Detroit Radiant Products Re-Verber-Ray DTH Series Скачать руководство пользователя страница 14

Thermostat Closed, Fan Operates, No Glo-Bar Energization

 (cont.)

(This step is applicable for all models)

2.3

The 

Exhaust

 

Pressure Switch

 is located on the valve side of the heater 

(pg. 6, pic. 4)

.  

*

Bypass this switch

(pg. 21, #6)

.  If the heater works with the exhaust pressure switch bypassed, the problem is with this switch or what

it is sensing and you should continue with step 2.3.1.  If bypassing this switch does not cause the heater to work,
continue with step 2.4.

2.3a

Be sure the lid is on correctly and tightly, and the gasket is in intact.

2.3b

Check to make sure the clear vinyl or aluminum tube that bleeds pressure to the outside of the heater is
clean and clear of obstructions.

2.3c

Clean any obstructions from the emitter tube, exhaust tube and vent cap.

2.3d

Check to make sure the heater’s baffle is located properly.  It should be found at the exhaust end of the
emitter tube.

NOTE:  Excessive winds may cause properly operating safety pressure switches to shut down the heater.  Heaters ducted

through (on either the intake or exhaust sides) the roof may be deprived of the air necessary to pressurize the burner box.  This
“chimney effect” will typically not allow the burner pressure switch to close.  Heaters vented through a sidewall may see too

much back-pressure, thus opening the exhaust pressure switch.  In either case, the caps need to be shielded to lessen the effects

of high winds.

2.3e

Check to make sure the sensing tube pointed in the outlet of the fan is at the bottom of the opening 

(pg 5,

pic. 4)

2.3f

If steps 2.3a - 2.3e were performed and the heater still won’t properly function, the exhaust pressure switch
is faulty.

2.4(-2)  

(This step is applicable for non-DTHS-2 & DTHS-2 model heaters 40-100 MBTU/H).

Check the normally closed radiant sensor to see if it is stuck in the open position.  See how to 

(pg. 22, #8)

.  If stuck

open, the radiant sensor can be bypassed.  See “How To” 

(pg. 22, #7)

 to confirm that there are no other failures.

2.4(-3)  

(This step is applicable for DTHS-3 models only)

Check the 

Circuit Board (pg. 6, pic. 3)

.  Use a volt meter to ensure that power is actually entering the circuit

board.  Turn off the gas to the heater and 

*

bypass both pressure switches 

(pg. 21, #6)

, as a heater with no cover will

not allow pressure switches to function properly.  120 volts exiting the circuit board indicates that the glo-bar is
faulty.  If no voltage exits the circuit board, it is faulty.

13

Refer to warnings on cover prior to servicing the unit.  Bypass safety pressure switches for supervised troubleshooting purposes only.

*Do not leave switches bypassed while the heater is unattended or for normal operations.

Consult Detroit Radiant Products for further technical information.

Solution 2

Содержание Re-Verber-Ray DTH Series

Страница 1: ...the vicinity of this or any other appliance Note presence of flammable gas and electrical shock hazard WARNING Extinguish open flame while servicing heaters Test for gas leaks with soap and water solu...

Страница 2: ...Component Photographs Troubleshooting Flow Chart General Troubleshooting Reference Solution Chart Troubleshooting Solutions Component History Chart How To For Trouble Shooting Procedures 2 3 4 5 6 7 8...

Страница 3: ...ruments 1 4 Nut Driver Can be used to remove screws holding top on Part 5X509 from Grainger Pliers 8 Tool for burner box access Part 6C183 from Grainger Pipe Wrench 8 Can be used to disassemble gas tr...

Страница 4: ...lve is energized and opened Running Circuit When the glo bar reaches ignition temperature the radiant sensor is heated and opens maximum 60 seconds The radiant sensor is a heat sensitive bimetal switc...

Страница 5: ...flame probe As long as a flame is present the valve is held open If the flame is lost the control acts to close the valve within one second and a new trial sequence identical to that at start up is in...

Страница 6: ...DTHS 3 Series Heater DTHS 2 Series Heater 5 Burner Unit Photographs...

Страница 7: ...his symbol appears when directions indicate the presence of flammable gas This symbol appears when directions indicate the presence an electrical shock hazard Gas Cock Regulator Air Intake Collar Orif...

Страница 8: ...Are they ok Repair wiring or hose connections Remove obstruction Is the model in question equipped w 2 switches Replace the door switch Temporarily place jumpers on switch Does ignitor glow red If the...

Страница 9: ...734 ohms Check to make sure that the gas pressure is within minimum and maximum inputs as indicated on AGA burner rating label Is gas pressure ok Replace valve Replace radiant snesor Does the burner s...

Страница 10: ...sensor 4 Low gas pressure 1 Polarity reversed 2 No electrical ground 3 Faulty circuit control 4 Low gas pressure 5 Glo bar faulty 6 Faulty exhaust switch 1 Polarity reversed 2 No electrical ground 3 F...

Страница 11: ...Clean 1 Assure that tube is fully inserted into flared end and properly clamped 2 Replace 1 Shorten stack 2 Minimum of 26 gauge vent pipe is required 3 Provide fresh air inlet duct 1 Provide 2 sq in...

Страница 12: ...ced If power is at the heater continue on to the next step 1 3 Check the electrical connections leading to the fan Be sure that the wire nuts are tight 1 4 Using the voltmeter check to be sure power i...

Страница 13: ...or exhaust sides the roof may be deprived of the air necessary to pressurize the burner box This chimney effect will typically not allow the burner pressure switch to close Heaters vented through a s...

Страница 14: ...ee too much back pressure thus opening the exhaust pressure switch In either case the caps need to be shielded to lessen the effects of high winds 2 3e Check to make sure the sensing tube pointed in t...

Страница 15: ...oes not work the valve is faulty and must be replaced 3 1a Be sure the radiant sensor MICA is clean and intact 3 1b Check to make sure the glass on the underside of the radiant sensor is clear and not...

Страница 16: ...ressure entering the system may be too high The maximum value for both natural and propane is 14 W C P Correct this problem by either adjusting the building s regulator down to 14 W C P or by using st...

Страница 17: ...hin the heater or the circuit board may be faulty 6 4 The gas pressure is too low Check the manifold pressure pg 6 pic 6 pg 21 2 for appropriate pressure 6 5 The glo bar may be cracked pg 6 pic 7 Chec...

Страница 18: ...Be sure the fan is clean and able to supply the appropriate amount of air to the heater Clean any obstructions from the air intake pipe and cap Clean the squirrel cage Oil the motor SAE 20 Examine an...

Страница 19: ...ng it to burn hotter than normal Be sure there is nothing blocking the air intake and that the fan is clean pg 6 pics 5 8 11 2 Contaminated combustion air could alter the flame characteristics overhea...

Страница 20: ...Example high winds bird nest snow etc Solution15 Odor or Fumes Present in Space Odors present in the space being heated may be caused by a variety of products being used stored or processed in the spa...

Страница 21: ...60A TP 64 TP 50 N TP 33 P TP 33P TP 36 N 3 8 P 10 0 DTH TP 8B 100MBH N AND BELOW TP 8D 100MBH P DTHS 16 INCH TUBE TP6A 10 FOOT TUBE TP26A 100MBH N AND BELOW TP 26B 100MBH P DTH S 2 APR 92 TO JAN 00 T...

Страница 22: ...one probe and the green wire with the other confirm 120V Using a voltmeter touch the white wire with one probe and the green wire with the other confirm 0 0V If the previous step confirmed 120V the po...

Страница 23: ...meter measure across the normally closed switch if it is open then the radiant sensor is bad 9 Ohming out the WR 25K valve Turn off the power to the heater Remove the cover on the radiant sensor box D...

Страница 24: ...tached Install the new center panel using the old screws Rewire the heater according to the wiring diagram on page 3 On the front panel of the burner box same side that the emitter tube is attached to...

Отзывы: