Technical data
Deutschmann Automation GmbH & Co. KG
50
UNIGATE
®
Fieldbus Gateway UNIGATE
®
CL - MPI V. 3.1
29.6.20
15 Technical data
15.1 Device data
The technical data of the module is given in the table below.
Table: Technical data of the module
No. Parameter
Data
Explanations
1
Location
Switch cabinet
DIN-rail mounting
2
Enclosure
IP20
Protection against foreign
bodies and water to IEC 529
(DIN 40050)
4
Service life
10 years
5
Housing size
23 x 117 x 111 mm
(screw-plug-connector included)
23 x 117 x 100 mm
(screw-plug connector not included)
W x D x H
6
Installation position
Any
7
Weight
130 g
8
Operating temperature
-40ºC ... +85ºC
9
Storage/transport
temperature
-40 ºC ... +85 ºC
10
Atmospheric pressure
during operation
during transport
795 hPa ... 1080 hPa
660 hPa ... 1080 hPa
11
Installation altitude
2000 m
4000 m
Unrestricted
Restricted -
Ambient temperature
40ºC
12
Relative humidity
Max. 80 %
No condensation,
no corrosive atmosphere
14
External
power supply
10...33 V DC
Standard power supply unit to
DIN 19240
15
Current consumption at 24
VDC
Typ. 60 mA
max 70 mA
At 10.V. typ. 155 mA
16
Supply at the MPI-bus-inter-
face
5 V DC / max. 50 mA
(Max. 50 mA at < 30°C ambient
temperature)
17
Reverse voltage protection Yes
But does not function!
18
Short-circuit protection
Yes
19
Overload protection
Poly-switch
Thermal fuse
20
Undervoltage detection
(USP)
9 V DC
21
Emergency power supply
5 ms
Device fully operable