application q Pipes q Watt DEVI A S DK 7100 Vejle Phone 45 76 42 47 00 Fax 45 76 42 47 03 Internet www devi com Email Info devi com Suppliers Stamp Connection box code 08090135 01 01 ...

Отзывы: