21.4.15
Instruction manual UNIGATE
®
IC - RS V. 2.8
48
Deutschmann Automation GmbH & Co. KG
Appendix
Attention:
In case the RS-interface is NOT potentially divided, "GND" and "supply
0V" are connected internally.
Pin assignment P2 (2-pin screw-type/plug connector)
Pin No.
Name
Function
1
10.8...30 V / DC
10.8...30 V supply voltage
2
0 V / DC
0 V supply voltage
14.2.2.2
RS fieldbus connector
The connector for the connection to the fieldbus is located on the upper side of the device.
Pin No.
Name
Function
1
-
2
RS485-/Tx422-
When using RS485 this line has to be bridge-connected
with pin 6 (Rx 422-).
3
RS485+/Tx422+
When using RS485 this line has to be bridge-connected
with pin 7 (Rx 422+).
4
Tx232
5
RSGND
Ground connection, reference for PIN 2, 3, 4, 6, 7 + 9
6
Rx422-
7
Rx422+
8
-
9
Rx232
Pin assignment P10 (9-pin D-SUB, socket)
14.2.2.3
Power supply of the basis board
The device must be powered with 10.8-30 VDC. The devices of the series UNIGATE
®
with 9-pin
D-SUB connector, the power supply is routed via the separate 2-pin screw-type/plug connector.
Please pay attention to the fact that devices of the series UNIGATE
®
cannot be operated with AC
voltage.
14.2.2.4
Shield terminal lead
The shield signal for the electronic circuitry is connected to the DIN-rail via the connector pro-
vided.
14.2.2.5
Rotary coding switches
The rotary coding switches are socketed and can be taken off, in order to alternatively use the
pins of the shift register.
14.2.2.6
Slide switch (RS485/RS232 interface)
This slide switch is used to select whether an RS485 interface or an RS232 interface is con-
nected at the connector to the external device.
8
Not connected
Not connected
9
Rx / Diag
Receive signal Debug interface
Содержание UNIGATE IC-RS
Страница 5: ...Deutschmann Automation GmbH Co KG 5 Instruction manual UNIGATE IC RS V 2 8 21 4 15...
Страница 7: ...Deutschmann Automation GmbH Co KG 7 Instruction manual UNIGATE IC RS V 2 8 21 4 15...
Страница 27: ...Script and configuration Deutschmann Automation GmbH Co KG 27 Instruction manual UNIGATE IC RS V 2 8 21 4 15...
Страница 51: ...Appendix Deutschmann Automation GmbH Co KG 51 Instruction manual UNIGATE IC RS V 2 8 21 4 15...
Страница 52: ...21 4 15 Instruction manual UNIGATE IC RS V 2 8 52 Deutschmann Automation GmbH Co KG Appendix...
Страница 57: ......
Страница 58: ......