2.10.19
UNIGATE
®
CX V. 1.4
49
Deutschmann Automation GmbH & Co. KG
Installation guidelines
11.2.2.6 LONWorks
This interface is located on the module in the form of a 4-pin screw-plug-connector on the lower
side of the housing.
•
Plug the LONWorks connecting plug onto the socket labelled "LONWorks".
11.2.2.7 MPI
This interface is located on the module in the form of a 9-pin D-SUB socket on the front side of
the housing.
•
Plug the MPI-bus connector onto the D-SUB socket labelled "MPI-bus".
•
Firmly screw the securing screws of the plug connector tight using a screwdriver.
•
If the module is located at the start or end of the MPI-bus line, you must connect the bus termi-
nating resistor integrated in the Gateway. In order to do this, slide the slide switch to the posi-
tion labelled ...on...
•
If the module is not located at the start or at the end, you must set the slide switch to position
"off".
11.2.2.8 PROFIBUS DP
This interface is located on the module in the form of a 9-pin D-SUB socket on the front side of
the housing.
•
Plug the PROFIBUS connector onto the SUB-D socket labelled "PROFIBUS DP".
•
Firmly screw the securing screws of the plug connector tight using a screwdriver.
•
If the module is located at the start or end of the PROFIBUS line, you must connect the bus ter-
minating resistor integrated in the gateway. In order to do this, slide the slide switch to the posi-
tion labelled ...on...
•
If the module is not located at the start or at the end, you must set the slide switch to position
"off".
11.2.2.9 PROFINET-IO
This interface is located on the module in the form of a 8-pin RJ45 socket on the bottom side of
the housing.
•
Plug the Profinet-connector onto the RJ45 socket labelled "RJ45 PROFINET-IO" until it snaps
in.
•
Please make sure that the length of the line to the adjacent Ethernet participants does not fall
below 0.6 m.
11.2.3
Line routing, shield and measures to combat interference voltage
This chapter deals with line routing in the case of bus, signal and power supply lines, with the aim
of ensuring an EMC-compliant design of your system.