5
DX2
Series
Model Number
Mounting
Angle*
Side
Top
Below
Front
Behind
DX2 (20, 30, 40) - 50, 60 [N, P]
0°
9
9
6
47
45°
39
8
10
47
with 1 side shield
0°
29
8
6
47
with 2 side shields
0°
9
9
6
47
20 ft. from burner
0°
7
7
6
30
DX2 (20, 30, 40) - 75 [N, P]
0°
9
9
6
60
45°
39
8
10
60
with 1 side shield
0°
29
8
6
60
with 2 side shields
0°
9
9
6
60
20 ft. from burner
0°
7
7
6
30
DX2 (20, 30, 40, 50) - (80, 100) [N, P]
0°
14
14
6
66
45°
39
8
10
66
with 1 side shield
0°
29
8
6
66
with 2 side shields
0°
16
16
6
66
20 ft. from burner
0°
7
7
6
30
DX2 (30, 40, 50, 60) - 125 [N, P]
0°
20
20
6
76
45°
58
8
10
76
with 1 side shield
0°
42
8
6
76
with 2 side shields
0°
20
20
6
76
20 ft. from burner
0°
7
7
6
30
DX2 (40, 50, 60) - 150 [N, P]
0°
24
24
6
81
45°
58
8
10
81
with 1 side shield
0°
42
8
6
81
with 2 side shields
0°
23
23
6
81
20 ft. from burner
0°
11
11
6
44
DX2 (40, 50, 60, 70) - 175 [N, P]
0°
34
34
6
92
45°
63
8
10
92
with 1 side shield
0°
50
8
6
92
with 2 side shields
0°
30
30
6
92
20 ft. from burner
0°
11
11
6
44
DX2 (50, 60, 70, 80) - 200 [N, P]
0°
41
41
6
94
45°
63
8
10
94
with 1 side shield
0°
54
8
6
94
with 2 side shields
0°
30
30
6
94
20 ft. from burner
0°
11
11
6
44
1.0
Safety
• Clearance to Combustibles
Chart 1.1 •
Clearance to Combustibles in Inches
(see Figure 1.1 for Mounting Angles)
Figure 1.1
•
Mounting Angles
0° Mounting Angle
45° Mounting Angle
0° Mounting Angle
with 1 Side Shield
(P/N: SSE)
0° Mounting Angle
with 2 Side Shields
(P/N: SSE)
Side
Side
Below
Top
Front
Behind
Below
Top
Front
Behind
Below
Top
Side
Side
Below
Top
Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.
*