17.7.17
UNIGATE
®
fieldbus gateway UNIGATE
®
MB - EtherCAT
®
V. 1.4
25
Deutschmann Automation GmbH & Co. KG
Implemented protocols in UNIGATE® MB
Display of the data in the Modbus Master (FC1):
Example: StartAddress 0008, Length 80, FC2 (Read Input Status)
[01] [02] [00] [07] [00] [50] [c9] [f7]
UNIGATE
®
sends response via RS232/485:
[01] [02] [0a] [02] [03] [04] [05] [06] [07] [08] [00] [00] [00] [8f] [7a]
8.7.1.2
Example: FC3 (Read Holding Register) + FC4 (Read Input Register)
Fieldbus sends to the UNIGATE
®
00 30 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 20 20 20...
(The configuration is "Data exchange = On Trigger", with an additonal 1. control byte in the field-
bus data.)
„Fieldbus length byte = active“, in this example 30h (48d), the UNIGATE
®
copies the following 48
Byte from the fieldbus into the internal storage.
Connected Modbus Master sends request to the RS232/484 side of the UNIGATE
®
[01] [03] [00] [00] [00] [14] [45] [c5]
UNIGATE
®
sends response via RS232/485:
[01] [03] [28] [02] [03] [04] [05] [06] [07] [08] [09] [0a] [0b] [0c] [0d] [0e] [0f] [10] [11] [12] [13] [14]...
... [15] [16] [17] [18] [19] [1a]
Display of the process data in the Modbus Master:
8.7.1.3
Example: Write Single Coil FC5
The Fieldbus Master sent the following data to the UNIGATE
®
once:
07 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 20 20 20...