background image

 

1

 

1.0 General Description 

 
The  Model  d-RTTI  Digital,  Room-Temperature,  Transmitter-
Indicator  is  designed  to  accurately  sense  and  display  ambient 
room  temperature  and  provide  a  4  to  20  mA  output  signal  that  is 
proportional to the measured temperature to within ±0.1 ºF. 
 
The  d-RTTI  displays  ambient  room  temperature  across  an 
operating range of -40ºF to 180ºF or -40ºC to 82ºC. The standard 
factory  configuration  scales  the  4  to  20  mA  output  signal  to 
represent  a  temperature  span  of  0  to  100ºF.  The  user  can  easily 
reconfigure  the  unit  in  the  field  by  using  the  three  push  button 
switches located on the backside of the device. 
 
A  precision  1000  ohm  RTD  sensor  is  used  to  detect  the  ambient 
temperature.  An  option  is  also  available  that  will  accept  its  input 
from an external 1000 ohm platinum RTD sensor. 
 
The  d-RTTI  operates  on  a  supply  voltage  of  10  to  28  Volts  DC. 
This  is  a  true  two  wire  device  with  signal  and  power  being 
provided over a single pair of wires. 
 
 

2.0 Physical Description 

 
The d-RTTI enclosure consists of a beige 4.7” high by 2.8” wide by 
3/8” thick plastic  plate. Captivated mounting screws  and  a  gasket 
seal  are  provided  to  attach  the  unit  to  a  single-gang  electrical 
outlet  box.  The  sealed  front  faceplate  provides  a  measure  of 
splash  resistance  for  applications  where  wash  down  is  required. 
The internal RTD temperature sensor is mounted on the backside 
of  the  black  anodized  aluminum  heatsink  that  protrudes  from  the 
front  of  the  unit.  The  heatsink  ensures  temperature  compliance 
with  the  ambient  environment.  The  temperature  is  indicated  on  a 
seven-segment,  0.4-inch  high,  red  LED  display,  with  a 
temperature resolution of one tenth of a degree. The three buttons 
labeled 

FUNC

INCR

,  and 

NEXT

  are  located  on  the  backside  of 

the  d-RTTI  and  allow  the  user  to  set  the  operating  parameters. 
Compression  screw-terminals  on  the  rear  provide  connection 
points  for  the  4  to  20mA  output  wires  and  the  optional  remote 
sensor. 

Refer to figures 1 and 2.

 

Содержание d-RTTI

Страница 1: ...DEVAR Inc Model d RTTI User Manual ...

Страница 2: ...erview of how to configure and operate this device The Model d RTTI includes the following features 4 Digit Red LED Temperature Display Fahrenheit or Centigrade Operating Modes 40 to 180 ºF or 40 to 82 ºC Operating Ranges Precision RTD Temperature Sensor Field Configurable 4 20 mA Temperature Output True 2 Wire Operation Push Button Configuration Fits Standard Single Gang Electrical Outlet Box Spl...

Страница 3: ... 4 1 Using the Buttons 3 4 2 Select Temperature Scale 3 4 3 Set Top of Range 3 4 4 Set Bottom of Range 3 4 5 Set Offset 4 5 0 Error Messages 4 6 0 Specifications 4 Illustrations Fig 1 General Dimensions 6 Fig 2 Rear Panel Wiring 7 Fig 3 Option H gray painted die cast aluminum housing 8 Fig 4 Configuration Flowchart 9 ...

Страница 4: ...ue two wire device with signal and power being provided over a single pair of wires 2 0 Physical Description The d RTTI enclosure consists of a beige 4 7 high by 2 8 wide by 3 8 thick plastic plate Captivated mounting screws and a gasket seal are provided to attach the unit to a single gang electrical outlet box The sealed front faceplate provides a measure of splash resistance for applications wh...

Страница 5: ...ns for approximately five seconds The unit will enter the startup sequence by lighting all segments 8 8 8 8 and then displaying COnF Pressing any button at this point will produce the first Configuration Prompt on the list of configurable operating parameters below Configuration Parameters Prompt Operation Selects whether the temperature will be displayed in ºF or ºC Selects the temperature value ...

Страница 6: ...n use the INCR or NEXT button to toggle between the two choices Press the FUNC button again to enter the selection and move on to the next prompt 4 3 Set Top of Range The Top of Range function is used to set the temperature value that corresponds to an output signal of 20 milliamps At the HI prompt press the FUNC button to select the item A four digit number will appear with the leftmost digit bli...

Страница 7: ...ument will cause Err to be displayed and the unit will return to the edit screen so that the number can be re entered Setting the 4 to 20 mA output span span HI LO to a value of less than 35 ºF or 20 ºC will cause SPAN Err to be displayed press any button to return to the HI prompt so that the error can be corrected Setting the OFFS value to a number greater than 10 will cause Err to be displayed ...

Страница 8: ... of Span per 300 Ohm Change DEFAULT CALIBRATION Display 40 to 180 ºF Loop 4 to 20 mA Represents 0 to 100 ºF FIELD CALIBRATION Display 40 to 180 ºF or 40 to 82ºC Output Loop The HI and Lo Milliamp outputs must be set to represent temperatures within the displayable range 40 to 180 ºF or 40 to 82ºC Output Limits Maximum milliamp span 220 ºF or 122 ºC Minimum milliamp span 35 ºF or 20 ºC Maximum offs...

Страница 9: ...6 0 760 4 700 GASKET SCREW RETAINER HEATSINK 0 375 1 2 2 800 3 9 32 PLATE Figure 1 General Dimensions ...

Страница 10: ...7 LOAD LOAD POWER SUPPLY REMOTE RTD OPTION R REMOTE SENSING PS PS SPARE NEXT FUNC INCR Figure 2 Rear Panel Wiring ...

Страница 11: ...8 SWIVEL LUG HOLE DIA 0 25 2 55 1 2 NPT PORT THREE PLACES TOP BOTTOM AND CENTER BACK INCLUDES TWO 1 2 NPT PLUGS Figure 3 Option H gray paint die cast aluminum housing ...

Страница 12: ... OPERATING MODE PRESS AND HOLD FUNC INCR AND NEXT FOR 5 SECONDS SET TEMPERATURE SCALE SET 20 mA TEMPERATURE SET 4 mA TEMPERATURE USE INCR TO EDIT FLASHING DIGIT USE NEXT TO SELECT DIGIT USE FUNC TO ACCEPT USE INCR TO EDIT FLASHING DIGIT USE NEXT TO SELECT DIGIT USE FUNC TO ACCEPT USE INCR TO EDIT FLASHING DIGIT USE NEXT TO SELECT DIGIT USE FUNC TO ACCEPT SET TEMPERATURE OFFSET FUNC INCR and NEXT F...

Страница 13: ... at its discretion repair or replace the defective item at no charge to the customer Products that are damaged by accident misuse fire water lightning or other acts of nature are not covered under this warranty Also not covered is damage due to shipping installation incorrect wiring or any other cause not related to a product defect Unauthorized product modification repair or attempted repair or s...

Страница 14: ...Blank page ...

Страница 15: ...Blank Page ...

Страница 16: ...DEVAR INC 706 Bostwick Ave Bridgeport Ct 06605 USA 800 566 6822 www devarinc com MODEL d RTTI Rev A ...

Отзывы: