Hardware ports, switches and LEDs
Deutschmann Automation GmbH & Co. KG
26
UNIGATE
®
Feldbus-Gateway UNIGATE
®
CM - PROFIBUS V. 1.6
23.6.17
9.3.6
LED "Bus State"
Lights green
PROFIBUS in the state data exchange
Flashes green
Gateway waits for PROFIBUS communication data
Flashes green/red
Gateway waits for PROFIBUS parameter data
Lights red
General PROFIBUS error
9.4 Switches
The Gateway features 8 switches with the following functions:
Termination Rx 422
switchable Rx 422-terminating resistor for the serial interface
Termination Tx 422
switchable Tx 422- or RS485-terminating resistor for the serial
interface
Rotary coding switch S4
ID High for serial interface i. e. configmode
Rotary coding switch S5
ID Low for serial interface i. e. configmode
Termination (PROFIBUS)
switchable PROFIBUS DP-terminating resistor
Rotary coding switch High
PROFIBUS-ID (high byte)
Rotary coding switch Low
PROFIBUS-ID (low byte)
CANopen-Termination
switchable CANopen terminating resistor
9.4.1
Termination Rx 422 + Tx 422 (serial interface)
If the Gateway is operated as the physically first or last device in an RS485-bus or as 422, there
must be a bus termination at this Gateway. In order to do this the termination switch is set to posi-
tion ON. The resistor (150
) integrated in the Gateway is activated. In all other cases, the switch
remains in position OFF.
Please refer to the general RS485 literature for further information on the subject of bus termina-
tions.
If the integrated resistor is used, please allow for the fact that this also activates a pull-down
resistor (390
) to ground and a pull-up resistor (390
) to VCC.
At RS48 only the Tx 422-switch must be set to ON.
The Rx 422-switch has to be on OFF.
9.4.2
Rotary coding switches S4 + S5 (serial interface)
These two switches can be read out through the Script command "
Get (RS_Switch,
Destination)
" and the value can be used for further functions. This value is read in when the
Gateway is switched on or always after a Script command has been executed. The switch
positions "EE" (testmode) and "FF" (config mode) are not possible for RS422- or RS485-
operation.
The switch position "DD" (ie, S4 and S5 in position "D") is reserved for
internal purposes, Firmware-Update extension. The Gateway should only
be switched into this mode for a Firmware-Update. Otherwise the firm-
ware of the extension will be deleted and there is no access, respectively
no function of the extension anymore. For details see chapter 12.