![DEUTSCHMANN AUTOMATION UNIGATE IC-DeviceNet Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/deutschmann-automation/unigate-ic-devicenet/unigate-ic-devicenet_instruction-manual_2488409037.webp)
Error handling at UNIGATE® IC
Deutschmann Automation GmbH & Co. KG
37
Instruction manual UNIGATE
®
IC - DeviceNet V. 4.0
9.2.22
10 Error handling at UNIGATE
®
IC
A distinction can be made between two categories of system-errors:
Serious errors (1-4): In this case, the Gateway must be switched off and switched back on again.
If the error occurs again, the Gateway must be exchanged and returned for repair.
Warnings (6-15): These warnings are displayed for one minute simply for information purposes
and are then automatically reset. If such warnings occur frequently, please inform After-Sales
Service.
The system-error can be read-out via the Script.
Error no. Error description
0
Reserved
1
Hardware fault
2
EEROM error
3
Internal memory error
4
Fieldbus hardware error or wrong Fieldbus-ID
5
Script error
6
Reserved
7
RS-transmit buffer overflow
8
RS-receive buffer overflow
9
RS timeout
10
General fieldbus error*
11
Parity-or frame-check-error
12
Reserved
13
Fieldbus configuration error
14
Fieldbus data buffer overflow
15
Reserved
Table 1: Error handling at UNIGATE
®
IC
Flashing frequency 2 times per second (system error)
*) The system-error 10 is always displayed when one of the following errors appears:
Error
Error value
DUP_MAC_ERROR
0x0001
RX_QUEUE_OVERRUN
0x0002
TX_QUEUE_OVERRUN
0x0004
IO_SEND_ERROR
0x0008
CAN_BUS_OFF
0x0010
CAN_OVERRUN
0x0020
EXPL_CNXN_TIMEOUT 1)
0x0040
IO_CNXN_TIMEOUT
0x0080
IO_CNXN_DELETE
0x0100
DNS_RESET
0x0200
DNS_BUS_SENSE_ERROR
0x0400
1) Timeout = Expected Packed Rate * 4!
With the Script command "
Get (DetailErrorCode, w_Error)
" the above value can be
read out and with it it can be exactly determined, what error was the actuator.
Содержание UNIGATE IC-DeviceNet
Страница 2: ...Manual Art No V3289E...
Страница 3: ......
Страница 7: ...Deutschmann Automation GmbH Co KG 7 Instruction manual UNIGATE IC DeviceNet V 4 0 9 2 22...
Страница 9: ...Deutschmann Automation GmbH Co KG 9 Instruction manual UNIGATE IC DeviceNet V 4 0 9 2 22...
Страница 21: ...Hardware design Deutschmann Automation GmbH Co KG 21 Instruction manual UNIGATE IC DeviceNet V 4 0 9 2 22...
Страница 47: ...Servicing Deutschmann Automation GmbH Co KG 47 Instruction manual UNIGATE IC DeviceNet V 4 0 9 2 22...
Страница 48: ......