Dettson FEM10-M2301CM-B Скачать руководство пользователя страница 19

 

4

 

 

2.1 

POSITIONING THE FURNACE

 

 

WARNING 

Fire and explosion hazard. 

 

The furnace must be installed in a level position, never 
where it will slope toward the front. 

 

Do not store or use gasoline or any other flammable 
substances near the furnace 

 

Non-observance of these instructions will potentially result 
in death, bodily injury and/or property damage. 

 

CAUTION

 

This furnace is not watertight and is not designed for 
outdoor installation.  It must be installed in such a manner 
as to protect its electrical components from water. 

 

Outdoor installation will lead to a hazardous electrical 
condition and to premature failure of the equipment 

 
If the furnace is installed in a basement or on a dirt floor, in a 
crawl space for example, it is recommended to install the unit on 
a cement base 2.5 cm to 5.0 cm (1’’ to 2’’) thick. 
 
The unit must be installed in an area where the ambient and 
return air temperatures are above 15˚C (60˚F).  In addition, the 
heater should also be located close to the center of the air 
distribution system. 
 

2.2  CLEARANCES TO COMBUSTIBLE 

MATERIAL

 

 

2.2.1. Heating 

unit

 

 

The furnace is approved for zero clearance to combustible 
material regardless of the heating capacity. 

 

2.2.2. 

Supply air ducts

 

 

Ducts for furnaces with a heating capacity up to and including 
20 k W, can be installed with a zero clearance to combustible 
material. 

 

Ducts for furnaces of 23 kW or more must have a clearance of 
25 mm (1’’) to combustible material for the first 0.9 m (36’’) of 
duct.  Thereafter the clearance can be zero. 

 

Units of 23 kW and up, installed in the downflow position must 
use a DFB-FEM downflow base, which is especially designed 
for this purpose.  It ensures that the required clearances are 
being adhered to. 
 

2.3 CONFIGURATIONS

 

 

2.3.1. Upflow 

installation

 

 

The return air opening may be located on either side of the 
furnace.  Care should be taken not to damage the wires inside, 
while cutting the opening.  Install the filter rack supplied with the 
unit according to the instructions provided with it.  It is also 
recommended to install the blower door before handling or 
moving the unit.  Refer to Figure 1 for additional details. 

Figure 1 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2.3.2. Downflow 

installation

 

 

When the furnace is installed in the downflow position on a 
combustible floor, the clearances from combustibles must be 
adhered to.  The downflow base DFB-FEM can be used to 
ensure these clearances.  Refer to Figure 2 and the installation 
instructions provided with the base. 
 

Figure 2 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

2.3.3. Horizontal 

installation

 

 

When the furnace is installed in the horizontal position, either 
suspended or on a combustible floor with a choice of right or left 
discharge, the clearances from combustible material must be 
adhered to.  Refer to Figure 3 for additional details. 
 

Figure 3 

 
 
 
 
 
 
 
 
 
 
 
 

Содержание FEM10-M2301CM-B

Страница 1: ...7 M2301DM B 2011 02 04 X40163 Rev D Fabriqu par Industries Dettson inc 3400 boulevard Industriel Sherbrooke Qu bec Canada J1L 1V8 DNS 0981 Rev A MULTI POSITION INSTALLATEUR TECHNICIEN UTILISER LES REN...

Страница 2: ...DE FONCTIONNEMENT 7 3 3 UTILISATION DES COMMANDES MANUELLES SUR LA FOURNAISE 7 3 4 V RIFICATION DU D BIT D AIR 8 4 ENTRETIEN 8 4 1 FILTRE AIR 8 4 2 LUBRIFICATION DU MOTEUR 8 5 INFORMATION 9 TABLEAUX...

Страница 3: ...conforme aux codes nationaux qui s appliquent Les renseignements contenus dans ce manuel s adressent un technicien qualifi exp riment dans ce type de travail au courant des pr cautions prendre des r...

Страница 4: ...t de 0 pouce par rapport aux mat riaux combustibles Pour les fournaises d une puissance de 23 kW et plus les conduits d alimentation en air doivent tre install s avec un d gagement de 1 pouce par rapp...

Страница 5: ...rre ininterrompue pour minimiser les risques de blessures corporelles si jamais un probl me lectrique se produisait Un connecteur de mise la terre est inclus dans la bo te de contr le pour effectuer c...

Страница 6: ...es du r frig rant et de vidange ne devraient aucunement nuire l enl vement des panneaux d acc s de la fournaise 2 6 AJUSTEMENT DES D BITS D AIR DE VENTILATION Sur les unit s quip es de moteur de venti...

Страница 7: ...trique principal ON 3 2 S QUENCE DE FONCTIONNEMENT Mode chauffage 1 Le thermostat ferme le circuit R W1 et envoie un signal 24 VAC au premier relais 22 VDC en passant par un redresseur de courant Sans...

Страница 8: ...tre actionn s durant un fonctionnement normal de l appareil Ceux ci sont con us pour tre activ exceptionnellement lors d un mauvais fonctionnement du ventilateur ou lorsque le filtre air a t mal entre...

Страница 9: ...MISE EN MARCHE Voltage Courant total consomm par les l ments Temp rature de l air chaud d alimentation Temp rature de l air de retour Pression statique dans le conduit d alimentation en air Pression s...

Страница 10: ...r 2 55 80 97 107 122 111 126 147 Disjoncteur maximum du circuit Amp 2 60 80 100 110 125 125 150 150 DONN ES TECHNIQUES DU VENTILATEUR ajust en usine pour une pression statique de 0 5 W C Vit du ventil...

Страница 11: ...PCM arrondis 5 PCM le plus pr s Donn es prisent avec le filtre air install TABLEAU 3 D bit d air PCM SUPR ME avec un moteur de 1 HP 0 1 0 2 0 3 0 4 0 5 0 6 0 7 LOW 1035 1030 1030 1025 1020 1020 1015...

Страница 12: ...12 FIGURE 6 Diagramme lectrique...

Страница 13: ...13 COMPOSANTES ET PI CES DE REMPLACEMENT...

Страница 14: ...14 LISTE DE PI CES Vue explos e Supr me avec moteur 1 3 HP ou 1 0 HP FEMxx M2301CM B ou FEMxx M2301DM B B50089C dwg...

Страница 15: ...4 L05F004 BORNIER A VIS 4 POSITIONS 15 L01H009 RELAIS SPDT 24 VAC 16 L01F010 TRANSFORMATEUR 208 240 24Volts 17 L99F004 BLOC TERMINAL 18 L01H030 RELAIS DPST 22 VDC 19 R99G006 REDRESSEUR DE PUISSANCE 20...

Страница 16: ...1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician Printed in Canada Printed on 100 recycled paper DNS 0981 Rev A MULTI POSITION INSTALLER SERVICE TECHNICIA...

Страница 17: ...P 7 3 2 OPERATING SEQUENCE 7 3 3 USE OF MANUAL FURNACE CONTROLS 7 3 4 AIRFLOW VERIFICATION 8 4 MAINTENANCE 8 4 1 AIR FILTER 8 4 2 MOTOR LUBRICATION 8 5 INFORMATION 9 TABLES AND FIGURES FIGURE 1 CONFIG...

Страница 18: ...nqualified persons can result in hazards to them and to others Installations must conform to local codes or in the absence of same to codes of the country having jurisdiction The information contained...

Страница 19: ...uding 20 k W can be installed with a zero clearance to combustible material Ducts for furnaces of 23 kW or more must have a clearance of 25 mm 1 to combustible material for the first 0 9 m 36 of duct...

Страница 20: ...trol the temperature of the area to be heated Follow the instructions supplied with the thermostat Install the thermostat on an interior wall in a location where it will not be subject to direct sun l...

Страница 21: ...airflow refer to the following table as well as the airflow tables based on static pressure in the Technical Specifications section of this manual For the adjustment of the airflow on heating mode to...

Страница 22: ...RATING SEQUENCE Heating mode 1 The thermostat closes the R W1 circuit 24 VAC thereby activating the first 22 VDC relay passing by a rectifier control Without delay the first heating element is activat...

Страница 23: ...al protectors should never need to engage during the normal functioning of the appliance They are strictly designed to engage during the improper functioning of the blower or when the filter was impro...

Страница 24: ...ame and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total pres...

Страница 25: ...17 9 Circuit Amperage wire sizing 2 55 80 97 107 122 111 126 147 Maximum size circuit breaker Amp 2 60 80 100 110 125 125 150 150 BLOWER DATA factory adjusted to a staic pressure of 0 5 W C Blower spe...

Страница 26: ...5 CFM more or less These readings were taken with the air filter installed TABLE 3 Air Flow CFM SUPREME with 1 HP motor 0 1 0 2 0 3 0 4 0 5 0 6 0 7 LOW 1035 1030 1030 1025 1020 1020 1015 MED LOW 1315...

Страница 27: ...12 FIGURE 6 Wiring Diagram...

Страница 28: ...13 COMPONENTS AND REPLACEMENT PARTS...

Страница 29: ...14 PARTS LIST Exploded View SUPREME with 1 3 HP and 1 HP motor FEMxx M2301CM B and FEMxx M2301DM B B50089C dwg...

Страница 30: ...PLATE FOR ELECTRICAL SIDE 14 L05F004 TERMINAL STRIP 4 POSITION 15 L01H009 RELAY SPDT 24 VAC 16 L01F010 TRANSFORMER 208 240 24 Volts 17 L99F004 TERMINAL BLOCK 18 L01H030 SEQUENCER Please refer to Table...

Отзывы: