12 Error handling
12.1 Error handling at UNIGATE RS
If the gateway detects an error, the error is signalled by the “State“ LED lighting red and, simulta-
neously, the error number being indicated by means of LEDs “Error No.“ as shown in the table
below. In addition, this error number is transferred as an external diagnostic byte via the Profibus
to the Master. A distinction can be made between two error categories:
Serious errors (1-5): In this case, the gateway must be switched off and switched back on again.
If the error occurs again, the gateway must be exchanged and returned for repair.
Warnings (6-15): These warnings are displayed for one minute simply for information purposes
and are then automatically reset. If such warnings occur frequently, please inform After-Sales
Service.
For user-defined errors the flash frequency is 1 hertz.
In the configuration mode these displays are not valid and only meant for internal use.
Table 1: Error handling at UNIGATE RS
12.2 Error handling at UNIGATE SC
If the gateway detects an error, the error is signalled by the “State“ LED lighting red and, simulta-
neously, the error number being indicated by means of LEDs “Error No.“ as shown in the table
below. In addition, this error number is transferred as an external diagnostic byte via the Profibus
to the Master. A distinction can be made between two error categories:
Serious errors (1-5): In this case, the gateway must be switched off and switched back on again.
If the error occurs again, the gateway must be exchanged and returned for repair.
Warnings (6-15): These warnings are displayed for one minute simply for information purposes
and are then automatically reset. If such warnings occur frequently, please inform After-Sales
Service.
For user-defined errors the flash frequency is 0.5 hertz. The error is displayed as long as defined
by "Set Warning Time".
LED8 LED4 LED2 LED1
Error no.
resp. ID
Error description
0
0
0
0
0
Reserved
0
0
0
1
1
Initialisation error of the RS485/RS232 interface
0
0
1
0
2
EEROM error
0
0
1
1
3
Stack error
0
1
0
0
4
Hardware fault of the fieldbus ASIC
0
1
0
1
5
Configuration error of the gateways (unknown protocol)
0
1
1
0
6
Reserved
0
1
1
1
7
RS485/RS232 transmit buffer overflow
1
0
0
0
8
RS485/RS232 receive buffer overflow
1
0
0
1
9
Time-out on reception RS485/RS232 interface
1
0
1
0
10
Transmit error of the RS485/RS232 interface
1
0
1
1
11
Parity- or frame-check-error
1
1
0
0
12
Addressing error of the RS485/RS232 interface
1
1
0
1
13
Configuration error by Profibus Master
1
1
1
0
14
General error of the RS485/RS232 interface
1
1
1
1
15
Internal error